Peaco Support FC280 Series VFD User Manual
VFD
Free Shipping Worldwide
Reliable Supplier

Advertisement

Table of Contents
loading

Summary of Contents for Peaco Support FC280 Series

  • Page 1 Peaco Support FC280 Series VFD User Manual (General Purpose) (220V Input, 380V Output Series) (Elevator & Lift Series) (Single Phase Output Series) ( Off Grid Solar Series) www.peacosupport.com sales@peacosupport.com Free Shipping Worldwide Reliable Supplier...
  • Page 2 Peaco Support FC280 Series VFD User Manual Preface Thank you for purchasing the AC drive developed by Our company. AC drives are general type inverters with vector control based on BD330.High quality, multiple functions and low noise, developed independently by ourselves.
  • Page 3: Table Of Contents

    Peaco Support FC280 Series VFD User Manual Contents Chapter 1 Safety and Attentions 1.1 Safety Matters....................6 1.2 Use Considerations..................9 Chapter 2 Product Brief Introduction 2.1 Position and content of nameplate..............12 2.2 Nameplate model description and rated parameters........12 2.3 Specifications and models of AC drives............13 2.4 Technical Features..................15...
  • Page 4 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes F00 Standard Function Parameters............86 F01 Standard Function Parameters............98 F02 Motor 1 Parameters..............104 F03 Vector Control Parameters............108 F04 V/F Control Parameters.............114 F05 Fault and Protection..............120 F06 Input Terminals.................131 F07 Output Terminals...............146...
  • Page 5 Peaco Support FC280 Series VFD User Manual www.peacosupport.com sales@peacosupport.com Free Shipping Worldwide Reliable Supplier...
  • Page 6: Chapter 1 Safety And Attentions

    Peaco Support FC280 Series VFD User Manual Chapter Safety and Attentions 1.1 Safety Matters....................6 1.2 Use Considerations..................9 www.peacosupport.com sales@peacosupport.com Free Shipping Worldwide Reliable Supplier...
  • Page 7: Safety Matters

    Peaco Support FC280 Series VFD User Manual Chapter 1 Safety and Attentions Users are requested to read this chapter carefully when installing, commissioni- ng and repairing this product and perform the operation according to safety precautions as set forth in this chapter without fail. Our company will bear no responsibility for any injury and loss as a result of any violation operation.
  • Page 8 Peaco Support FC280 Series VFD User Manual Chapter 1 Safety and Attentions Use Stage Safety Grade Precautions ² Consider the installation space for cooling purpose when Installation DANGER two or more inverters are placed in the same cabinet. ² Wiring must be performed by authorized and qualified personnel.
  • Page 9 Peaco Support FC280 Series VFD User Manual Chapter 1 Safety and Attentions Use Stage Safety Grade Precautions S, T or L1, L2 and output terminals U, V, and W, wiring of Before inverter and its peripheral circuits, and all wires should...
  • Page 10: Use Considerations

    Peaco Support FC280 Series VFD User Manual Chapter 1 Safety and Attentions 1.2 Use Considerations 1.2.1 Motor Insulation Inspection When the motor is used for the first time or when the motor is reused after being kept, or when periodical inspection is performed, insulation inspection shall be conducted with motor so as to avoid damaging the inverter because of the insulation failure of the motor windings.
  • Page 11 Peaco Support FC280 Series VFD User Manual Chapter 1 Safety and Attentions When a contactor is installed between the output side of the AC drive and the motor, do not turn off the contactor when the AC drive is active. Otherwise, modules inside the AC drive may be damaged.
  • Page 12 Peaco Support FC280 Series VFD User Manual Chapter Product Brief Introduction 2.1 Position and content of nameplate..............12 2.2 Nameplate model description and rated parameters........12 2.3 Specifications and models of AC drives............13 2.4 Technical Features..................15 2.5 All components schematic diagram of AC drive..........17 2.6 Dimensions....................18...
  • Page 13: Chapter 2 Product Brief Introduction

    Peaco Support FC280 Series VFD User Manual Chapter 2 Product Brief Introduction 2.1 Position and content of nameplate MOD L: 4T-1.5G-B SOURCE: PH AC380V 50/60HZ OUTPUT: 1.5KW 4A 0-600HZ BDDG3DFDF122466 2.2 Nameplate model description and rated parameters 4 T - 1.5 G...
  • Page 14: Specifications And Models Of Ac Drives

    Peaco Support FC280 Series VFD User Manual Chapter 2 Product Brief Introduction 2.3 Specifications and models of AC drives Rated power Rated output Adaptive Rated input Models (KW) current (A) current(A) motor (KW) Input 1PH 220V±15% 47Hz~63Hz 2S-0.5G-B 0.55 0.55 2S-0.7G-B...
  • Page 15 Peaco Support FC280 Series VFD User Manual Chapter 2 Product Brief Introduction Rated power Rated input Rated output Adaptive Models (KW) current (A) current(A) motor (KW) Input 3PH 380V±15% 47Hz~63Hz 4T-11G/15P 11/15 26/35 24/30 11/15 4T-15G/18.5P 15/18.5 35/38.5 30/37 15/18.5 4T-18.5G/22P...
  • Page 16: Technical Features

    Peaco Support FC280 Series VFD User Manual Chapter 2 Product Brief Introduction 2.4 Technical Features Technical Features Description 1AC 220V±15%, 3AC 220V±15%,3AC 380V±15%, 3AC Input voltage range 660V±10%, 3AC 1140V±15% Input frequency range 47~63Hz Power factor ≥95% V/F control, non-PG vector control(SVC),PG vector control...
  • Page 17 Peaco Support FC280 Series VFD User Manual Chapter 2 Product Brief Introduction Technical Features Description Automatic voltage Automatically maintain a constant output voltage when the regulation(AVR) voltage of electricity grid changes Common DC bus function: multiple inverters can use a...
  • Page 18: All Components Schematic Diagram Of Ac Drive

    Peaco Support FC280 Series VFD User Manual Chapter 2 Product Brief Introduction 2.5 All components schematic diagram of AC drive The following picture is all components and names of below 22KW plastic shell AC drive. Name Description ❶ Cabinet-cover Protect the internal components.
  • Page 19: Dimensions

    Peaco Support FC280 Series VFD User Manual Chapter 2 Product Brief Introduction 2.6 Dimensions Plastic case and wall mount case Wall/Cabinet Combination Chassis Rated Power AC Drive Model (KW) (mm) (mm) (mm) (mm) (mm) (mm) Input 1PH 220V±15% 47Hz~63Hz 2S-0.5G-B 0.55...
  • Page 20 Peaco Support FC280 Series VFD User Manual Chapter 2 Product Brief Introduction Rated Power AC Drive Model (KW) (mm) (mm) (mm) (mm) (mm) (mm) Input 3PH 380V±15% 47Hz~63Hz 4T-0.7G/1.5P-B 0.75/1.5 4T-1.5G/2.2P-B 1.5/2.2 4T-2.2G/4.0P-B 2.2/3.7 4T-4.0G/5.5P-B 3.7/5.5 4T-5.5G/7.5P-B 5.5/7.5 4T-7.5G/11P-B 7.5/11...
  • Page 21 Peaco Support FC280 Series VFD User Manual www.peacosupport.com sales@peacosupport.com Free Shipping Worldwide Reliable Supplier...
  • Page 22 Peaco Support FC280 Series VFD User Manual Chapter Installation 3.1 Mechanical installation..................22 3.2 Electrical Installation..................23 3.3 Basic wiring diagram..................26 3.4 Jumper function declaration of main board...........27 3.5 Main circuit terminals and connection............27 3.6 Control circuit terminal and wirin..............29 3.7 Treatment of EMC problem................32 www.peacosupport.com...
  • Page 23: Chapter 3 Installation

