DES-P Digital Engine Supervisor 1.0 Introduction • 16 Bit RISC, state of art, • All system parameters are user microcontroller based System. programmable • True RMS measurement of all • Measurement and display of LLOP, measured parameters with 1% accuracy Fuel Level and HWT •...
DES-P Digital Engine Supervisor 6.0 Timers DES-P is equipped with the following timers: • Stop Solenoid on time • Hooter Reset Time • Fuel supervision time • Service Time Hour • LLOP Supervision Time • Ch- Alt on contact timer •...
DES-P Digital Engine Supervisor 9.1 Parameter Mode Display Explanation of parameter Factory Setting Range setting Engine Max Max. permissible RPM, above this the 1650 300-3000 RPM is treated unhealthy & the Generator is stopped. Engine O/RPM The time for which the Generator RPM 10Sec 1-999 Sec.
Page 7
DES-P Digital Engine Supervisor Disp Auto Scroll Setting ON will enable Auto Scroll of ON/OFF display. OFF: No scroll and next parameter can be viewed by pressing next Emer Sol Time This setting is to protect the fuel solenoid 22 Sec 1-100Sec in case the Stop button or Emergency is kept pressed.
Page 8
DES-P Digital Engine Supervisor 10.3 Fault Reset All internal faults can be reset by pressing (R) switch after the generator is stopped. In case the engine fails to stop “STOP KEY” can be pressed for manual attempt to stop engine. 11.0 Terminal description Terminal Number Description...
Page 9
DES-P Digital Engine Supervisor 14.0 Connection Diagram : Not Connected Crank /start Not Connected Solenoid /Stop Not Connected Charging Alternator ON Hooter Not Connected Common for Oil Pressure 12,13,14,15 Sensor/Switch Remote Start Water Temp. Sensor/Switch Low Fuel Remote Stop Sensor/Switch RWL Switch Not Connected Not Connected...