Download Print this page

E2S BExCP3A-BG Instruction Manual

Manual call point - push button with resistor modules, for use in flammable gas and dust atmospheres
Hide thumbs Also See for BExCP3A-BG:

Advertisement

Available languages

Available languages

Quick Links

BExCP3C-PB
Manual Call Point – Push Button
With resistor Modules
For use in Flammable Gas and
Combustible Dust Atmospheres
1)
Introduction
The BExCP3C-PB is a push button manual call
point which is certified to the European and
International Gas and Dust standards. The unit
meets the requirements of the ATEX directive
2014/34/EU and IECEx scheme.
The call point can be used in hazardous areas
where
potentially
flammable
gas
and
dust
atmospheres may be present.
All units have up to two of the following:
Monitoring resistors up to 1.5W per module
Monitoring diode
Monitoring Zener diode
The units are Group II, EPL (equipment protection
level) Gb. The equipment is certified 'Ex db eb mb
IIC T4 Gb' and as such may be used in Zones 1
and 2 with flammable gases and vapours with gas
groups IIA, IIB & IIC and temperature classes T1,
T2, T3 and T4.
These units are also Group III, EPL Db. The
equipment is certified 'Ex tb IIIC T75ºC Db' and as
such may be used in Zones 21 and 22 for
combustible dusts groups IIIA, IIIB & IIIC.
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
Document D150-00-155-IS Issue 2 11-08-2022
INSTRUCTION MANUAL
BExCP3C-PB Push Button Manual Call Point
For use in Flammable Gas and Dust Atmospheres
2)
Ratings & Marking
All units have a rating label, which carries the
following important information: -
Unit Type No.:
BExCP3C-PB Manual Call Point
Input Voltages:
Important: See section 7.1 for current ratings
125VDC Max
0.5A Max. Resistive Load;
0.03A Max Inductive Load
75VDC Max
0.75A Max
48VDC Max
1.0A Max
24VDC Max
5.0A Max Resistive Load;
3.0A Max Inductive Load
12VDC Max
5.0A Max
6VDC Max
5.0A Max
Code:
BExCP3C-PB
Ex db eb mb IIC T4 Gb
Ex tb IIIC T75ºC Db
IP66
–40ºC <= Ta <= +65ºC
Certificate No.:
SIRA 09ATEX3286X
IECEx SIR 09.0121X
CSAE 21UKEX3556X
Epsilon x:
II 2GD
CE Marking
Notified
2813
Body No.
UKCA Marking
Notified Body No.
0518
Year/Serial No. i.e. 20/1CP3CPB000001
WARNING - DO NOT OPEN WHEN AN
EXPLOSIVE ATMOSPHERE MAY BE PRESENT
3)
Type Approval Standards
The beacon has an EC Type examination
certificate issued by SIRA and have been approved
to the following standards: -
EN60079-0:2018 / IEC60079-0:2017
EN60079-1:2014 / IEC60079-1:2014
EN60079-7:2015 / IEC60079-7:2017
EN60079-18:2015 / IEC60079-18:2014
EN60079-31:2014 / IEC60079-31:2013
The equipment is certified for use in ambient
temperatures in the range
BExCP3C-PB -40
o
C to +65
o
C
and shall not be used outside this range.
4)
Installation Requirements
Installation of this equipment shall only be carried
out by suitably trained personnel in accordance
with the applicable code of practice e.g.
IEC 60079-14/EN 60079-14
Repair of this equipment shall only be carried out
by the manufacturer or in accordance with the
applicable code of practice e.g. IEC 60079-19/EN
60079-19.
Refer to certificates SIRA 09ATEX3286X, IECEx
SIR 09.0121X and CSAE 21UKEX3556X for
special conditions of safe use.
The certification of this equipment relies on the
following materials used in its construction:
Enclosure: Aluminium Pressure Die Cast Body
LM6
Through enclosure mechanism: Plastic Nylon Zytel
Injection Moulded
Sealing of enclosure and mechanism: O-ring
Acrylonitrile-Butadiene Rubber
Potting Compound of resistors where used: Epoxy
Resin
If the equipment is likely to come into contact with
aggressive substances, then it is the responsibility
of the user to take suitable precautions that prevent
it from being adversely affected, thus ensuring that
the type of protection is not compromised.
"Aggressive substances" - e.g. acidic liquids or
gases that may attack metals, or solvents that may
affect polymeric materials.
"Suitable precautions" - e.g. regular checks as part
of routine inspections or establishing from the
material's data sheet that it is resistant to specific
chemicals.
Sheet 1 of 3
5)
Call Point Location and Mounting
The location of the call point should enable ease of
access for operation and testing. The unit should
be mounted using the 4 off fixing holes which will
accept up to M4 sized fixings.
View of base unit showing fixing centres.
To gain access to the mounting holes in the base
the front cover must be removed.
This is achieved by removing the 4 off M4 cap
head bolts holding on the cover.
Once the screws are removed the cover will hang
down out of the way to gain access to the Ex e
terminal block, the internal earth terminal and
mounting hole recesses.
sales@e2s.com Tel: +44 (0)208 743 8880
www.e2s.com Fax +44 (0)208 740 4200