    Peaco Support FC280 Series VFD User Manual Chapter 3 Installation 3.1 Mechanical Installation 3.1.1 Installation Environment Ø Environment temperature: Surrounding environment temperature has a gre- at impact on lifetime of AC drive, and the operation environment temperat- ure of AC drive shall not exceed allowable temperature range (- 10℃...
  • Page 24: Electrical Installation

    Peaco Support FC280 Series VFD User Manual Chapter 3 Installation 3.2 Electrical Installation 3.2.1 Model Selection of Main Circuit Peripheral Devices Cable of Input Cable of Output Cable of Models MCCB Contactor Side Main Circuit Side Main Circuit Control Circuit...
  • Page 25 Peaco Support FC280 Series VFD User Manual Chapter 3 Installation Cable of Input Cable of Output Cable of Models MCCB Contactor Side Main Circuit Side Main Circuit Control Circuit (mm ) (mm ) (mm ) Input 3PH 380V±15% 47Hz~63Hz 4T-18.5G/22P...
  • Page 26 Peaco Support FC280 Series VFD User Manual Chapter 3 Installation 3.2.2 Peripheral device wiring diagram Use within the allowable power supply specification Three-phase R S T of the AC drive AC power Moulded case Select a proper breaker to resistlarge in-rush current...
  • Page 27: Basic Wiring Diagram

    Peaco Support FC280 Series VFD User Manual Chapter 3 Installation 3.3 Basic wiring diagram External braking unit External DC reactor External braking resistor Note1 Short connector Breaker Contactor Input reactor (+) (+) PB (+) Output reactor Shielded or armored cable...
  • Page 28: Jumper Function Declaration Of Main Board

    Peaco Support FC280 Series VFD User Manual Chapter 3 Installation 3.4 Jumper function declaration of main board Item Meaning Analogue input 1 voltage/ current signal conversion Analogue input 2 voltage/ current signal conversion 0-10VDC voltage signal input 0-20mA analog current signal input...
  • Page 29 Peaco Support FC280 Series VFD User Manual Chapter 3 Installation 3.5.1 Main circuit terminal description Main circuit wiring terminal ≤22kw Terminal Name Function description Main circuit power input Connect three- phase ( one- phase) 、 、 、 terminal power supply...
  • Page 30: Control Circuit Terminal And Wirin

    Peaco Support FC280 Series VFD User Manual Chapter 3 Installation The wiring length of brake unit shall not be more than 10m, and only twisted pair or tight double-line is available in parallel. Brake resistance cannot be connected onto DC bus directly, or it may cause damag- es to AC drive, or even fire hazard.
  • Page 31 Peaco Support FC280 Series VFD User Manual Chapter 3 Installation 3.6.2 Control circuit terminal description Terminal Terminal function description S1-DCM Multifunctional input terminal 1 S2-DCM Multifunctional input terminal 2 S3-DCM Multifunctional input terminal 3 Function setting: F06.00~F06.05 S4-DCM Multifunctional input terminal 4...
  • Page 32 Peaco Support FC280 Series VFD User Manual Chapter 3 Installation less than 20m +10V Potentiometer Figure 3-5 Schematic diagram of analog input terminal wiring At some occasion where analog signal suffers severe interference, filter condenser or ferrite core shall be installed at the side of analog signal source, as Figure 3-6shows: wind 2~3 turns 0.022UF...
  • Page 33: Treatment Of Emc Problem

    Peaco Support FC280 Series VFD User Manual Chapter 3 Installation AC Driver electric relay Diode Figure 3-7 Wiring diagram of digital output terminal 3.7 Treatment of EMC problem 3.7.1 Effects of harmonic wave Ø Higher harmonic wave of power supply will cause damages to inverter. So in some places with bad power grid quality, we advise to install AC input reactor.
  • Page 34 Peaco Support FC280 Series VFD User Manual Chapter 3 Installation  Handling methods of interference from peripheral electromagnetic equipment on AC drive.Electromagnetic effects on inverter generally result from the inst- allation of many relays, contactors or electromagnetic contactors near AC drive.
  • Page 35 Peaco Support FC280 Series VFD User Manual Chapter 3 Installation Ø Separated ground connection for peripheral equipments can help to elimi- nate the interference from ground wires’leakage current of AC drive while common grounding. 3.7.3 Leakage current and treatment Leakage current has two categories when inverter is in service: One is leaka- ge current over the ground: and the other is leakage current between lines.
  • Page 36 Peaco Support FC280 Series VFD User Manual Chapter Operation and Display 4.1 Keypad description..................36 4.2 Function code examining and modifying methods explanation.....38 4.3 How to view status parameters..............40 4.4 Password setting...................40 4.5 Self-learning of motor parameters ( when vector control function)....41 www.peacosupport.com...
  • Page 37: Chapter 4 Operation And Display

    Peaco Support FC280 Series VFD User Manual Chapter 4 Operation and Display 4.1 Keypad description 4.1.1 Keypad explanation and function Keypad locates above AC drive, and can be divided into two parts: display area and control area. Display area shows parameter setting mode and different run state.
  • Page 38 Peaco Support FC280 Series VFD User Manual Chapter 4 Operation and Display Name Function Description Used to start AC drive operation.(This key has no 运行 effect when the drive is set to terminal run.) Keypad Used to stop the AC drive operation.If the AC drive has 停止STOP...
  • Page 39: Function Code Examining And Modifying Methods Explanation

    Peaco Support FC280 Series VFD User Manual Chapter 4 Operation and Display  In halted state ( Refer to more details of display items selection in F08.05): Display Code Item Fescription Operation 功能FUNC Setting frequency Press DATD设定 功能FUNC Bus voltage Press DATD设定...
  • Page 40 Peaco Support FC280 Series VFD User Manual Chapter 4 Operation and Display Explanation: In third-level menu operation, press PRGM or DATA to return to second-level menu. The difference between them: Press DATA to store the setting parameters into control panel, return to second-level menu, and automatically shift to next function code;...
  • Page 41: How To View Status Parameters

    Peaco Support FC280 Series VFD User Manual Chapter 4 Operation and Display 4.3 How to view status parameters In stop or running status, LED nixie tube can be used to display the multiple state parameters of AC drive. The function code F08.03( operating parameter1) and F08.05( stop parameter) can be used to select whether this state parameter...
  • Page 42: Self-Learning Of Motor Parameters ( When Vector Control Function)

