Page 1
G-LMS-188-4P February, 2021 LMS-188-4P 4 POINT DIGITAL MONITOR/ALARM OPERATING INSTRUCTIONS WARNING: This product can expose you to chemicals including lead, which is known to the State of California to cause cancer. For more information, go to www.P65Warnings.Ca.gov 1360 Elmwood Avenue...
Front Panel The Multi-Probe Alarm System front panel consists of the following: Graphic LCD Channel Status LEDs (STATUS) Alarm LED (ALARM) Audible alarm indicator (buzzer) Buttons o Test & Reset (TEST/RESET) o Step button (STEP) o Alarm Limits &...
Probe Installation RTD sensors supplied with the LMS-188-4P should be installed using the supplied fittings, which are 1/2” MNPT x 1/8” compression. After installing the fitting into a tee, insert the RTD into the fitting and adjust the depth of the probe so as the tip of the probe is approximately at the center of the piping.
Alarm Conditions / Temperature Alarms If the readings are within the alarm limits, the STATUS LED will blink green. When the temperature reading meets or exceed the temperature limits the STATUS LED will blink red. After the probe’s alarm delay time is exceeded the unit will blink the ALARM LED and beep the buzzer.
LMS Email Notification Feature The LMS sends email on unit reset, alarm, continued alarm and recovery from alarm. The unit sends email 5 minutes after email failure and repeats every 10 minutes after that. Once daily, it sends a report of the last 24 hours that includes temperatures on the hour and alarms to contact #1.
Page 7
IP1, IP2 and IP3 from the LMS unit. For IP4, enter any combination of numbers, 1-3 digits long. Just be sure it is not the same as LMS-188-4P. Subnet Mask is 255.255.255.0 and the Default Gateway is left blank.
Page 8
[Setup page – "initial setup"] [Access by adding "setup.html" to the IP] [ User: setupadmin (not editable, case sensitive) Password:<5-digit code from LMS>] Gateway on Setup Page MUST match the Gateway of the network that is utilized. See Network administrator for DNS Server & SMTP information. If these parameters are unavailable, use 8.8.8.8 for DNS Server, smtp.1and1.com for SMTP Server, t140@hampshirecontrols.com for SMTP auth...
Page 9
Defaults: Setup Administrator setupadmin *this is coded into the firmware and is not editable Setup Password -22718 *use LMS NetworkCode as password List Administrator listadmin List Password idoemaillist Please define: LMS: IP (IP1, IP2, IP3, IP4) NetworkCode: number –30000 to 30000 Setup: Subnet Mask SMTP Server Gateway...
LMS Overview Buttons: TEST/RESET, STEP, DOWN, UP, MUTE/MENU Runtime Display 8.9'C 8.4'C Edit Parameters At Runtime tap MENU Repeat MENU, MENU,.. To Edit Limits , Edit Times , Return to Runtime or while in Edit tap MENU AND RESET simultaneously to access Edit Limits *SETUP* group 1 Low...
Min/Max Temperatures Display Min/Max Reset *while viewing Min or Max At Runtime tap UP tap RESET Min & Max ActualMin 3.1’C Reset ActualMax 6.8’C RESET to confirm ActualMin 3.6’C STEP to cancel ActualMax 6.6’C Relay Test At Runtime tap TEST Relay Test Relay Test * seconds counting down...
Page 12
RESET. A dead battery may prevent proper operation of the Alarm Delay Module. This is the hookup from a relay (contact) output of an LMS-188-4P, or other device, to the RDU. Use the slide switch on the main board to choose N.O. or N.C. input.
The primary application is in systems where it is desirable to control an AC powered solenoid in the event that the alarm on the LMS-188-4P is active. When in non-alarm condition the relay is in a N.O. state and the solenoid will allow water to flow through it freely.
The primary application is in systems where it is desirable to control a DC powered solenoid in the event that the alarm on the LMS-188-4P is active. When in non-alarm condition the relay is in a N.O. state and the solenoid will allow water to flow through it freely.