4Evac SW6 / SW6-LITE INSTALLATION and USER
GUIDE V04
Summary
This document includes installation and user guide of the 4E-SW6 and 4E-SW6-LITE, zone expander module
dedicated for 4EVAC voice evacuation systems. It explains how the 4E-SW6 should be installed and
configured. Installation instructions are addressed to the trained technical personnel, such as installers,
service technicians and commissioning engineers. User instructions explain how to operate 4E-SW6 by the
end users as well as technical personnel, such as service technicians.
Rev.
Date
043
10-03-2020
044
01-03-2021
045
03-08-2021
Page 1 of 26
REVISION and APPROVAL
Nature of Changes
Spec change max. load SW6 output to 200W
SW6-LITE reference added
Revision of technical spec. section
https://www.4evac.com
Author:
TC
Approved By
AJH
AJH
AJH

Advertisement

Table of Contents
loading

Summary of Contents for 4EVAC SW6

  • Page 1 GUIDE V04 Summary This document includes installation and user guide of the 4E-SW6 and 4E-SW6-LITE, zone expander module dedicated for 4EVAC voice evacuation systems. It explains how the 4E-SW6 should be installed and configured. Installation instructions are addressed to the trained technical personnel, such as installers, service technicians and commissioning engineers.
  • Page 2: Table Of Contents

    5.2.3 Live monitoring of EOL impedance measurement .................. 9 5.2.4 EOL monitoring - step plan for commissioning ..................11 5.2.5 Operation of SW6 with Compact: ......................13 5.2.6 Operation of SW6 with Impact: ......................14 5.2.7 Fault detection, backup amplifier function ................... 15 5.3.
  • Page 3: What Is The 4E-Sw6

    4E-SW6 module, feeding maximum 6 loudspeaker lines – outputs of 4E-SW6. 4E-SW6 is controlled by the main system controller (Compact 500 or Impact Controller) via L-Net, receiving in real time routing information for each output line in order to connect to channel A, channel B or internal bus C.
  • Page 4: What Is The Sw6-Lite

    SW6-LITE is a special version of the SW6 that works with LoopDrive LDB ONLY! SW6-LITE has no ability to provide speaker line integrity. The SW6-LITE ‘sits’ in front of LDB and provide audio zoning from amplifier (COMPACT / IMPACT) to LDB.
  • Page 5: Configuration Settings

    Configuration settings Settings for 4E-SW6 are included in the configuration file located on micro SD memory card installed in the Compact 500 / Impact CONTROLLER unit. Configuration file includes user-defined settings, such as:...
  • Page 6: Hardware Installation And Settings

    In single channel mode 4E-SW6 works as 1x6 matrix. Only one audio signal can be distributed over 6 output zones. Each output zone of SW6 can be either transmitting signal from input A, or remain silent (internal surveillance bus). In case of multiple sources attempting to occupy channel A, system controller (Compact or Impact) transmits the top priority signal, while the other signals are suspended.
  • Page 7: Dual Channel Mode

    4E-SW6. Compact 500 is capable to operate with max. 3 x 4E-SW6 in dual channel mode, each fed by 2 of 6 amplifier channels available in Compact. Maximum total load in this case is 3 x 100W (100W per 4E-SW6), maximum number of individual zones is 18.
  • Page 8: Eol Module

    Once the loudspeaker lines are connected and EOL boards mounted at the end of every line, you can calibrate EOL measurement to currently detected impedance value @20kHz. As result of calibration the reference impedance value is saved for every line to the internal memory of SW6. Page 8 of 26...
  • Page 9: Live Monitoring Of Eol Impedance Measurement

    1. Check load: measure every loudspeaker line individually with impedance meter and check if the load is as expected. During measurement lines should be disconnected from SW6. 2. Check EOL: make sure that EOL board is properly connected at the end of every loudspeaker line.
  • Page 10 Live Monitoring feature of the 4EVAC Manager GUI application, where you can observe exact impedance at 20kHz of each loudspeaker line, in real time. (More information on how to use 4EVAC Manager you can find in 4EVAC Manager User Manual).
  • Page 11: Eol Monitoring - Step Plan For Commissioning

    Author: 4Evac SW6 / SW6-LITE INSTALLATION and USER GUIDE V04 In this example above SW6 has following loads connected to output terminals: Line 1: 200Ω resistor + EOL module (in parallel) Line 2: open Line 3: EOL module (~300Ω @20kHz) Line 4: 100Ω...
  • Page 12 Hacousto Holland bv Industrieweg 87 2651BC Berkel & Rodenrijs Author: 4Evac SW6 / SW6-LITE INSTALLATION and USER GUIDE V04 2) EOL measurement in 4EVAC Manager A. Turn on Live monitoring a) Open 4EVAC Manager and load system configuration, b) Connect to the system in order to have live link c) Go to “Live monitoring”...
  • Page 13: Operation Of Sw6 With Compact

