Configuration and Account Setup ......................31 TROUBLESHOOTING AND REPAIRS ........................ 33 End User ..............................33 Qualified Installer ............................33 OPERATIONAL INFORMATION ........................34 PRODUCT SPECIFICATIONS ..........................35 LIMITED WARRANTY FOR LUMIN SMART PANEL ................... 36 RADIO FREQUENCY STATEMENT ........................37...
A Lumin Smart Panel will not function as designed until it is fully commissioned. It is generally NOTE: the responsibility of the installer to perform both the physical installation and the online setup/commissioning process.
Installation and servicing must be conducted by a qualified professional, according to local and • national electrical codes Lumin Certified Installer training is required for installation and servicing • Review entire manual before starting the installation or servicing •...
Controlling the circuit that powers the Internet connection is not recommended; manual control of the LSP will be lost when this circuit is switched off. The LSP does not replace the need for standard circuit breakers. Lumin does not provide overcurrent •...
INSTALLATION Items in the Box 1 Outdoor LSP with Conduit, Conduit Bushings & Wire Whips Attached Upper Outdoor Wall Lower Outdoor Wall 1 Pair of 200A Current Transformers Mounting Brackets Mounting Brackets (A second pair is optional) NOTE: Additional items include an antenna, installation hardware, and an LSP Circuit Label & CT Table.
Lumin Smart Panel - Outdoor DOCUMENTATION AND INSTALLATION MANUAL Hardware Installation Overview STEP 1. Turn Off Main Feed and Remove STEP 14. Record Circuit Label/Name and Breaker Electrical Panel Cover Row (A/B) With Corresponding LSP Wire Number STEP 2. Knock Out or Punch One Hole for 2”...
Hardware Installation Steps STEP 1. Turn Off Main Feed and Remove Electrical Panel Cover WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE ALWAYS LIVE. AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR PRINCIPAL EST ÉTEINT. LES CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS TENSION. Tools: Screwdriver...
Page 13
Lumin Smart Panel - Outdoor DOCUMENTATION AND INSTALLATION MANUAL STEP 2. Knock Out or Punch One Hole for 2” Conduit Fitting WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE ALWAYS LIVE. AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR PRINCIPAL EST ÉTEINT. LES CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS TENSION.
Page 14
STEP 3. Determine LSP Mounting Position Relative to Conduit Routing WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE ALWAYS LIVE. AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR PRINCIPAL EST ÉTEINT. LES CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS TENSION. NOTE: The LSP must be mounted in the vertical orientation shown (with the conduit exiting the LSP from the bottom).
Page 15
Lumin Smart Panel - Outdoor DOCUMENTATION AND INSTALLATION MANUAL STEP 4. Measure and Mark Hole Locations for Mounting Location of Mounting Holes and Slots (Large Arrows) Marking Hole Locations Using Brackets Bracket Attachment Stud Locations (Small Dashed Arrows) Tools: Tape measure, marker, stud-finder (optional), and level.
Page 16
STEP 5. Secure Mounting Brackets to Wall Tools: Drill, stud-finder (optional), screws (x4), and washers (x4) NOTE: Ensure the outer screws of the upper bracket are securely threaded into studs, sheathing, brick, masonry, or other suitable structural anchors. For masonry applications (including brick) use the appropriate fasteners included in the installation hardware.
Page 17
Lumin Smart Panel - Outdoor DOCUMENTATION AND INSTALLATION MANUAL STEP 6. Attach LSP Antenna and Guide LSP Wire Whip into Electrical Panel Attach Antenna Wire Whip Conduit Bushing WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE ALWAYS LIVE.
Page 18
STEP 7. Secure LSP to Wall/Bracket and Electrical Panel WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE ALWAYS LIVE. AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR PRINCIPAL EST ÉTEINT. LES CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS TENSION. Tools: Drill, washer, and nuts (x3) NOTE: Lift the LSP to align with the mounting holes and secure it to the mounting brackets utilizing the...
Page 19
Lumin Smart Panel - Outdoor DOCUMENTATION AND INSTALLATION MANUAL STEP 8. Connect LSP Equipment Grounding Conductor (EGC) to Ground Bar EGC to Ground Bar WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE ALWAYS LIVE. GROUND WIRE MUST BE INSTALLED FOR SAFETY.
Page 20
STEP 9. Identify A-Row and B-Row Breakers NOTE: For purposes of Lumin installation, the top row of breakers will always be classified as “A”. The second row of standard breakers will be “B”. The alternating A-B-A-B pattern continues down the rows of breakers.
Page 21
Exception: Use a single-pole breaker for “Line A” and securely cap “Line B” in panels with two-wire single-phase power rather than three-wire single-phase (split phase). Mark the breaker with a clearly identifying label (ex. “Lumin Smart Panel Power”). DO NOT CONNECT THESE CONDUCTORS TO GFCI BREAKERS. Do not double-tap breakers unless they are appropriately rated.
Page 22
STEP 11. Select Circuit Breaker to Connect to LSP, Turn Off, and Disconnect Load Disconnect Load Wire Turn Off Circuit WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE ALWAYS LIVE. AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR PRINCIPAL EST ÉTEINT. LES CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS TENSION.
Page 23
Lumin Smart Panel - Outdoor DOCUMENTATION AND INSTALLATION MANUAL STEP 12. Connect One LSP Wire Labeled “Line 1 Breaker” to Circuit Breaker Load Wire “Line 1 Breaker” WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE ALWAYS LIVE.
Page 24
STEP 13. Connect Corresponding LSP Wire Labeled “Line 1 Load” to Load and Turn Circuit Breaker Back On Load Wire “Line 1 “Line 1 Breaker” Load” WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE ALWAYS LIVE. AVERTISSEMENT: HAUTE TENSION.