    Peaco Support FC280 Series VFD User Manual Chapter 4 Operation and Display 4.5 Self-learning of motor parameters ( when vector control function) When you select vector control mode without PG, before inverter is running, you must input nameplate parameters of motors correctly. AC drives will match stan- dard motor parameters upon the nameplate parameters.
  • Page 43 Peaco Support FC280 Series VFD User Manual Chapter 4 Operation and Display No-load current: Mutual inductance calculation: I0 is no-load current, L is mutual inductive reactance, and L is leakage inductive δ reactance. -42- www.peacosupport.com sales@peacosupport.com Free Shipping Worldwide Reliable Supplier...
  • Page 44: Chapter 5 Function & Parameter Table

    Peaco Support FC280 Series VFD User Manual Chapter Function & Parameter Table 5.1 How to read the parameter list..............44 5.2 Functional group....................45 www.peacosupport.com sales@peacosupport.com Free Shipping Worldwide Reliable Supplier...
  • Page 45: How To Read The Parameter List

    Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table 5.1 How to read the parameter list The functional parameters of AC drives are grouping by function, total 16 groups from F00~F15. Each functional group includes several function codes. Function codes adopt three-level menu, for example, “F06.
  • Page 46: Functional Group

    Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Ž To make more effective parameter protection,AC drives provide password prote- ction for function codes. After users set password (the parameter of user passw- ord, F08. 00 set to non-0), and press PRGM/ ESC to enter into user parameter editingstate, the system will enter into user password authorization state, and display “0.
  • Page 47 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default 5:pulse(HDI) 6:multi-speed running Frequency A 7:simple PLC ● F00.06 command selection 8:PID control 9:RS485 Communication 10:potentiometer Frequency B ●...
  • Page 48 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default Model ※ Carrier frequency 0.5kHz~16.0kHz F00.17 dependent Carrier frequency 0: No ※ F00.18 adjustment with 1: Yes temperature 0: set by F00.04...
  • Page 49 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default Range of frequency B 100% ※ F00.23 source during 0%~150% superposition Frequency offset of ● frequency B source 0.00Hz~max.frequency F00.03...
  • Page 50 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default Time proportion of S- ● 0.0%~(100.0%-F01.07) 30.0% F01.06 curve start segment Time proportion of S- ※ 0.0%~(100.0%- F01.06) 30.0%...
  • Page 51 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default 0.001Ω~65.535Ω Stator resistance of (inverter power<= 55kW) Model ● F02.06 dependent 0.0001Ω~6.5535Ω asynchronous motor 1 (AC drive power> 55kW)...
  • Page 52 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default Encoder wire-break 0.0s: No action ● F02.36 fault detection time 0.1–10.0s 0: no self-learning 1: dynamic self- learning of Self-learning of motor ●...
  • Page 53 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default Digital setting of ※ F03.10 torque upper limit in 0.0%~200.0% 150.0% speed control mode Excitation adjustment ※ F03.13 0~60000...
  • Page 54 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default 7:MAX(AI1,AI2) Torque setting mode ※ F03.24 (corresponding to F03.26 selection digital setting) Torque setting by ※ F03.26 -200.0%~200.0%...
  • Page 55 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default ● Motor1 V/F voltage point 2 0.0%~100.0% 0.0% F04.06 F04.05~F02.02(motor Motor1 V/F frequency ● F04.07 0.00Hz point 3 rated frequency ●...
  • Page 56 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default Voltage rally judging time a ※ F05.03 0.00s~100.00s 0.50s instantaneous power failure Action judging voltage at 60.0%~100.0%(standard ※...
  • Page 57 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default Unit's digit:motor overload( E007) 0:coast to stop 1:stop according to the stop mode 2:continue to run Fault Ten's digit :power input phase loss (E012) protection ※...
  • Page 58 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default Ten thousand's digit :PID feedback lost Fault during running(E02E) protection 0:coast to stop ※ F05.23 00000 action 1:stop according to the stop mode...
  • Page 59 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default 13:Buffer resistance overload (E014) 14: Contactor fault (E017) 15: External equipment fault (E00d) 16: Communication fault(E018) 17: Current detection fault (E015)
  • Page 60 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default Input terminal status upon current ● F05.33 — — fault Output terminal status upon ● — — F05.34 current fault ●...
  • Page 61 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default Short-circuit to ground 0: Disabled ● F05.54 upon power-on 1: Enabled Output terminal action 0: Not act ●...
  • Page 62 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default 15: multi-speed terminal 4 16: Pause operation 17: Acc/Dec time selection 1 18: Acc/ Dec time selection 2...
  • Page 63 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default 48: external stop terminal 2 49: deceleration DC braking 50: clear the current running time 0: valid on high level...
  • Page 64 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default Corresponding setting ※ F06.21 -100.0%~+100.0% 100.0% of AI1 upper limit ※ F06.22 AI1 input filter time 0.00s~10.00s 0.10s ※...
  • Page 65 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default 4: curve 4( 4 point, see F06.40~F06.47) 5: curve 5( 4 point, see ※ AI curve selection F06.48~F06.55) H.321...
  • Page 66 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default AI curve 5 inflection point ※ F06.50 F06.48~F06.52 - 3.00V 1 input AI curve 5 inflection point ※...
  • Page 67 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default 6: zero-speed running (no output at stop) 7: zero-speed running 2(no output at stop) 8: frequency upper limit reached...
  • Page 68 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default 37: Frequency lower limit reached (having output at stop) 38: Alarm output (keep running) ※ 39: motor overheat warning...
  • Page 69 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default 15: output voltage(100.0% corresponding to 1000.0V) 16: reserved ※ AO1 offset coefficient -100.0%~100.0% 0.0% F07.15 ※ AO1 gain -10.00~+10.00...
  • Page 70 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default Bit13: AI2 voltage (V) ※ Bit14: AI3 voltage (V) Bit15: count value 0000–FFFF Bit00: length value Bit01: PLC stage...
  • Page 71 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default 0: Operating frequency 1: Set frequency 2: Output current 3: Output voltage 4: Load speed display 5: Output power...
  • Page 72 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default Model ※ Deceleration time 4 0.0s~6500.0s F09.05 dependent 0.00Hz~F00.03( max. ※ F09.06 JOG running frequency 2.00Hz frequency) ※...
  • Page 73 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default Detection range of 0.0%~100.0%( F00.03 ( ※ 0.0% F09.24 frequency reached max. frequency) ) Jump frequency during 0: disabled ※...
  • Page 74 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default 0: Disabled ※ Timing function F09.43 1: Enabled 0: F09.45 1: analog AI1 2: analog AI2 ※ Timing duration source F09.44...
  • Page 75 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default 0: PWM random disabled Depth of PWM ※ F09.58 1~10: PWM carrier frequen-cy random random depth 0: Disabled ※...
  • Page 76 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default 0: PID output is positive characteristic PID output characteristic ※ F10.03 selection 1: PID output is negative characteristic ※...
  • Page 77 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default Maximum deviation ※ F10.24 between two PID outputs 0.00%~100.00% 1.00% in reverse direction Unit's digit :Integral separated 0: Invalid...
  • Page 78 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default Number of pulses per ※ F11.07 0.1~6553.5 100.0 meter ※ F11.08 Set count value 1~65535 1000 ※ F11.09 Designated count value 1~65535...