Advertisement

loading

Summary of Contents for E2S BExCP3A-BG

  • Page 1 IIIA, IIIB & IIIC. EN60079-7:2015 / IEC60079-7:2017 European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880 Document D150-00-155-IS Issue 2 11-08-2022 Sheet 1 of 3 www.e2s.com Fax +44 (0)208 740 4200...
  • Page 2 Earthing For the six-way terminal block wire sizes allowable E2S recommends a minimum resistor value The call point switch will now change over its The unit has both internal and external earth are 0.5mm² to 4.0mm². For the 8-way DIN rail wire of 100 ohms for a Series device and 180 contacts to operate the alarm.
  • Page 3 Proof Test Interval Up to 1 year European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880 Document D150-00-155-IS Issue 2 11-08-2022 Sheet 3 of 3 www.e2s.com Fax +44 (0)208 740 4200...
  • Page 4 Nº: IEx 10.0011X INSTRUÇÕES Acionador Manual de Alarme Quebra Vidro BExCP3A-BG, BExCP3B-BG, BExCP3C-BG, BExCP3D-BG, BExCP3E-BG Acionador Manual de Alarme com Botão Pulsador de Rearme Manual Rotativo BExCP3A-PB, BExCP3B-PB, BExCP3C-PB, BExCP3D-PB, BExCP3E-PB Acionador Manual de Alarme com Botão Pulsador de Rearme Rotativo por Chave BExCP3A-PT, BExCP3B-PT, BExCP3C-PT, BExCP3D-PT, BExCP3E-PT Certificado Sira 09ATEX3286X e Certificado IECEx SIR 09.0121X...
  • Page 5 (Tensão nominal 24V mostrada; consulte as observações para obter informações sobre as alterações necessárias para outras variantes de tensão) European Safety Systems Ltd. Impress House, Mansell Road, Acton, Londres W3 7QH www.e2s.com Tel: +44 (0)208 743 8880 Nº do Documento D150-00-001-IS-IEx_Emissão_3 - 15/06/2022 - Folha 2 de 7...
  • Page 6 (Tensão nominal 24V mostrada; consulte as observações para obter informações sobre as alterações necessárias para outras variantes de tensão) European Safety Systems Ltd. Impress House, Mansell Road, Acton, Londres W3 7QH www.e2s.com Tel: +44 (0)208 743 8880 Nº do Documento D150-00-001-IS-IEx_Emissão_3 - 15/06/2022 - Folha 3 de 7...
  • Page 7 (Tensão nominal 24V mostrada; consulte as observações para obter informações sobre as alterações necessárias para outras variantes de tensão) European Safety Systems Ltd. Impress House, Mansell Road, Acton, Londres W3 7QH www.e2s.com Tel: +44 (0)208 743 8880 Nº do Documento D150-00-001-IS-IEx_Emissão_3 - 15/06/2022 - Folha 4 de 7...
  • Page 8 (Tensão nominal 24V mostrada; consulte as observações para obter informações sobre as alterações necessárias para outras variantes de tensão) Acionador Manual de Alarme Quebra Vidro BExCP3A-BG Acionador Manual de Alarme com Botão Pulsador de Rearme BExCP3A-BP Acionador Manual de Alarme com Botão Pulsador de Rearme Rotativo por Chave BExCP3A-PT Nenhuma unidade tem resistores de monitoramento.
  • Page 9 IIA, IIB & IIC e classes de temperatura T1, T2, T3, e European Safety Systems Ltd. Impress House, Mansell Road, Acton, Londres W3 7QH www.e2s.com Tel: +44 (0)208 743 8880 Nº do Documento D150-00-001-IS-IEx_Emissão_3 - 15/06/2022 - Folha 6 de 7...
  • Page 10 Consulte os certificados SIRA 09ATEX3286X e IECEx SIR 09.0121X para obter informações sobre as condições para um uso seguro. European Safety Systems Ltd. Impress House, Mansell Road, Acton, Londres W3 7QH www.e2s.com Tel: +44 (0)208 743 8880 Nº do Documento D150-00-001-IS-IEx_Emissão_3 - 15/06/2022 - Folha 7 de 7...
  • Page 11 ISSUE MOD No. REASON - INITIAL - DATE E2S PART NO. DESCRIPTION DATA REFERENCE INTRODUCTION D.A.H - 07-02-2020 BExCP3B/C/D/E-BG BExCP3B/C/D-BG BREAK GLASS MANUAL CALL POINT 1.24.070 Module Device Codes Module Device Codes TYPE E ADDED ; SIMPLIFIED DIAGRAMS ACN0077 BExCP3B/C/D/E-PB BExCP3B/C/D-PB PUSH BUTTON MANUAL CALL POINT 1.24.080...
  • Page 12: Eu Declaration Of Conformity

