Download Print this page

olympia electronics ZLD-28/EM/ADR Quick Start Manual

Advertisement

Quick Links

Dimensional Drawings (mm)
172
242 295
290
350
450
36
50
100
182
46
44
70
Battery Replacement
It can be done only by a competent person and after the mains interruption.
1 1
2 2
Remove the old battery and place a new one of the same type and characteristics and
assembly the luminaire.
WARNING!! Use a maximum torque of 0,25Νm to tighten the screws.
NOTE: LED= Light Emitting Diode
LABELING EXPLANATION:
X: Self contained
1: Maintained operation (*)
A: Including test device
B: Including remote test mode
C: Including inhibiting mode
G: Internally illuminated safety sign
180: 3 hours duration
X
1
A B C G
1 8 0
(*) Maintained operation: The luminaire lights its illumination source, when it is powered
by the mains power supply or not.
Non Maintained operation: The luminaire lights its illumination source, only in mains
power supply's failure.
ATTENTION!!!
The light source of this luminaire is not replaceable when the light source reaches
its end of life the whole luminaire shall be replaced.
4
Technical Characteristics
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
SUPPLY CURRENT
U-OUT
EOFi
WIRE CROSS SECTION
BATTERY (Ni-MH)
INSULATION BETWEEN SUPPLY & BATTERY CIRCUIT
BATTERY PROTECTION
MIN MAX. DISCHARGE VOLTAGE
MIN MAX. DISCHARGE CURRENT
Rated CURRENT @3.6V
MIN MAX. CHARGE CURRENT
38
MAX CHARGE VOLTAGE
INDICATIONS
CHARGE TIME
MINIMUM DURATION
ZLD-28/EM/ADR: 290 x 38 x 172mm
LIGHT SOURCE
LIGHT SOURCE LUMINOUS FLUX (MAINS / EMERGENCY)
DEGREES OF COVER PROTECTION
ZLD-34/EM/ADR: 350 x 38 x 242mm
PRODUCED IN ACCORDANCE WITH
ZLD-44/EM/ADR: 450 x 38 x 295mm
VIEWING DISTANCE
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIAL
EXTERNAL DIMENSION (L x W x H)
WEIGHT
GUARANTEE
CONTROL GEAR WITH AUTOMATIC
TEST FUNCTION
Controlgear classification in accordance with IEC 62034: with automatic test function
The controlgear is suitable for LED modules only
The controlgear has mains-connected windings of transformer
The controlgear is proof against supply voltage polarity reversal
The lamp controlgear relies upon the luminaire enclosure for protection against accidental contact with live part (7.2 BS EN 61347-2-7)
Integrated SPD
LED Characteristics
MANUFACTURER
MODEL NUMBER
VOLTAGE RANGE
NOMINAL POWER
CONNECTIONS
TEMPERATURE (tc)
Warranty
Olympia Electronics guarantees the quality, condition and operation of the goods. The period of warranty is
specified in the official catalogue of Olympia Electronics and also in the technical leaflet, which accompanies
each product. This warranty ceases to exist if the buyer does not follow the technical instructions included in
official documents given by Olympia Electronics or if the buyer modifies the goods provided or has any
repairs or re-setting done by a third party, unless Olympia Electronics has fully agreed to them in writing.
Products that have been damaged can be returned to the premises of our company for repair or
replacement, as long as the warranty period is valid.
Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the
buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the
buyer the transportation cost.
5
922502862_09_009
ZLD-28/EM/ADR
ZLD-34/EM/ADR
ZLD-44/EM/ADR
220-240V AC / 50-60Hz
3.8W / 6.5VA
4W / 6.7VA
28mA
29mA
19V
1.3
0.60
2
2
0.3mm - 3.3mm (22-12AWG)
3.6V / 1.5 Ah
Basic insulation
Deep discharge and overcharge protection / the control gear will recharge the battery normally after the test of 22.3
3 - 4.2V
270 - 360mA
270 - 370mA
310mA
315mA
140 - 165mA
5V
LED Charge, Lamp Fault LED, Battery Fault LED
24 hours
3h
18 white LEDs
21 white LEDs
24 white LEDs
125lm/125lm
145lm/125lm
170lm/125lm
IP40
EN 60598-1, EN 60598-2-22, ΕΝ 55015,
ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
16m
30m
o
5 to 40 C
Up to 95%
Aluminum, Acrylic Plate, ABS/PC
290 x 38 x 172 mm
350 x 38 x 242 mm
450 x 38 x 295 mm
780gr.
1145gr.
3 years (1 year for the battery)
ZLD-28/EM/ADR
ZLD-34/EM/ADR
ZLD-44/EM/ADR
Olympia Electronics S.A.
1111153
1211153
8.5- 10.5V DC
1200mW
1400mW
Non reversible connection between main pcb and led module
45 °C max. across the board
72nd km. O.N.R. Thessaloniki-Katerini
P.C. 60300 P.O. Box 06 Εginio Pierias Greece
www.olympia-electronics.com
info@olympia-electronics.gr
Warranty
922502862_09_009
European
manufacturers
4.3W / 6.9VA
30mA
0.62
255 - 360mA
290mA
38m
1585gr.
ZLD-XX/EM/ADR
ADDRESSABLE
SELF TESTING MAINTAINED
1311153
EMERGENCY ILLUMINATION SIGNS
1600mW
Μ
NM
Non
IP40
16m
Maintained
maintained
Thank you for your trust in our products
Olympia Electronics - European manufacturer
ADR
Duration
Light output
Battery
30m
38m
3h
125/145/170lm
Ni-MH

Advertisement

loading

Summary of Contents for olympia electronics ZLD-28/EM/ADR

  • Page 1 B: Including remote test mode replacement, as long as the warranty period is valid. Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the C: Including inhibiting mode buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the G: Internally illuminated safety sign buyer the transportation cost.
  • Page 2 Manual Operational Test By pressing the test button an operation The luminaires can be connected to the test is initiated. The light source and the addressable panels of Olympia Electronics. Power Connection Communication Connection emergency circuit of the device are tested.

This manual is also suitable for:

Zld-34/em/adrZld-44/em/adr