  • Page 79 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default ※ Multi-speed 12 -100.0%~100.0% 0.0% F12.14 ※ Multi-speed 13 -100.0%~100.0% 0.0% F12.15 ※ Multi-speed 14 -100.0%~100.0% 0.0% F12.16 ※...
  • Page 80 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default Running time of simple ※ F12.30 0.0s(h)~6500.0s(h) 0.0s(h) PLC multi-speed 6 Acceleration/deceleration ※ F12.31 time of simple PLC multi- 0~3...
  • Page 81 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default Running time of simple ※ F12.44 0.0s(h)~6500.0s(h) 0.0s(h) PLC multi-speed 13 Acceleration/deceleratio ※ F12.45 n time of simple PLC 0~3...
  • Page 82 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default 5: 9600BPS 6: 19200BPS Data format 7: 38400BPS 8: 57600BPS 9: 115200BPS 0: No check, data format <8,N,2>...
  • Page 83 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default 0.001Ω~65.535Ω (AC drive power≤ 55kW) Model Stator resistance ● F15.06 dependent 0.0001Ω~6.5535Ω (AC drive power> 55kW) 0.001Ω~65.535Ω (AC drive power≤ 55kW)...
  • Page 84 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default Speed feedback PG disc- 0.0: No action F15.36 ● onnection detection time 0.1s~10.0s 0: No self-learning 1: Asynchronous motor F15.37...
  • Page 85 Peaco Support FC280 Series VFD User Manual Chapter 5 Function & Parameter Table Factory Function Description Name Change code (setting range) Default Excitation adjustment ※ F15.51 0~60000 2000 proportional gain Excitation adjustment ※ 0~60000 1300 F15.52 integral gain Torque adjustment ※...
  • Page 86 Peaco Support FC280 Series VFD User Manual Chapter Description of Function Codes F00 Standard Function Parameters............86 F01 Standard Function Parameters............98 F02 Motor 1 Parameters..............104 F03 Vector Control Parameters............108 F04 V/F Control Parameters.............114 F05 Fault and Protection..............120 F06 Input Terminals.................131 F07 Output Terminals...............146...
  • Page 87 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Group F00: Standard Function Parameters Factory Function Description Name Change code (setting range) Default ) 0: non-PG vector control (SVC ● F00.00 Speed control mode ( )...
  • Page 88 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes 2:RS485 communication control Commands are given from host computer. Refer to Group F13: Communication Parameters for parameters. Factory Function Description Name Change code (setting range) Default 50.00Hz ●...
  • Page 89 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default 2:analog AI1 3:analog AI2 4:analog Ai3 5:pulse(HDI) Frequency A ● F00.06 6:multi-speed running command selection 7:simple PLC 8:PID control...
  • Page 90 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes When AI is used as the frequency setting source, the corresponding value 100% of the volta- ge/current input corresponds to the value of F06. 5: Pulse setting (HDI) The frequency given is given by the terminal pulse.
  • Page 91 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes When used as an independent frequency input channel (frequency source switched over from A to B), the auxiliary frequency source B is used in the same way as the main frequency source A (refer to F00.06).
  • Page 92 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes It is used o select the frequency setting channel. If the frequency source involves Aan d operation, you can set the frequency offset in F00.25 for superposition to the A and B oper- ation result, flexibly satisfying various requirements.
  • Page 93 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Note: When modifying this function parameter, the decimal places of all frequency-related parameters will change, and the corresponding frequency value will also change. Special attention should be paid during use.
  • Page 94 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default Acceleration/Decele ● 0: 1s; 1: 0.1s; 2: 0.01s F00.14 ration time unit To satisfy requirements of different applications, the provides three acceleration/ deceleration time units, 1s, 0.1s and 0.01s.
  • Page 95 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Relationship between model and carrier frequency: Highest carrier Lowest carrier Carrier frequency Default(kHz) frequency(kHz) frequency (kHz) Model G model:0.75kW~11kW P model:0.75kW~15kW G model:15kW~45kW P model:18.5kW~55kW G model:55kW P model:75kW...
  • Page 96 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default 2:analog AI2 3:analog AI3 Source of frequency ● F00.19 upper limit 4:pulse(HDI) 5:RS485 comminication It is used to set the source of the frequency upper limit, including digital setting (F00.04), AI,pulse setting or communication setting.
  • Page 97 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default 2: analog Ai1 3: analog Ai2 4: analog Ai3 5:pulse setting (HDI) 6: multi- speed run setting 7: Simple PLC...
  • Page 98 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default Frequency offset of 00.00Hz ● F00.25 frequency B source 0.00Hz~max.frequency F00.03 during superposition If the frequency source involves A and B operation, you can set the frequency offset in F00.25 for superposition to the A and B operation result, flexibly satisfying various requirements.
  • Page 99 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Group F01: Start-stop Control Parameters Factory Function Description Name Change code (setting range) Default 0:direct start 1: rotational speed tracking ※ F01.00 Start mode restart 2: pre-excited start...
  • Page 100 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default Startup DC braking ● F01.03 current/ Pre-excited 0%~100% current Startup DC braking ● 0.0s~100.0s 0.0s F01.04 time/ Pre-excited time Startup DC braking is generally used during restart of the AC drive after the rotating motor stops.
  • Page 101 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes In this curve, the rated motor frequency fb is always the inflexion point. This mode is usually used in applications where acceleration/deceleration is required at the speed higher than the rated frequency.
  • Page 102 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default 0: deceleration to stop ● F01.08 Stop mode 1:stop freely 0: Decelerate to stop After the stop command is enabled, the AC drive decreases the output frequency according to the deceleration time and stops when the frequency decreases to zero.
  • Page 103 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Output frequency (Hz) Initial frequency of stop DC braking Time (t) Effective value of output voltage stop DC braking Stop DC braking Time t Stop DC braking time command Fig.6-4 Stop DC braking process...
  • Page 104 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default Rotational speed ※ F01.14 1~100 tracking speed In the rotational speed tracking restart mode, select the rotational speed tracking speed. The larger the value is, the faster the tracking is.
  • Page 105 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Group F02: Motor 1 Parameters Factory Function Description Name Change code (setting range) Default 0:common asynchronous motor ● F02.00 Motor type selection 1:variable frequency asynchro- nous motor...
  • Page 106 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default 0.1mH~6553.5mH Mutual inductive (inverter power<= 55kW) Model ● reactance of F02.09 dependent 0.01mH~655.35mH asynchronous motor 1 (AC drive power> 55kW)...
  • Page 107 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default AB phase sequence 0: forward ● of ABZ incremental F02.30 1: reverse encoder This parameter is valid only for ABZ incremental encoder (F02.27 = 0) and is used to set the A/B phase sequence of the ABZ incremental encoder.
  • Page 108 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Before performing static self-learning, properly set the motor type and motor nameplate par- ameters of F02.00 to F02.05 first. The AC drive will obtain parameters of F02.06 to F02.08 by dynamic self-learning.
  • Page 109 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Group F03: Vector Control Parameters Group F03 is valid for vector control, and invalid for V/F control. Factory Function Description Name Change code (setting range) Default Proportional gain 1 of ※...
