Mitsubishi Electric FX3U-4AD-PTW-ADP User Manual page 2

Hide thumbs Also See for FX3U-4AD-PTW-ADP:

Advertisement

3. Wiring
WIRING
PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before
attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
WIRING
PRECAUTIONS
• When drilling screw holes or wiring, make sure cutting or wire debris does
not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Make sure to observe the following precautions in order to prevent any
damage to the machinery or accidents due to abnormal data written to the
PLC under the influence of noise:
1) Do not bundle the power line or shield of the analog input/output cable
together with or lay it close to the main circuit, high-voltage line, or load
line.
Otherwise, noise disturbance and/or surge induction are likely to take
place. As a guideline, lay the control line at least 100mm (3.94") or more
away from the main circuit, high-voltage line, or load line.
2) Ground the shield of the analog input/output cable at one point on the
signal receiving side. However, do not use common grounding with heavy
electrical systems.
• Make sure to properly wire to the terminal block (European type) in
accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit,
wire breakage, malfunctions, or damage to the product.
- The disposal size of the cable end should follow the dimensions
described in the manual.
- Tightening torque should follow the specifications in the manual.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires
of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected
parts are directly stressed.
• Make sure to properly wire the terminal block in accordance with the
following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit,
wire breakage, malfunctions, or damage to the product.
- The disposal size of the cable end should follow the dimensions
described in the manual of the PLC main unit.
- Tightening torque should follow the specifications in the manual of the
PLC main unit.
3.1 Applicable cable and terminal tightening torque
3.1.1
Terminal block (European type)
1) Wire size
- The power supply wire should use 22-20 AWG wire.
- Wiring to a Pt100 platinum resistance thermometer should be used the
cable of it or a twisted shielded cable.
2) Applicable cable
Type
Wire size
Single-wire
2
2
0.3 mm
to 0.5 mm
(AWG22 to 20)
2-wire
2
2 pieces of 0.3 mm
(AWG22)
3) Termination of cable end
Strip the coating of strand wire and twist the cable core before connecting it,
or strip the coating of single wire before connecting it.
An alternative connection is to use a ferrule with insulating sleeve.
<Reference>
Manufacturer
Model
Caulking tool
CRIMPFOX 6
Phoenix Contact Co., Ltd.
AI 0.5-8WH
(or CRIMPFOX 6T-F
*1 Old model name: CRIMPFOX ZA 3
*2 Old model name: CRIMPFOX UD 6
- Strand wire/single wire
- Stick terminal with insulating sleeve
Insulation sleeve
Contact area
(Crimp area)
9mm
(0.35")
2.6mm(0.1")
14mm(0.55")
When using a stick terminal with insulating sleeve, choose a wire with proper
cable sheath referring to the above outside dimensions, or otherwise, the wire
cannot be inserted easily.
The tightening torque must be 0.22 to 0.25 N
m. Do not tighten terminal
screws exceeding the specified torque. Failure to do so may cause equipment
failures or malfunctions.
3.2 Power Supply Wiring
For the power supply wiring, refer to the following manual.
→ FX
/FX
/FX
/FX
/FX
Series User's Manual - Analog Control Edition
3S
3G
3GC
3U
3UC
3.3 Selection of platinum resistance thermometer sensors
→ For the terminal configuration, refer to Section 1.2
Precautions on platinum resistance thermometer wiring
• Type of platinum resistance thermometer
Select Pt100 3-wire platinum resistance thermometer sensors.
This thermometer will not be affected by voltage drop in the cable connection area,
and will ensure accurate measurement.
• Separate the cable of the platinum resistance thermometer sensors from the other
motive power cables or areas easily affected by inductive noise (of the commercial
power, etc.).
Example of platinum resistance thermometer wiring
Platinum resistance
thermometer wiring
Terminal
4.7kΩ
Pt100
Shielded wire
block
L
+
L
-
I
-
4.7kΩ
Pt100
L
+
L
-
I
-
External power supply
wiring
24+
24 V DC
24-
*1
Grounding
(Ground resistance:
100 Ω or less)
L +, L -, I +, ch
:
represents the channel number.
*1 24 V DC service power supply of the FX
/FX
3S
3G
used.
3.4 Grounding
Grounding should be performed as stated below.
• The grounding resistance should be 100 Ω or less.
• Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" of the
following figure.
For details, refer to the respective PLC User's manual Hardware Edition.
