25

6.2.6. 6 (0x06) Write Single Register

This function code is used to write a single holding register in a remote device. Therefore, register numbered
1 is addressed as 0. The normal response is an echo of the request, returned after the register contents have
been written.
- In case of address 0x0800 output register value: 0x0000 changes to 0x1122.

6.2.7. 8 (0x08) Diagnostics

MODBUS function code 08 provides a series of tests for checking the communication system between a
client (Master) device and a server (Slave), or for checking various internal error conditions within a server.
The function uses a two–byte sub-function code field in the query to define the type of test to be performed.
The server echoes both the function code and sub-function code in a normal response. Some of the
diagnostics cause data to be returned from the remote device in the data field of a normal response.
• Request
Field name
Function Code
Register Address Hi
Register Address Lo
Register Value Hi
Register Value Lo
• Response
Field name
Function Code
Register Address Hi
Register Address Lo
Register Value Hi
Register Value Lo
• Request
Field name
Function Code
Sub-Function Hi
Sub-Function Lo
Data Hi
Data Lo
• Response
Field name
Function Code
Sub-Function Hi
Sub-Function Lo
Data Hi
Data Lo
Example
0x06
0x08
0x00
0x11
0x22
Example
0x06
0x08
0x00
0x11
0x22
Example
0x08
0x00
0x00
0x11
0x22
Example
0x08
0x00
0x00
0x11
0x22