  • Page 110 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes The speed dynamic response characteristics in vector control can be adjusted by setting the proportional gain and integral time of the speed regulator. To achieve a faster system response, increase the proportional gain and reduce the integral time.
  • Page 111 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Increase the over-excitation gain if the AC drive is liable to overvoltage error during decelera- tion. Too large over-excitation gain, however, may lead to an increase in output current.
  • Page 112 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes These are current loop PI parameters for vector control. These parameters are automatically obtained through "Asynchronous motor complete self-learning" or "Synchronous motor nolo- ad self-learning", and need not be modified.
  • Page 113 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default Speed/torque control 0: speed control ※ F03.23 mode selection 1: torque control 0: digital setting (F03.26) 1:analog AI1...
  • Page 114 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes In the torque control mode, the difference between the motor output torque and the load torq- ue determines the speed change rate of the motor and the load. Therefore, the motor speed may change rapidly, causing problems such as excessive noise or mechanical stress.
  • Page 115 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Group F04: V/F Control Parameters Group F04 is valid only for V/F control. The V/F control mode is applicable to low load applications (fan or pump) or applications where one AC drive operates multiple motors or there is a large difference between the AC drive power and the motor power.
  • Page 116 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default 0.0%:( auto torque boost) Model ● F04.01 Motor 1 torque boost dependent 0.1%~30.0% 0.00Hz~F00.03( Cut-off frequency of motor ●...
  • Page 117 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default Motor1 V/F frequency ● F04.03 0.00Hz~F04.05 0.00Hz point 1 ● F04.04 Motor1 V/F voltage point 1 0.0%~100.0% 0.0% Motor1 V/F frequency ●...
  • Page 118 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default Motor1 V/F slip ※ F04.09 0.0%~200.0% 0.0% compensation gain This parameter is valid only for the asynchronous motor.
  • Page 119 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default 0: digital setting (F04.14) 1: analog AI1 2: analog AI2 3: analog AI3 4: pulse (HDI) Voltage source for V/F ※...
  • Page 120 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes 6: Simple PLC If the voltage source is simple PLC mode, parameters in group F12 must be set to determine the setting output voltage. 7: PID control The output voltage is generated based on PID closed loop.
  • Page 121 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Group F05: Fault and Protection Factory Function Description Name Change code (setting range) Default 0: disabled ※ F05.00 Input phase loss protection 1: enabled It is used to determine whether to perform input phase loss or contactor energizing protection.
  • Page 122 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Voltage rally judging time at instantaneous power failure F5.03 F5.03 Bus voltage Action judging voltage at instantaneous power failure F5.04 Time Running frequency Action pause judging voltage at instantaneous F5.02=1:Decelerate...
  • Page 123 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes DC bus voltage Overvoltage stall point Time(t) Output frequency (Hz) Time(t) Fig.6-10 Diagram of the overvoltage stall protection function Factory Function Description Name Change code (setting range) Default ※...
  • Page 124 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Output current Overcurrent stall protective current Time(t) Output frequency (Hz) Overcurrent anti-stall gain is determined by F05.07 Time(t) Fig.6-11 Diagram of the overcurrent stall protection function Factory...
  • Page 125 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default Protection upon load 0: disabled ※ F05.12 becoming 0 1: enabled Detection level of load 0.0~100.0% (rated motor ※...
  • Page 126 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes If F05.18 (Detection time of too large speed deviation) is 0.0s, this function is disabled. Factory Function Description Name Change code (setting range) Default ※ Fault auto reset times 0~20...
  • Page 127 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default Fault protection Ten thousand's digit ※ F05.22 00000 action (Accumulative running time reached)(E020) selection 2 Unit's digit: reserved Ten's digit: reserved...
  • Page 128 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default 0:Current running frequency Frequency 1:Set frequency selection for ※ F05.26 continuing 2:Frequency upper limit to run upon 3:Frequency lower limit...
  • Page 129 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default If a input terminal is ON, the setting is 1. Input terminal If the DI is OFF, the setting is 0. The ●...
  • Page 130 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default Output terminal status upon ● F05.42 — 2nd fault ● F05.43 AC drive status upon 2nd fault —...
  • Page 131 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default 0.0%~ 100.0% Backup frequency ● F05.56 (100.0% corresponding to 100.0% upon abnormality maximum frequency)F00.03) When the abnormal standby frequency is selected to run, the value set by F05.56 is a percentage relative to the maximum frequency.
  • Page 132 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Group F06: Input Terminals The provides six multi-function digital input ( DI) terminals and three analog input (AI) termin- als. The optional extension card provides another four DI terminals (S7 to HDI) , (HDI can be used for high-speed pulseinput).
  • Page 133 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Value Function Description The terminal is used for fault reset function, the same Fault reset (RESET) as the function of RESET key on the operation panel. Remote fault reset is implemented by this function.
  • Page 134 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Value Function Description It enables the AC drive to maintain the current Acceleration/Decelerati frequency output without being affected by external on prohibited signals (except the STOP command).
  • Page 135 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Value Function Description After this terminal becomes ON, the integral adjust- PID integral pause ment function pauses. However, the proportional and differentiation adjustment functions are still valid.
  • Page 136 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Value Function Description When this terminal becomes ON, the AC drive's Clear the current current running time is cleared. This function must be running time supported by F09.43 and F09.54.
  • Page 137 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes State combinations of two terminals for acceleration/deceleration time selection as follow table: Acceleration Time Corresponding Terminal 2 Terminal 1 selection Parameters Acceleration time 1 F00.12、F00.13 Acceleration time 2 F09.00、F09.01...
  • Page 138 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes 1: Low level valid The DI terminal (S) is invalid when being connected with COM, and invalid when being disco- nnected from COM. Factory Function Description Name...
  • Page 139 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes RUN command STOP STOP Sy(REV) Forward RUN Reverse RUN Fig.6-13 Setting of 2-wire control 2 2: 3-wire control 1 In this mode, EN is RUN enabled terminal, and the direction is decided by Sw1 and SW3.STOP command is by normal close SW2.
  • Page 140 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default Terminal UP/DOWN ※ F06.14 0.001Hz/s~65.535Hz/s 1.00Hz/s rate It is used to adjust the rate of change of frequency when the frequency is adjusted by means of terminal UP/DOWN.
  • Page 141 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes However, increase of the AI filter time will slow the response of analog detection. Set this par- ameter properly based on actual conditions. Corresponding set value (frequency, torque) 100.0%...
  • Page 142 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default ※ Ai3 upper limit F06.28~+10.00V 4.00V F06.30 Corresponding setting ※ F06.31 -100.0%~+100.0% 100.0% of AI3 upper limit ※...
