Turbidity limit-value evaluation unit

Advertisement

Quick Links

Evaluation Unit
TURBISWITCH GS4
Safety Precautions:
 Installation, initial start-up and maintenance may only be performed by trained personnel!
 The device may only be connected to power which complies with the specifications included in the technical data and on the
serial plate!
 The device must be disconnected from all sources of power during installation and maintenance work!
 The device may only be operated under the conditions specified in the operating instructions!
Functions Description:
TURBISWITCH GS4 evaluation unit with required measuring sensor for installation in piping, TURBISWITCH GA1, GA5, GA11
or TURBISWITCH CP2 immersion probe
Turbidity measurement is based on the absorption process, i.e. it reacts to reduced light due to suspended sediment in the
liquid. Measurement is insensitive to extraneous light thanks to the use of pulsed infrared light. Measuring sensitivity depends
on the length of the measuring section. The shorter the measuring section, the more turbid the liquid can be.
Pulsed infrared light is transmitted from the emitter through the liquid to the receiver. If the selected turbidity value is exceeded
or fallen short of, the output relay in the switching amplifier reacts.
Digital communication between the devices
Turbidity dynamics for the overall sensing range: >100dB
Measuring sensor for installation in piping: max. roughly 10,000 FAU (depending on diameter)
Immersion probe for open containers or troughs: max. roughly 30,000 FAU
3 adjustable measured value ranges (low / medium / high)
1 floating changeover contact (both contacts are open when supply power is switched off)
1 floating alarm output contact
Adjustable delay time
Adjustable hysteresis
Attention! Operation of the previous version of the turbidity emitter and receiver (TT-GS and TR-GS), as well as the CP1
immersion probe, is only possible with the TRUBOMAT GS3 turbidity limit monitor.
Technical Data:
Supply power:
(see type plate)
Power consumption:
Ambient temperature:
Output relay switching capacity:
Housing:
Terminals:
Max. cable length:
Threshold value adjustment:
Phone: +49 (0)621 84224-0  Fax: +49 (0)621 84224-90, e-mail: info@bamo.de  Internet: www.bamo.de
SU3547f.doc
12/18
T
URBIDITY
Measuring Sensor (for installation in piping)
TURBISWITCH GA1
TURBISWITCH GA5
100 - 255V AC / 50 - 60Hz (TURBISWITCH GS4 G)
10 - 3V DC and 12 - 24V AC (TURBISWITCH GS4 D)
1 - 5W
-10...+45°C
250V AC, 3A / 30V DC, 1A
Caution: Contacts are not protected against overload – use external
protective device!
22.5x100x122mm, IP40, for top-hat rail: 35x7.5mm (DIN EN 50 022)
Screw terminal for wire cross-sections of up to 1.5mm²
100m
3 x 0 - 100% range, low (5% steps), medium (2% steps), high (1% steps)
BAMO IER GmbH  Pirnaer Str. 24 D-68309 Mannheim, Germany
O
PERATING
L
-V
E
IMIT
ALUE
VALUATION
WITH
TURBISWITCH GA11
I
NSTRUCTIONS
U
TURBISWITCH GS4
NIT
M
S
I
EASURING
ENSOR OR
MMERSION
Immersion Probe
TURBISWITCH CP2
P
ROBE
1

Advertisement

loading

Summary of Contents for BAMO IER TURBISWITCH GS4

  • Page 1  The device may only be operated under the conditions specified in the operating instructions! Functions Description: TURBISWITCH GS4 evaluation unit with required measuring sensor for installation in piping, TURBISWITCH GA1, GA5, GA11 or TURBISWITCH CP2 immersion probe Turbidity measurement is based on the absorption process, i.e. it reacts to reduced light due to suspended sediment in the liquid.
  • Page 2 Setting range of 0.1 to 9.9 s above/below the selected limit value  wait for delay time to elapse  the relay is then switched Default setting: 0.1 s BAMO IER GmbH  Pirnaer Str. 24 D-68309 Mannheim, Germany Phone: +49 (0)621 84224-0  Fax: +49 (0)621 84224-90, e-mail: info@bamo.de  Internet: www.bamo.de SU3547f.doc...
  • Page 3 LED off LED on Press button Back to Back to level 1 level 1 BAMO IER GmbH  Pirnaer Str. 24 D-68309 Mannheim, Germany Phone: +49 (0)621 84224-0  Fax: +49 (0)621 84224-90, e-mail: info@bamo.de  Internet: www.bamo.de SU3547f.doc 12/18...
  • Page 4 Use the included assembly set in order to remove the lenses from measuring sensors GA5 and GA11 (key and suction cup). BAMO IER GmbH  Pirnaer Str. 24 D-68309 Mannheim, Germany Phone: +49 (0)621 84224-0  Fax: +49 (0)621 84224-90, e-mail: info@bamo.de  Internet: www.bamo.de SU3547f.doc...
  • Page 5 Signaling and Controlling equipment All relays contacts are open when supply power is switched off. BAMO IER GmbH  Pirnaer Str. 24 D-68309 Mannheim, Germany Phone: +49 (0)621 84224-0  Fax: +49 (0)621 84224-90, e-mail: info@bamo.de  Internet: www.bamo.de SU3547f.doc 12/18...
  • Page 6: Switching Logic

    Signaling and All relays contacts are open when supply controlling equipment power is switched off. BAMO IER GmbH  Pirnaer Str. 24 D-68309 Mannheim, Germany Phone: +49 (0)621 84224-0  Fax: +49 (0)621 84224-90, e-mail: info@bamo.de  Internet: www.bamo.de SU3547f.doc 12/18...
  • Page 7 Calcium deposits can be removed with commercially available decalcifiers. Maintenance intervals depend on operating conditions. BAMO IER GmbH  Pirnaer Str. 24 D-68309 Mannheim, Germany Phone: +49 (0)621 84224-0  Fax: +49 (0)621 84224-90, e-mail: info@bamo.de  Internet: www.bamo.de SU3547f.doc...