Page 25
Lumin Smart Panel - Outdoor DOCUMENTATION AND INSTALLATION MANUAL STEP 14. Record Circuit Label/Name and Breaker Row (A/B) With Corresponding LSP Wire Number Refrigerator Single-pole circuit Range Double-pole circuit Range NOTE: Record the circuit label/name and breaker row (A or B) with the corresponding LSP line number in the LSP Circuit Label &...
Page 26
The LSP can connect to up to 12 single-pole (or six double-pole) circuit breakers. Each hot leg of a double-pole circuit must be connected to its own numbered Lumin wire set (ex. LSP controls a clothes dryer. Dryer Leg "A" is connected to LSP Line 3. Dryer Leg "B" is connected to LSP Line 4).
Page 27
CTs as well as leads for an optional set of auxiliary CTs which is available for purchase from Lumin. Most LSP installations do not utilize auxiliary CTs and use the main CTs to measure the total consumption of the electrical panel(s) backed up by a battery. In this typical installation, the CTs are placed on the feeders from the Microgrid Interconnect Device (MID) or Automatic Transfer Switch (ATS) to the electrical panel, as shown in Figure A.
Page 28
“A”. Whichever feeder leg supplies breaker Row A will be designated “A.” NOTE: Lumin CTs are designated either “A” or “B”. Placing them on the incorrect leg of a circuit will result in erroneous consumption data. If the panel is a main-lug-only type as shown in Figure B (no main circuit breaker) then the feeder on the left will be Lumin Leg “A”.
Page 29
Lumin Smart Panel - Outdoor DOCUMENTATION AND INSTALLATION MANUAL STEP 18. Testing for Crossover before Current Transformer Placement To determine A and B feeders when a main circuit breaker is present, test for AC voltage between the left lug and the left bus bar*.
Page 30
STEP 19. Connecting Current Transformers Prior to installation, measure the CT leads’ routing path(s) in the electrical panel. Local electrical codes may require securing CT wiring at regular intervals. If the provided leads are not long enough, fashion CT wire extensions in the field.
Page 31
Lumin Smart Panel - Outdoor DOCUMENTATION AND INSTALLATION MANUAL STEP 20. Record Line Name(s) of Corresponding Current Transformers BREAKER BREAKER CIRCUIT BREAKER CIRCUIT BREAKER LINE LINE (circle LABEL/NAME (circle LABEL/NAME one) one) CURRENT TRANSFORMER CURRENT TRANSFORMER (CT) (CT) Aux. A/B CTs Ex.
Page 32
STEP 21. Connect the LSP’s Grid Detection Circuit (GDC) Wires to the Grid Side of an Automatic Transfer Switch (ATS) or Microgrid Interconnect Device (MID) “Grid Line” (black) Connect black wire to a portion of the electrical system that will lose power “Grid Neutral”...
Page 33
Lumin Smart Panel - Outdoor DOCUMENTATION AND INSTALLATION MANUAL STEP 22. Replace Electrical Panel Cover and Turn On Main Feed WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE ALWAYS LIVE. AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR PRINCIPAL EST ÉTEINT. LES CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS TENSION.
Page 34
STEP 23. Attach Antenna and Turn On the LSP to Begin Configuration and Account Setup WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE ALWAYS LIVE. AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR PRINCIPAL EST ÉTEINT. LES CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS TENSION.
Replace the LSP cover by hooking over the top lip of the enclosure and latching the toggle clamps on both sides. Download the Lumin mobile app. In the Apple App Store or Google Play Store, search for "Lumin Smart". Log in with an existing account or create a new account.
Page 36
STEP 25. Reinstall LSP Cover Completed Exterior Wall Mount Installation WARNING: FOR ALL OUTDOOR INSTALLATIONS, OPERATING THE LSP WITH THE COVER REMOVED DURING INCLEMENT WEATHER (RAIN, SNOW, SLEET, DUSTY CONDITIONS, ETC) WILL VOID THE WARRANTY. THE NEMA RATING IS ONLY APPLICABLE WITH THE COVER INSTALLED. NORMAL OPERATION/INSTALLATION OF THE LSP INCLUDES THE INSTALLATION OF THE COVER.
Alternatively, contact Lumin directly for assistance. Qualified Installer Observe all safety precautions (pg. 2). Be aware that Lumin app readings may not accurately reflect electrical conditions, so always assume that the LSP circuits are enabled and conductors are live.
Setup Mode and that Wi-Fi connectivity is enabled on the mobile device. NOTE: To manually enable all circuits controlled by Lumin, turn LSP power off, then on, then off once again. Leave the LSP off and all controlled circuits will function normally.
20 A per Line × 6 Lines Beyond Conduit End Load Breaker Ratings 40 A per Line × 6 Lines and Additional Units Use of Multiple Lumin Smart Panels at 60-70 °C 15 A per Line × 6 Lines Supported Breaker Types Single Pole (1 Line) and Dual Pole CONNECTIVITY &...
Who May Use This Warranty? Coulomb Inc. (d/b/a Lumin), a Delaware corporation located at address 501 Locust Ave, Floor 1, Suite 2, Charlottesville, VA 22902 (“we”) extends this limited warranty only to the consumer who originally activated the product and connected it to a Lumin Account (through https://www.luminsmart.com/) and to any subsequent owner or other transferee of the product (“you”).
Lumin Smart Panel - Outdoor DOCUMENTATION AND INSTALLATION MANUAL RADIO FREQUENCY STATEMENT This device complies with Part 15 of the FCC rules and with Innovation, Science and Economic Development Canada’s licence-exempt RSS(s). Operation is subject to the following two conditions: This device may not cause interference.