  • Page 143 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default tens'digit: AI2 curve selection ※ AI curve selection hundreds'digit: AI3 curve H.321 F06.38 selection The unit's digit, ten's digit and hundred's digit of this parameter are respectively used to select the corresponding curve of AI1, AI2 and AI3.
  • Page 144 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default ※ AI curve 4 lower limit -10.00V~F06.42 0.00V F06.40 AI curve 4 lower limit ※ F06.41 -100.0%~+100.0% 0.0%...
  • Page 145 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes AI corresponding setting Corresponding setting of AI max. input Corresponding setting of Max.input of AI AI curve AI input 0 V (0 mA) voltage AI curve 10 V (20 mA)
  • Page 146 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes For example: the voltage of the analog input AI1 fluctuates around 5.00V, the fluctuation range is 4.90V~ 5.10V, the minimum input of AI1 is 0.00V corresponds to 0.0%, and the maximum input of 10.00V corresponds to 100.%, then the detected AI1 corresponds to the setting It fluctuates...
  • Page 147 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Group F07: Output Terminals The provides 2 analog output (AO) terminal, 1 open-collector switch signal output, 2 relay ter- minal and a HDO terminal (used for high-speed pulse output or open-collector switch signal output) as standard.
  • Page 148 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Value Function Description AC drive overload The terminal becomes ON 10s before the AC drive pre-warning overload protection action is performed. zero-speed If the AC drive runs with the output frequency of 0, the running(no output terminal becomes ON.
  • Page 149 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Value Function Description When the input of AI1 is larger than the input of AI2, the Ai1> Ai2 terminal becomes ON. undervoltage state If the AC drive is in undervoltage state, the terminal output becomes ON.
  • Page 150 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Value Function Description frequency lower limit If the running frequency reaches the lower limit, the reached(having terminal becomes ON. In the stop state, the signal is output at stop) still ON.
  • Page 151 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes These parameters are used to set the delay time of output terminals HDO, relay 1, relay 2, MO1 from status change to actual output. Factory Function Description...
  • Page 152 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Value Function Description setting frequency 0 to maximum output frequency output voltage 100% corresponding to 0.0V~1000.0V 1000.0V Factory Function Description Name Change code (setting range) Default ※...
  • Page 153 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Group F08: Keypad And Display Factory Function Description Name Change code (setting range) Default ※ F08.00 User password 0~65535 Press FUNC/DATA key to confirm password. Don’t press again within 1 minute, password will saved.
  • Page 154 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default LED display running ※ F08.04 0000–FFFF H.0000 parameters 2 7 6 5 4 3 2 1 0 Length value...
  • Page 155 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes 7 6 5 4 3 2 1 0 Set frequency (Hz) Bus voltage (V) Input terminal status Output terminal status PID setting AI1 voltage (V) AI2 voltage (V)
  • Page 156 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default Accumulative running time 0h~65535h — F08.10 Product number — — F08.11 These function code can not be modify.
  • Page 157 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default Accumulative power 0–65535 kWh — F08.14 consumption It is used to display the accumulative power consumption of the AC drive until now.
  • Page 158 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Group F09: Auxiliary Functions Factory Function Description Name Change code (setting range) Default Model ※ Acceleration time 2 0.0s~6500.0s F09.00 dependent Model ※ Deceleration time 2 0.0s~6500.0s F09.01...
  • Page 159 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes If the set frequency is within the frequency jump range, the actual running frequency is the jump frequency close to the set frequency. Setting the jump frequency helps to avoid the mechanical resonance point of the load.
  • Page 160 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default 0: enabled ※ F09.13 Reverse control 1: disabled It is used to set whether the AC drive allows reverse rotation. In the applications where reve- rse rotation is prohibited, set this parameter to 1.
  • Page 161 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes This parameter is used to set whether to enable the safety protection. If it is set to 1, the AC drive does not respond to the run command valid upon AC drive power-on (for example, an input terminal is ON before power-on).
  • Page 162 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Output frequency (Hz) FDT level FDT hysteresis =F09.20 * F09.21 Time (t) Frequency reached detection signal (MO, relay) Time (t) Fig.6-20 The FDTfunction Factory Function Description Name...
  • Page 163 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default Jump frequency during 0: disabled ※ F09.25 acceleration/deceleration 1: enabled It is used to set whether the jump frequencies are valid during acceleration/deceleration.
  • Page 164 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Output frequency (Hz) Set frequency Deceleration time 1 Acceleration time 1 F09.28 Deceleration time 2 F09.29 Acceleration time 2 Time (t) Fig.6-23 Acceleration/deceleration times witchover During acceleration, if the running frequency is smaller than the value of F09.28, acceleration time 2 is selected.
  • Page 165 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes If the output frequency of the AC drive is within the positive and negative amplitudes of the any frequency reaching detection value, the corresponding multi-function output becomes ON.The provides two groups of any frequency reaching detection parameters, inclu-ding...
  • Page 166 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default 1.1% (no detection) Output overcurrent ※ F09.37 1.2%–300.0% (rated 200.0% threshold motor current) Output overcurrent detectio ※ 0.00s~600.00s 0.00s...
  • Page 167 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Output current Any current reaching amplitude Any current reaching Any current reaching amplitude Any current reaching detection signal MD1 or relay Fig.6-27 Any current reaching detection Factory...
  • Page 168 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes These two parameters are used to set the limits of the input voltage to provide protection on the AC drive. When the AI1 input is larger than the value of F09.47 or smaller than the value of F09.46, the corresponding multi-function output terminal becomes ON, indicating that AI1...
  • Page 169 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes When the AC drive is in dormant state and the current running command is effective, the AC drives starts up after the wakeup delay time (F09.51) if the set frequency is higher than or equal to the wakeup frequency (F09.50).
  • Page 170 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Only valid for V/F control. Synchronous modulation means that the carrier frequency chang- es linearly with the output frequency, ensuring that the ratio of the two (carrier ratio) remains unchanged.
  • Page 171 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default Current detection ※ F09.60 0~100 compensation It is used to set the current detection compensation of the inverter. If the setting is too large, the control performance may be degraded.
  • Page 172 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Set for 1140V voltage level. Adjusting this value can improve the effective utilization rate of the voltage, and if the adjustment is too small, it will easily lead to unstable system operation.
  • Page 173 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Group F10: Process Control PID Function PID control is a general process control method. By performing proportional, integral and differential operations on the difference between the feedback signal and the target signal, it adjusts the output frequency and constitutes a feedback system to stabilize the controlled counter around the target value.
