Sap Pca9555; Sap I²C Addresses; User Definable Leds - nVent SCHROFF 21596-077 User Manual

Shelf alarm panel
Table of Contents

Advertisement

Schroff Shelf Alarm Panel (SAP)
21596-077

6 SAP PCA9555

The PCA9555 device:
• controls the status of the LEDs
• reads the status of the Telco Alarm Cutoff push button (CLEAR)
• controls the Telco Alarm relays
Table 1: SAP PCA9555 Device Function
D
PCA9555 I/O pins
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
1.0
1.1
1.2
1.3
1.4
1.5
1.6
1.7
6.1 SAP I²C Addresses
Table 2: SAP I²C Addresses
LM75
0x96/0x4b

6.2 User definable LEDs

The LEDs USER (1, 2, 3) are user definable and connected to the I²C-bus I/O
port of the PCA 9555 on the SAP.
www.schroff.biz
Function
Power Alarm to telco relays output
Minor Alarm to telco relays output
Major Alarm to telco relays output
Critical Alarm to telco relays output
N/C
LED_MIN (Minor alarm LED) output
LED_MAJ (Major alarm LED) output
LED_CRIT (Critical alarm LED) output
Alarm cutoff push button input
Minor Clear input
Major Clear input
N/C
N/C
LED_USER3 output
LED_USER2 output
LED_USER1 output
SEEPROM
PCA9555
0xa6/0x53
0x44/0x22
4
SAP PCA9555
State
1 = relays powered
1 = relays powered
1 = relays powered
1 = relays powered
Pulled High
1 = On
1 = On
1 = On
0 = push button pushed
0 = voltage applied to input pins
0 = voltage applied to input pins
Pulled High
Pulled High
1 = On
1 = On
1 = On
R1.0, February 05, 2008