Download Print this page

VersaMax GFK-1551D Quick Start Manual

Network interface unit

Advertisement

Quick Links

October 2000
Preinstallation Check _____________________________
Carefully inspect all shipping containers for damage. If any equipment
is damaged, notify the delivery service immediately. Save the damaged
shipping container for inspection by the delivery service. After
unpacking the equipment, record all serial numbers. Save the shipping
containers and packing material in case it is necessary to transport or
ship any part of the system.
Quick Start Guide ________________________________
1.
Install the NIU on the DIN Rail by simply clicking it into place.
(Refer to the heading Module Installation for information about
space requirements or module orientation, or if you are installing
the NIU in an area of excessive vibration).
2.
Install the Power Supply on the NIU.
The latch on the power supply must be
in the unlocked position.
Align the connectors and the latch post
and press the power supply module
down until the two tabs on the bottom of
the power supply click into place.
Turn the latch to the locked position to
secure the power supply to the top of the
NIU.
Complete the power supply wiring as described in the installation
instructions provided with the Power Supply.
3.
Adjust the rotary switches on the front of the NIU using a
2.44mm (3/32in) flat screwdriver.
0
U
A
N
0
9
8
7
6
5
0
N
§
Select the serial bus address with the two upper rotary
switches, SBA X10 (for the tens digit) and SBA X1(for the
ones digit). Each device on a bus must have a unique serial
bus address in the range 0 - 31.
§
Select the baud rate to match that used by the other devices
on the bus by setting the bottom rotary switch: (3) 153.6
Kbaud extended, (2) 153.6 Kbaud standard, (1) 76.8 Kbaud,
or (0) 38.4 Kbaud.
§
Cycle power to the NIU after changing the switch settings.
Network Interface Unit
Note: The NIU and connecting carriers
must be installed on the same section
of 35mm x 7.5mm DIN rail.
The DIN rail must have a conductive
(unpainted) finish for proper grounding.
1
2
SBA
3
X10
1
2
SBA
3
X1
4
1
2
BAUD
3
RATE
4.
Connect the communications bus to the NIU. (Refer to the
heading Bus Installation Guidelines if the NIU is at the end of the
bus, or for detailed bus installation instructions.)
SERIAL A1
SERIAL A2
Main Bus
SHIELD IN
Connections
SHIELD OUT
SERIAL B1
Redundant
SERIAL B2
Connections
SHIELD IN
SHIELD OUT
5.
Remove the connector cover on the righthand side of the
NIU. Do not discard this cover; you will need to install it on the last
carrier. It protects the connector pins from damage and ESD during
handling and use. Do not remove the connector cover on the
lefthand side.
Connector Cover
6.
Install additional modules by mounting modules on their carriers
and sliding them along the DIN rail to fully engage the connectors in
the sides of the carriers.
7.
Power up the NIU. The modules in the I/O station will automatically
be configured, starting at slot 1 in each rack including expansion
racks. If an empty slot or faulted module is encountered,
autoconfiguration for that rack stops. Autoconfiguration then skips to
the next rack and continues until all racks are configured.
Note: If the I/O station includes any additional power supplies, those
power supplies should be turned on at the same time.
8.
Observe the NIU LEDs, which indicate the presence of power and
show the operating mode and status of the NIU.
PWR
PWR
OK
OK
FAULT
I/O ENBL
FAULT
FORCE
SBA ERR
I/O ENBL
BUS B
FORCE
SBA ERR
BUS B
1
GFK-1551D
The NIU has two sets of bus
terminals. The upper terminals are
for the main bus cable. The lower
bus terminals are for an optional
redundant (dual) bus cable.
Connector Cover
Indicates that the NIU is receiving
power.
Indicates diagnostics executed
successfully.
Is ON if there are one of more
faults.
This bicolor LED is green if the I/O
scan is enabled and data is being
received from the bus. Otherwise,
this LED is amber.
Is ON if one of more I/O points is
forced.
Is ON if a duplicate device SBA or
invalid SBA exists.
Is ON if bus B is active.

Advertisement

loading

Summary of Contents for VersaMax GFK-1551D

  • Page 1 Network Interface Unit October 2000 GFK-1551D Preinstallation Check _____________________________ Connect the communications bus to the NIU. (Refer to the heading Bus Installation Guidelines if the NIU is at the end of the Carefully inspect all shipping containers for damage. If any equipment bus, or for detailed bus installation instructions.)
  • Page 2 Network Interface Unit October 2000 GFK-1551D Bus Installation Guidelines ________________________ General Module Installation Instructions______________ The maximum exposed length of unshielded wires should be 5cm (2in). For added protection, each shield drain wire should be insulated with Modules may be mounted on a spaghetti tubing to prevent the Shield In and Shield Out wires from horizontal or vertical DIN rail.
  • Page 3 Network Interface Unit October 2000 GFK-1551D Compatibility _________________________________ Product Description ______________________________ Any type of PLC or computer capable of controlling the bus can be used Revision Letters: as the host. This Network Interface Unit is compatible with: § Firmware version: 2.00...
  • Page 4 Network Interface Unit October 2000 GFK-1551D § In an local system, the NIU rack and the expansion rack may be on RS-485 Differential Expansion System different power supplies if desired. If so, on a single-ended or differential system, disconnecting the cable between the A multi-rack expansion system requires an Expansion Transmitter NIU/transmitter and receivers may cause disruptions on the bus.