  • Page 174 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default 0: AI1 1: AI2 2: AI3 3: AI1–AI2 4: Pulse setting(HDI) ※ F10.02 PID feedback source 5: Rs485 communication...
  • Page 175 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default ※ Proportional gain Kp1 0.0~100.0 20.0 F10.05 ※ Integral time Ti1 0.01s~10.00s 2.00s F10.06 ※ Differential time Td1 0.000s~10.000s...
  • Page 176 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes setting value deviation limit feedback time output frequency time Fig.6-29 Relation between deviation limit and output frequency Factory Function Description Name Change code (setting range) Default ※...
  • Page 177 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes F10.12 is used to filter the PID feedback, helping to reduce interference on the feedback but slowing the response of the process closed-loop system. F10.13 is used to filter the PID output frequency, helping to weaken sudden change of the AC drive output frequency but slowing the response of the process closed-loop system.
  • Page 178 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes PI parameter Group 1 of PID parameters F10.05、F10.06、F10.07 Group 1 of PID parameters F10.15、F10.016、F10.17 PID deviation P10.19 P10.20 Fig.6-30 PID parameters switchover Factory Function Description Name Change...
  • Page 179 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default Maximum deviation ※ F10.23 between two PID outputs 0.00%~100.00% 1.00% in forward direction Maximum deviation ※ between two PID outputs 0.00%~100.00%...
  • Page 180 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default Detection value of PID 0.0%: Not judging feedback ※ F10.26 0.0% feedback loss loss 0.1%–100.0% Detection time of PID ※...
  • Page 181 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Group F11: Swing Frequency, Fixed Length and Count The swing frequency function is applied to the textile and chemical fiber fields and the applic- ations where traversing and winding functions are required.
  • Page 182 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default Swing frequency ※ F11.01 0.0%~100.0% 0.0% amplitude Jump frequency ※ 0.0%~50.0% 0.0% F11.02 amplitude Use this parameter to determine the value of swing amplitude and kick frequency.
  • Page 183 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default ※ Number of pulses per meter 0.1~6553.5 100.0 F11.07 The preceding parameters are used for fixed length control.
  • Page 184 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Group F12: Simple PLC Function And Multi-speed control The multi-command has many functions. Besides multi-speed, it can be used asthe setting source of the V/F separated voltage source and setting source of process PID. In addition, the multi-command is relative value.
  • Page 185 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes 1: Keep final values after the AC drive runs one cycle The AC drive keeps the final running frequency and direction after running one cycle. 2: Repeat after the AC drive runs one cycle The AC drive automatically starts another cycle after running one cycle, and will not stop until receiving the stop command.
  • Page 186 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default ※ Multi-speed 7 -100.0%~100.0% 0.0% F12.09 ※ Multi-speed 8 -100.0%~100.0% 0.0% F12.10 ※ Multi-speed 9 -100.0%~100.0% 0.0% F12.11 ※...
  • Page 187 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default Acceleration/deceleration time of ※ F12.23 0~3 simple PLC multi-speed 2 Running time of simple PLC ※ 0.0s(h)~6500.0s(h) 0.0s(h) F12.24...
  • Page 188 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default Running time of simple PLC ※ 0.0s(h)~6500.0s(h) 0.0s(h) F12.40 multi-speed 11 Acceleration/deceleration time ※ 0~3 F12.41 of simple PLC multi-speed 11 Running time of simple PLC ※...
  • Page 189 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Group F13: Communication Parameters Factory Function Description Name Change code (setting range) Default Local communication 1~247,0-bit broadcast ※ F13.00 address address When the local address is set to 0, it is the broadcast address, which realizes the broadcast function of the upper computer.
  • Page 190 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Factory Function Description Name Change code (setting range) Default ※ Response delay 0ms~20ms F13.03 Communication response delay: It refers to the interval time from the end of the inverter's data reception to the time when the data is sent to the upper computer.
  • Page 191 Peaco Support FC280 Series VFD User Manual Chapter 6 Description of Function Codes Group F15: Motor 2 Parameters The series products can be switched between 2 motors, the motor nameplate parameters can be set separately for the 2 motors, the motor parameter self-learning can be performed separately, the V/F control or vector control can be selected separately, the encoder-related parameters can be set separately, and the parameters can be set separately.
  • Page 192 Peaco Support FC280 Series VFD User Manual Chapter Fault Diagnosis and Trouble Shooting 7.1 Faults and Solutions..................192 7.2 Common Faults and Solutions..............198 www.peacosupport.com sales@peacosupport.com Free Shipping Worldwide Reliable Supplier...
  • Page 193 Peaco Support FC280 Series VFD User Manual Chapter 7 Fault Diagnosis and Trouble Shooting 7.1 Faults and Solutions The inverter has a total of 34 warning information and protection functions. Once a fault occ-urs, the protection function will act, the inverter will stop output, the inverter fault relay contact will act, and the fault code will be displayed on the inverter display panel.
  • Page 194 Peaco Support FC280 Series VFD User Manual Chapter 7 Fault Diagnosis and Trouble Shooting Display Fault name Possible Causes Solutions AC drive output circuit is eliminate external faults; ground or short circuit; self-learning of motor no self-learning of motor parameter;...
  • Page 195 Peaco Support FC280 Series VFD User Manual Chapter 7 Fault Diagnosis and Trouble Shooting Display Fault name Possible Causes Solutions Whether protection setting parameter correctly; parameter F05.10 is reduce the load and check suitable; Motor the motor and mechanical E007...
  • Page 196 Peaco Support FC280 Series VFD User Manual Chapter 7 Fault Diagnosis and Trouble Shooting Display Fault name Possible Causes Solutions EEPROM The EEPROM chip is Replace the main control E00F readwrite damaged. board. fault the three-phase power input is abnormal.
  • Page 197 Peaco Support FC280 Series VFD User Manual Chapter 7 Fault Diagnosis and Trouble Shooting Display Fault name Possible Causes Solutions the host computer is in check the cabling of host abnormal state. computer. the communication cable check the communication is faulty.
  • Page 198 Peaco Support FC280 Series VFD User Manual Chapter 7 Fault Diagnosis and Trouble Shooting Display Fault name Possible Causes Solutions overvoltage exists. handle based on overvoltage. AC drive E033 hardware fault overcurrent exists. handle based on overcurrent. the encoder set the encoder parameters parameters are set properly.
  • Page 199 Peaco Support FC280 Series VFD User Manual Chapter 7 Fault Diagnosis and Trouble Shooting 7.2 Common Faults and Solutions You may come across the following faults during the use of the AC drive. Refer to the following table for simple fault analysis.
  • Page 200 Peaco Support FC280 Series VFD User Manual Chapter 7 Fault Diagnosis and Trouble Shooting Fault name Possible Causes Solutions Power on the the cabling of the inverter shows temperature sensor replace the damaged fan. normal, after becomes loose. running, it will eliminate external fault.
  • Page 201 Peaco Support FC280 Series VFD User Manual Chapter 7 Fault Diagnosis and Trouble Shooting Fault name Possible Causes Solutions 1.the encoder is faulty. 1.replace the encoder The motor 2.the encoder cable is and ensure the cabling is speed is always connected incorrectly or in proper.
