DESCRIPTION
The SL-2000 Series Duct Smoke Detectors provide
early detection of smoke and combustion products pre-
sent in air moving through HVAC ducts. Air sampling is
accomplished by intake sampling tubes, which are
ordered separately. A standard length exhaust tube is
provided with each detector. These devices are designed
to prevent the recirculation of smoke in areas by the air
handling systems, fans, and blowers. Complete systems
may be shut down in the event of smoke detection.
OPERATION
The SL-2000 Series is designed to operate in duct
widths from 12.0" to 10.0' (30.5 cm to 3.05m) with an air
velocity from 100-4000 fpm (0.5-20.3 mps). The
SL-2000 Series will operate on any one of four input
voltages: 24 VAC, 24 VDC, 115 VAC, or 230 VAC. It
uses either a photoelectric or ionization smoke detector
head. Each detector contains two Form C and one Form
A alarm contact, which transfer in the event of smoke.
There is also one trouble contact, which supervises the
presence of input power and removal of the detector
head. A manual test/reset switch and visual indicators of
pilot and alarm are provided on the front of the detector.
Up to 30 SL-2000 Series units may be wired to use a
common test/reset function and to alarm simultaneously
when a single unit alarms.
SPECIFICATIONS
Power requirements
50/60 Hz (without
accessories)
24 VAC @ 55 mA standby,
24 VDC @ 15 mA standby,
115 VAC @ 16 mA standby,
230 VAC @ 10 mA standby,
Relay contact rating
Alarm (2)
SPDT, 10A, 115 VAC, resistive
Alarm (1)
SPST-NO, 2A, 115 VAC,
resistive
Trouble (1)
SPDT, 10A, 115 VAC, resistive
Radioactive element
For SL-2000-N only
Americium 241, 0.9 µCi
KELE • www.kele.com • FAX 800-284-5353
FEATURES
• Low flow technology, 100-4000 fpm
• Universal voltage: 24 VAC, 24 VDC, 115 VAC, or
• Two Form C and one Form A alarm contacts and
• Interchangeable "plug-in" photoelectric or ioniza-
• Compatible with building automation and fire
• Dust filtering included in detector head
• Interconnect up to 30 detectors for common
• Compatible with MS Series Remote Accessories
• Cover removal trouble indication
• Magnet test capability
• Front or rear loading sampling tubes
• Optional weatherproof enclosure
Air velocity
Approvals
UL
190 mA alarm
CSFM
MEA
70 mA alarm
Ambient temp
SL-2000-N
32 mA alarm
SL-2000-P
Humidity
20 mA alarm
Material
Weight
Mounting
Dimensions
DUCT SMOKE DETECTOR
SL-2000 SERIES
230 VAC
one trouble contact
tion heads
alarm systems
functions
100-4000 fpm (0.5-20.3 mps)
268A; UROX.S2829
3240-1004:105
73-92-E, Vol. 27
32° to 155°F (0° to 68°C)
32° to 100°F (0° to 38°C)
10% to 85% RH noncondensing
Gray plastic back box,
clear plastic cover
2.5 lb (1.13 kg)
7" (17.8 cm) exhaust tube, sampling
tube end cap, mounting template
and hardware supplied
13.5"L x 4.5"H x 2.25"D
(34.3 x 11.4 x 5.7 cm)
USA 888-397-5353 • International 901-382-6084
SL-2000
April 2004

Advertisement

loading

Summary of Contents for Kele SL-2000 Series

  • Page 1 Up to 30 SL-2000 Series units may be wired to use a • Dust filtering included in detector head • Interconnect up to 30 detectors for common...
  • Page 2 NEMA Type 3R Enclosure 11.06" x 18.13" x 4.38" (28.1 x 46.0 x 11.2 cm) 55000-250APO Replacement Ionization Smoke Detector Head Only 55000-350APO Replacement Photoelectric Smoke Detector Head Only KELE • www.kele.com • FAX 800-284-5353 USA 888-397-5353 • International 901-382-6084...