Other
Other
PLC
PLC
equipment
equipment
Independent grounding
Shared grounding
Best condition
Good condition
• The grounding wire size should be AWG 22-20 (0.3-0.5 mm
• The grounding point should be close to the PLC, and all grounding wire should be
as short as possible.
*1
*2
)
8mm
(0.31")
4. Specifications
STARTUP AND
MAINTENANCE
PRECAUTIONS
• Do not disassemble or modify the PLC.
Doing so may cause fire, equipment failures, or malfunctions.
* For repair, contact your local Mitsubishi Electric representative.
• Do not drop the product or exert strong impact to it.
Doing so may cause damage.
DISPOSAL
PRECAUTIONS
• Please contact a certified electronic waste disposal company for the
environmentally safe recycling and disposal of your device.
PTW-ADP
TRANSPORTATION AND
STORAGE PRECAUTIONS
• The product is a precision instrument. During transportation, avoid any impacts.
4.7kΩ
Failure to do so may cause failures in the product. After transportation, verify the
100kΩ
ch
operations of the product.
4.1 Applicable PLC
100kΩ
Model name
FX
Series PLC
Ver. 1.00 or later (from first production)
3S
4.7kΩ
FX
3G
Series PLC
Ver. 1.00 or later (from first production)
100kΩ
ch
FX
Series PLC Ver. 1.40 or later (from first production)
3GC
FX
Series PLC
Ver. 2.20 or later (from first production)
3U
100kΩ
Ver. 1.30 or later (from the production manufactured in August,
FX
Series PLC
3UC
2004 with SER No. 48****)
+5V
The version number can be checked by monitoring D8001/D8101 as the last three
digits indicate it.
4.2 General Specifications
Items other than the following are equivalent to the those of the PLC main unit.
For general specifications, refer to the respective PLC User's manual Hardware
Edition.
Item
Dielectric withstand
500 V AC for one minute
/FX
Series PLC can also be
3U
voltage
5 M Ω o r m o r e b y 5 0 0 V D C
Insulation resistance
megger
4.3 Power Supply Specifications
Item
A/D conversion
24 V DC +20 %/-15 %, 50 mA for 24 V DC
circuit driving power
Connect a 24 V DC power supply to the terminal block.
Other
5 V DC, 15 mA
PLC
Interface driving
equipment
5 V DC power is supplied from the internal power supply of
power
main unit.
Common grounding
Not allowed
2
).
4.4 Performance Specifications
Item
3-wire platinum resistance thermometer sensor Pt100
Input signal
Rated
-100 °C to +600 °C
temperature
range
Digital output
Resolution
±0.5 % for full scale (when ambient temperature is 25 °C±5 °C)
±1.0 % for full scale (when ambient temperature is in the range
Total accuracy
of 0 to 55 °C)
• FX
3U
A/D
(The data will be updated at every scan time of the PLC.)
conversion
• FX
3S
time
(The data will be updated at every scan time of the PLC.)
+6150
+6000
Applicability
Input
characteristics
-100
• The photocoupler is adopted to insulate the analog input
area from the PLC.
Insulation
• The DC/DC converter is adopted to insulate the power
method
supply line from the analog input area.
• Channels are not insulated from each other.
Occupied
0 point (This number is not related to the maximum number of
points
input/output points of the PLC.)
Specification
Between all terminals and
ground terminal of PLC
main unit
Specification
This manual confers no industrial property rights or any rights of any other kind,
nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
Warranty
Mitsubishi will not be held liable for damage caused by factors found not to be
the cause of Mitsubishi; opportunity loss or lost profits caused by faults in the
Mitsubishi products; damage, secondary damage, accident compensation
caused by special factors unpredictable by Mitsubishi; damages to products
other than Mitsubishi products; and to other duties.
This product has been manufactured as a general-purpose part for general
industries, and has not been designed or manufactured to be incorporated in
a device or system used in purposes related to human life.
Before using the product for special purposes such as nuclear power, electric
power, aerospace, medicine or passenger movement vehicles, consult with
Mitsubishi Electric.
This product has been manufactured under strict quality control. However
when installing the product where major accidents or losses could occur if the
product fails, install appropriate backup or failsafe functions in the system.
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Description
Centigrade (°C)
Fahrenheit (°F)
JIS C 1604-1997
-148 °F to +1112 °F
-1000 to +6000
-1480 to +11120
0.4 to 0.5 ° F
0.2 to 0.3 °C
Series PLC: 200 μs
/FX
3UC
Series PLC: 250 μs
/FX
3G
/FX
3GC
+11390
+11120
°
C
-148
°
F
0
0
+600
°
C
+1112
°
F
-1000
-1480
-1150
-1750
For safe use