Download Print this page

IBAIONDO CRB AUTOMAT Touch Screen Manual

Automatic pressurization systems with compressor

Advertisement

Quick Links

CRB
AUTOMAT
Touch Screen
COMPRESSOR CONTROLLED
PRESSURIZATION SYSTEM
PLENTZIA BIDEA, 3 BILLELA AUZOTEGIA
48100 MUNGIA- SPAIN

Advertisement

loading

Summary of Contents for IBAIONDO CRB AUTOMAT Touch Screen

  • Page 1 AUTOMAT Touch Screen COMPRESSOR CONTROLLED PRESSURIZATION SYSTEM PLENTZIA BIDEA, 3 BILLELA AUZOTEGIA 48100 MUNGIA- SPAIN...
  • Page 2 CRB AUTOMAT Description Compressor controlled pressurization units, classified as a dynamic pressurization system for heating and cooling water systems. It requires an auxiliary power source for its operation. They are controlled by a compressor and allow to maintain steady pressure in the system, by compensating volumetric changes suffered by the fluid, as a consequence of temperature variations in the system.
  • Page 3 CRB AUTOMAT Application Increases and decreases in water volume are continuous in heating and cooling systems due to temperature variation. When temperature raises, the pressure in the system increases. As a consequence water level in water side of the expansion vessel changes. That increase is absorbed by the expansion vessel. Pressure differences in air side is showed in display.
  • Page 4 CRB AUTOMAT Overview CRB AUTOMAT Nº Accessories Compressor Control unit Water side purgue Air connection Valves support Safety valve Solenoid valve Anti-return valve Pressure sensor Air pipe between vessel and anti-return valve Steel expansion vessel Sticker Bladder Cable duct Flexible hose to the system Level sensor - load cell PLENTZIA BIDEA, 3 BILLELA AUZOTEGIA 48100 MUNGIA- SPAIN...
  • Page 5 CRB AUTOMAT Overview CRB AUTOMAT Compressor Air supply When water in the system is heated, Control unit-Touch screen pressure in the system rises. If the Pressure system integrated nominal pressure at the controller is control exceeded, the solenoid valve opens and discharges air from the vessel.
  • Page 6: Main Features

    CRB AUTOMAT Main features - Automatic expansion vessels for pressure maintenance in heating and cooling systems - Replaceable bladder according to EN13831 (non-potable) - Upper membrane purge - Control unit for regulating water pressure and volume. Includes: 7 "color touch screen for control of the system Standard compressor with max.
  • Page 7: Spare Parts

    CRB AUTOMAT Spare parts Compressor LxPxH l/min 0,75 1.450 340x185x315 Control unit Load cell Control unit-Touch screen (2) 7” Touch screen - colour display Electronic board ABS Box for electronic hosting Permanent display of the operating parameters in the system Pressure &...
  • Page 8: Control Unit