    The product and all the components contained within it are in accordance with the restriction of the use of hazardous substances in electrical and electronic equipment, including amendment by Directive 2015/863/EU. E2S Telephone: +44 (0)20 8743 8880 Fax: +44 (0)20 8740 4200 Email: sales@e2s.com www.e2s.com DC-007_Issue_N (BExCP3) - Page 1 of 2 - QAF_252_Issue_5...
  • Page 13 EN 60529:1992+A2:2013 - Degrees of protection provided by enclosures (IP code) – enclosure rated IP66 Construction and design requirements according to EN54-11:2001 clause 4.7 – BExCP3A-BG / B-BG / C-BG / D-BG only (fitted with burning house symbol shown in figure 3a and no lift flap) On behalf of European Safety Systems Ltd., I declare that, on the date the equipment accompanied by this declaration is placed on the market, the equipment...
  • Page 14 The product and all the components contained within it are free from substances of very high concern. E2S Telephone: +44 (0)20 8743 8880 Fax: +44 (0)20 8740 4200 Email: sales@e2s.com www.e2s.com DC-093_Issue_A (BExCP3) - Page 1 of 2 - QAF_252_Issue_5...
  • Page 15 EN 60529:1992+A2:2013 - Degrees of protection provided by enclosures (IP code) – enclosure rated IP66 Construction and design requirements according to EN54-11:2001 clause 4.7 – BExCP3A-BG / B-BG / C-BG / D-BG only (fitted with burning house symbol shown in figure 3a and no lift flap) On behalf of European Safety Systems Ltd., I declare that, on the date the equipment accompanied by this declaration is placed on the market, the equipment...