    Wait for line fault detection 5.2.5 Operation of SW6 with Compact: If inputs of 4E-SW6 are attached to power amplifier of Compact 500 in system settings (see 4EVAC manager GUI manual), and output lines of 4E-SW6 are attached to zones, then the 4E-SW6 can route each of the outputs to any input, depending on routing command from main controller.
  • Page 14: Operation Of Sw6 With Impact

    5.2.6 Operation of SW6 with Impact: If inputs of 4E-SW6 are attached to an amplifier in system settings (see 4EVAC manager GUI manual), and its output lines are attached to zones, then the 100V matrix can route each of the outputs to any input, depending on routing command from main controller.
  • Page 15: Fault Detection, Backup Amplifier Function

    GUIDE V04 5.2.7 Fault detection, backup amplifier function Input fault If input monitoring is enabled, then SW6 will measure of 20 kHz tone coming from this input. If the signal is not detected, input fault is generated. Backup amplifier function When both inputs CHA and CHB are enabled and monitored, 4E-SW6 by default supports automatic backup amplifier function.
  • Page 16: Dc Input

    L-Net port (see power consumption in specification sheet). If you need to connect more than 2x SW6 modules to the same L-Net bus, then you need to provide additional 24V DC power line via the power connector on all SW6 modules connected to the same L-Net bus.
  • Page 17: Indications

    4E-SW6: 24V DC input 5.4. Indications SW6 has 2 bi-colour LED indicators per output. Status is given individually per speaker line. Additionally general status of booting mode or calibration mode is also displayed on LEDs. LED indicators show status of each output line, including: a.
  • Page 18: L-Net

    (for 2 LEDs) 5.5. L-Net 4E-SW6 is a network device connected to L-Net port of C500 main unit. Multiple 4E-SW6 interfaces may be used in the same L-Net, with following limitations: maximum 2 units per L-Net port (without additional power cable) •...
  • Page 19: Network Ports

    GUIDE V04 5.5.1 Network ports 4E-SW6 offers 2 L-Net ports (RJ-45) for network connections to C500 main unit and distributed parts of the 4EVAC Voice Evacuation System. Both L-Net ports are equal, therefore it makes no difference which port is connected to which side of L-Net daisy-chain.
  • Page 20: Network Cabling

    5.5.3 Network cabling 4EVAC network features full duplex RS-422 data link and 24V DC power to remote devices. If you’re building distributed system using 4EVAC network, you should make physical links between devices using the right cables. Cabling should meet following requirements: 1.
  • Page 21: Device Id

    5.6. Device ID SW6 needs ID setting in order to be properly recognized in the network and operate. If the device ID is duplicated or set to a wrong value, the device will not receive correct configuration settings from the master Compact 500 main unit.
  • Page 22: Connections And Recommended Cable Types

    Hacousto Holland bv Industrieweg 87 2651BC Berkel & Rodenrijs Author: 4Evac SW6 / SW6-LITE INSTALLATION and USER GUIDE V04 Connections and recommended cable types Connector Signal type Additional Recommended cable Max. length many type information (minimum) Inputs 100V audio 20kHz tone typ.
  • Page 23: Examples Of Use With Impact

    Hacousto Holland bv Industrieweg 87 2651BC Berkel & Rodenrijs Author: 4Evac SW6 / SW6-LITE INSTALLATION and USER GUIDE V04 Examples of use with Impact: Impact system, 2x500W, 12 zones Page 23 of 26...
  • Page 24: Example Of Use With Compact

    Hacousto Holland bv Industrieweg 87 2651BC Berkel & Rodenrijs Author: 4Evac SW6 / SW6-LITE INSTALLATION and USER GUIDE V04 Example of use with Compact: Compact system, 2x100W, 6 zones Page 24 of 26...
  • Page 25: Technical Specifications

    Storage temperature -40 to 70°C All information provided in this document is subject to change without notice. 4EVAC may also make improvements and/or changes in the products described in this information at any time without notice. Page 25 of 26...
  • Page 26 Hacousto Holland bv Industrieweg 87 2651BC Berkel & Rodenrijs Author: 4Evac SW6 / SW6-LITE INSTALLATION and USER GUIDE V04 M A D E T H E N E T H E R L A N D S 4EVAC is a trade name of:...