    CRB AUTOMAT Control unit The control unit includes the following parts:  ABS Box for electronic hosting  7” Touch screen  Electronic board Touch screen 7 "color touch screen. The operating data of the system are entered through the touch screen. There are 6 different screens through which you can navigate by entering an access code.
  • Page 9 CRB AUTOMAT Control unit Electronic board The electronic board include de following elements:  Terminals for 230Vac power input  Magnetothermic protection 10A serie C  Microcontroller for the management and control of the equipment  Relay for the activation of the 230Vac 10A compressor with function check ...
  • Page 10 CRB AUTOMAT Connectors (control unit): Box view from the back side Connector 1 Connector 3 1. Ground 1. LOAD CELL (-) 2. Phase 2. LOAD CELL (A) 3. Neutral 3. LOAD CELL (B) 4. COMPRESSOR Phase 4. LOAD CELL (+) 5.
  • Page 11 CRB AUTOMAT Pre-Comissioning Determine the position of the expansion vessel. It must be placed on a level ground or surface, or failing that, proceed to level it correctly, in order to ensure the proper functioning of the vessel. It is important to do this correctly so that the volume sensor can detect a third of the weight of the vessel and therefore, indicate the correct volume.
  • Page 12 CRB AUTOMAT Attention: If using a secondary expansion vessel in addition to the primary vessel, make sure that all vessels have the same type and dimensions. Being the valve that connects the expansion vessel with the closed heating system closed, install the expansion vessel to the heating / cooling system using the flexible hose with elbow supplied.
  • Page 13 CRB AUTOMAT Comissioning Plug the connector to provide power (230 V) to the controller. If this is the first time the control unit is used, you will be asked to calibrate the touch screen through 3 points. Once calibrated, the following symbol appears in the screen Once calibrated, the following symbol appears in the screen Press the power icon (stand-by) for 2 seconds to start the unit.
  • Page 14 CRB AUTOMAT In addition, if desired, data such as, - DATE: Click on the grid to the right of DATE. A keyboard emerges that allows you to enter the date in DDMMYY format (DayMayYear). It is validated by pressing the ENTER button. - TIME: Press on the grid to the right of TIME, A keyboard emerges that allows you to enter the date in HHMMSS format (HourMinuteSeconds).
  • Page 15 CRB AUTOMAT The control unit has 6 menus (Password 1861 configurable at client's choice). Main Settings Test Comm Event Info To move or to modify the unit's parameters, a password is required. The default password is 1861 press ENTER. Main: Shows in general the data of the selected model, setpoint values of the device as well as the status of the alarms.
  • Page 16 CRB AUTOMAT Comm. RS-485 and Ethernet communications configuration. Language selection and password change. Event. It shows with date and time the events generated throughout the operation of the equipment. (Maximum 250 events) Info. Shows the different processor parameters for information PLENTZIA BIDEA, 3 BILLELA AUZOTEGIA 48100 MUNGIA- SPAIN...
  • Page 17 CRB AUTOMAT Language selection: For it, access to COMM Menu. Once COMM menu is selected, is need to enter the PASSWORD. Press ENTER to validate access. In the MISC section of the COMM menu - LANGUAGE: Click on the box below the language and select the desired language between SPANISH (ESP), ENGLISH (ENG), SWEDISH (SE) and FRENCH (FRA).
  • Page 18 CRB AUTOMAT Device: Configuration of the values corresponding to the selected expansion vessel model. - MODEL: Click on the box MODEL, enter the desired model between, 200, 300, 500, 700, 1000, 1400, 2000, 3000, 5000, 200x2, 300x2, 500x2, 700x2, 1000x2, 1400x2, 2000x2, 3000x2 and 5000x2. By default the chosen model is “NoDef”...
  • Page 19 CRB AUTOMAT Pressure: Configuration of the values corresponding to the air side of the chosen expansion vessel. - NOMINAL: Value of the nominal pressure or compressor stop pressure. Press on the box and enter the value of the desired NOMINAL PRESSURE, between values from MIN 0.5 bar to MAX 5.0 bar. It is validated by pressing ENTER button.
  • Page 20 CRB AUTOMAT - BLK.TIM: Value in seconds of the compressor BLOCKING TIME. By compressing the selected time the compressor will stop giving rise to a monitoring alarm in case of selection in any of the RELAY1, RELAY2, RELAY3. The Screensaver in case of activation, will do in RED FLASHING. Press on the box and enter the value of COMPRESSOR BLOCKING, between values from 0 seconds to 999 seconds.
  • Page 21 CRB AUTOMAT Installed the tank correctly, supported uniformly on the three legs of the tank and completely empty of water / air, the calibration of the weight cell is established. It is important to do this correctly so that the volume sensor can detect a third of the weight of the vessel and therefore, indicate the correct volume.
  • Page 22 CRB AUTOMAT In menu TEST, it can also check the functioning of compressor, air solenoid valve, autofilling, and three alarms below RELAY 1, RELAY 2 and RELAY 3. Once tested, the MANUAL button is pressed and the vesel will go into AUTO mode. Through the MAIN screen, you can check the operation of the unit as well as the status of the indicated alarms.
  • Page 23 CRB AUTOMAT In the event that the touch screen is not activated in the course of the time set for the SCREENSAVER, and during that time if alarm is activated, the screensaver will be shown in flashing red. EVENTS, All events or incidents generated during the operation of the unit will be reflected with date and time in the following screen.
  • Page 24: Maintenance

    CRB AUTOMAT Maintenance Maintenance must be carried out exclusively by authorized personnel. The equipment is designed and built for a long service life and high operational safety with minimum maintenance and care. However, we recommend performing the following operational controls at least once a year to prevent and prevent unnecessary operational anomalies.
  • Page 25 CRB AUTOMAT It means that the equipment does not communicate with the installation. Empty the container (up to approximately 60%). Then the membrane is compressed and "opens" the communication between the container and the unit. Now, the pressure in the installation and the pressure shown in the pressure maintenance unit are equal again.
  • Page 26 CRB AUTOMAT Reception of material Control on arrival: Check immediately that the equipment corresponds to the order and that all the components are in perfect condition and that the correct instructions for use have been attached. It is especially important to check the pressure vessel to detect possible deformations that could affect its resistance.
  • Page 27 CRB AUTOMAT Notes ………………………………………………………………………………………………… ………………………………………………………………………………………………… ………………………………………………………………………………………………… ………………………………………………………………………………………………… ………………………………………………………………………………………………… ………………………………………………………………………………………………… ………………………………………………………………………………………………… ………………………………………………………………………………………………… ………………………………………………………………………………………………… ………………………………………………………………………………………………… ………………………………………………………………………………………………… ………………………………………………………………………………………………… ………………………………………………………………………………………………… ………………………………………………………………………………………………… ………………………………………………………………………………………………… ………………………………………………………………………………………………… ………………………………………………………………………………………………… ………………………………………………………………………………………………… ………………………………………………………………………………………………… PLENTZIA BIDEA, 3 BILLELA AUZOTEGIA 48100 MUNGIA- SPAIN...
  • Page 28 CRB AUTOMAT COMPRESSOR CONTROLLED PRESSURIZATION SYSTEM PLENTZIA BIDEA, 3 BILLELA AUZOTEGIA 48100 MUNGIA- SPAIN...