Installation Instructions Electric Heaters Precedent™ 6 to 10 Ton Models Model Numbers: Used With: See General Information SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training.
Page 2
Introduction Read this manual thoroughly before operating or servicing this unit. WARNING Proper Field Wiring and Grounding Warnings, Cautions, and Notices Required! Safety advisories appear throughout this manual as Failure to follow code could result in death or serious required. Your personal safety and the proper operation of injury.
Page 3
Introduction to its content without obligation to notify any person of such revision or change. Trademarks All trademarks referenced in this document are the trademarks of their respective owners. Revision History • Updated eFlex™ models ACC-SVN67H-EN...
General Information Figure 1. Electromechanical wiring diagram Inspection 1. Unpack all components of the kit. 2. Check carefully for any shipping damage. If any damage is found it must be reported immediately and a claim made against the transportation company. 3.
Installation 5. Check the opening in the vestibule panel. Remove any metal burrs or slivers that could damage or pinch the heater elements resulting in a short circuit when elements are installed in the opening. WARNING Note: Locator tabs on the vestibule panel support the electric heat assembly and secure the inward edge Hazardous Voltage w/Capacitors! of the electric heat accessory control panel.
Page 9
Installation hooked in step 8 to the terminals on the new TCO-A. Table 2. TCO-A replaced for horizontal duct Refer to the heater package wiring diagram to assure configuration that the wiring is connected properly. Electric Heater Model TCO-A Note: The back of the electric heater element assembly is Unit Model Number Number location...
Page 10
Installation outer tab flush against center post and secure each Figure 6. door stop with 1 or 2 screws. See zoom view in Figure 8 Figure Figure 8. Single point power LOCATOR TABS SCREWS NOT REQUIRED ALONG THE TOP SCREWS SCREWS FILLER PANEL Figure 9.
Page 11
Installation 16. In the unit control box, route the wires along the units with or without duct work installed or existing harness to contactor CC1. Secure wires to horizontal units without ductwork installed, existing harness. remove horizontal supply cover and carefully inspect elements after installation 17.
Electrical Data Table 3. Air temperature rise (60 hz) 6 Ton 7.5 Ton 7.5 Ton 8.5 Ton 10 Ton (b),(c) (d),(e) 2000 cfm 3000 cfm 3000 cfm 3400 cfm 4000 cfm T*C072E3 THC120E3 TSC092E3 T*C102E3 T*C072E4 THC120E4 T*C102E4 TSC092E4 T*C072EW TSC120F3 WSC072E3 TSC090E3...
Page 13
Electrical Data Table 4. Unit wiring with electric heat (single point connection) - standard efficiency (continued) Standard Indoor Motor Oversized Indoor Motor Max Fuse Size or Max Fuse Size or Unit Model Heater Model Heater kW Control Max Circuit Max Circuit Tons Number Number...
Page 14
Electrical Data Table 5. Unit wiring with electric heat (single point connection) - standard efficiency Standard Indoor Motor Oversized Indoor Motor Max Fuse Size or Max Fuse Size or Unit Model Heater Model Heater kW Control Max Circuit Max Circuit Tons Number Number...
Page 15
Electrical Data Table 6. Unit wiring with electric heat (single point connection) - high efficiency and eFlex™ - 6 to 10 tons Standard Indoor Motor Oversized Indoor Motor Max Fuse Size Max Fuse Size Unit Model Heater Model Heater kW Control or Max Circuit or Max Circuit...
Page 16
Electrical Data Table 6. Unit wiring with electric heat (single point connection) - high efficiency and eFlex™ - 6 to 10 tons (continued) Standard Indoor Motor Oversized Indoor Motor Max Fuse Size Max Fuse Size Unit Model Heater Model Heater kW Control or Max Circuit or Max Circuit...
Page 17
Electrical Data Table 7. Air temperature rise 380/415 volt (50 hz) (Degrees C) (Degrees F) 6 Ton 7.5 Ton 10 Ton 6 Ton 7.5 Ton 10 Ton 4100 5100 6800 2400 3000 4000 WSC072E WSC090E WSC120 WSC072E WSC090 WSC120 Voltage Stages Voltage Stages...
Page 18
Electrical Data Table 9. Cooling only units with electric heater — single power source — 380/415 volt three phase (50hz) Standard Indoor Fan Motor Oversized Indoor Fan Motor Maximum Maximum Fuse Size Or Fuse Size Or Maximum Maximum Unit Model Heater Model Heater Heater...
Page 20
Ingersoll Rand (NYSE:IR) advances the quality of life by creating comfortable, sustainable and efficient environments. Our people and our family of brands—including Club Car®, Ingersoll Rand®, Thermo King® and Trane®—work together to enhance the quality and comfort of air in homes and buildings; transport and protect food and perishables; and increase industrial productivity and efficiency.