  • Page 202 Peaco Support FC280 Series VFD User Manual Chapter Appendix Appendix A: Serial Communications..............202 Appendix B: Accessories Selection..............212 www.peacosupport.com sales@peacosupport.com Free Shipping Worldwide Reliable Supplier...
  • Page 203 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix Appendix A: Serial Communications AC drive, provide the RS485 communication interface, and adopt the ModBus communicatio- n protocol of international standard to make master- slave communication. Users can realize centralized control by PC/ PLC, upper computer controlling and so on( set the controlling co- mmand, operation frequency, correlation function code parameters change, inverter working state and fault information monitoring, etc.
  • Page 204 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix “query/ command” of the host. Host here refers to the personal computer ( PC) , industrial control equipment or programmable logic controller ( PLC) , etc. , and slave refers to BD330 series inverter or other controlling equipment of the same communication protocol.
  • Page 205 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix DATA(n - 1) DATA(n - 2) Data: function code parameter address,number of function code parameter ,value of function code parameter …………… DATA 0 CRC CHK high- order Check value: CRC CRC CHK low- order T1- T2-T3-T4( 3.
  • Page 206 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix hen F13.05 set to 1: Number of bytes Data address F002H high- order Data address F002H low- order Data address F003H high- order Data address F003H low- order CRC CHK low- order...
  • Page 207 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix CRC checking methods- - - CRC( Cyclical Redundancy Check) : Use the RTU frame format, and frame contains frame error detection domain ba- sed on CRC calculation. CRC domain detects the content of the entire frame.
  • Page 208 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix The definition of communication data address: : This part is the address definition of communication data, and used to con- trol the operation of the inverter, obtain inverter state information and rel- ated function parameters settings,etc.
  • Page 209 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix Control command input to AC drive: (only write) Command Address Command Function 0001H forward running : 0002H reverse running : 0003H forward jog : 1000H 0004H reverse jog : 0005H free stop :...
  • Page 210 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix Pulse output control: (only write) Command Address Command Function 1004H 7FFF means 0% 100% ~ ~ Read AC drive status: (only write) Status address Status Command Function 0001: forward running...
  • Page 211 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix Note: 4communication setting value is relative percentage(-100. 00% 100. ~ 00% ) , and can make communication write operations.When setting as frequency source, relative is the largest frequency(F00.03);When setting as torque source, relative is F03.10,F15.48 (motor1,motor2.)
  • Page 212 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix AC Drive fault address AC Drive fault information 0013H: accumulative running time reached E020 ( ) 0014H: EEPROM readwrite fault E00F ( ) 0015H: Short circuit to ground E023 (...
  • Page 213 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix Appendix B: Accessories Selection 1.Beake unit and brake resistance Brake unit Brake resistance AC drive Quantity Quantity Power Model Power(W)/Resistance value(Ω) (piece) (piece) 220V 0.55KW ---- 0.75KW ---- 1.5KW ---- 2.2KW...
  • Page 214 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix Brake unit Brake resistance AC drive Quantity Quantity Power Model Power(W)/Resistance value(Ω) (piece) (piece) 380V 160KW 30000 DBU-4160 200KW 35000 220KW 40000 250KW 44000 13.6 280KW 50000 315KW DBU-4280 55000...
  • Page 215 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix  The resistance of the resistor that over 2500W and the power are the total amount of resistance and power. The power of the resistor is get from parallel connection based on 2500W. For example, to get a...
  • Page 216 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix 2.Mounting dimension of brake resistance Ød Rated L1(±2) L2(±5) L3(±3) D(±2) H1(±3) power 1000 1500 2000 2500 3.Display panel 92mm 86mm 编程PRGM ESC退出 60mm STOP STOP 编程PRGM 正转FWD ESC退出 REV反转...
  • Page 217 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix Appendix C: Mini Series introduction 1. Specification model Rated power Rated input Rated output Adaptive Models (KW) current (A) current(A) motor (KW) Single- phase 220V±15%, 47/63Hz 2S-0.7G 0.75 0.75 2S-1.5G 14.0...
  • Page 218 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix Power Housing No (KW) (mm) (mm) (mm) (mm) (mm) (mm) 220V:0.75-2.2 380V:0.75-3.7 220V:3.7-5.5 380V:5.5-7.5 3. Control Circuit and Main Circuit Wirin -217- www.peacosupport.com sales@peacosupport.com Free Shipping Worldwide Reliable Supplier...
  • Page 219 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix 4. Display panel The Apparatus Size of the Digital Hand-Held Programming Panel. 5. Functional group Except for the following parameters, other parameters are the same as those in Chapter 5.
  • Page 220 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix Appendix D: Single Phase Output Series 1. Specification model Input output Rated power Rated input Rated output Models voltage voltage (KW) current (A) current(A) 2SS-0.5G 0.55 2SS-0.7G 0.75 1PH 220 1PH 220 2SS-1.5G...
  • Page 221 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix 3. Wiring diagram 220V Single Phase Output Series Ground Wire Single Phase 220V Single Phase 220V(U/V) 380V Single Phase Output Series Ground Wire Three Phase 380V Single Phase 380V(U/V) -216- -220- www.peacosupport.com...
  • Page 222 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix Appendix E: 220V Input, 380V Output Series 1. Specification model Input Output Rated power Rated input Rated output Models voltage voltage (KW) current (A) current(A) FC280-2S/4T-0.75G 0.75 FC280-2S/4T-1.5G FC280-2S/4T-2.2G FC280-2S/4T-3.7G FC280-2S/4T-5.5G...
  • Page 223 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix 3. Wiring diagram Ground Wire Three Phase 380V(U/V/W) Single Phase 220V -216- -222- www.peacosupport.com sales@peacosupport.com Free Shipping Worldwide Reliable Supplier...
  • Page 224 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix Appendix F: Elevator & Lift Series 1. Wiring diagram Analog speed given Supports two kinds of speed given: Analog speed given and multi-stage speed given; Life controller sends out speed command curve, inverter get speed given command throu- gh the analog signal.
  • Page 225 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix Built-in Emergency leveling mode In the using of eleva tor, if the power is cut suddenly, passengers may be kept in the cage.I- nverters can support emergency UPS power running, Both the main circuit and the working are powered by 220V UPS.
  • Page 226 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix Factory Function Description Name Change code (setting range) Default F6 Group S1 terminal function 0: No function ● F06.00 selection 1: Forward running S2 terminal function ● F06.01 2: Reverse running...
  • Page 227 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix Factory Function Description Name Change code (setting range) Default ● Brake open frequency (down) 0.00 〜10.00Hz 1.00Hz F26.07 ● Brake close frequency (down) 0.00 〜10.00Hz 0.20Hz F26.08 ● Brake open current 0.0 〜100.0%...
  • Page 228 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix The detailed Solution steps for setting inverter used on Elevator Step 1: F00.28 set to “T to confirm, restore the factory value. Step 2: F00.01 is Tto confirm, and then press PRG to exit, and then close the UP Down terminals.
  • Page 229 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix Step 7: set the acceleration and deceleration should be F05.05=0 F00.12/F0-13/ F09.00 / F09.01 /F09.02 /F09.03 / F09.04/F09.05 all set2.5. Step 8: F07.02= 7 when the inverter is stopped or 0Hz is running TA-TB, normally open change into normally closed F00.01 = 1 Terminal control...
  • Page 230 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix Appendix G: Off Grid Solar Series 1. Wiring diagram Barren Hill Management AC/DC PV array SI200 Ecological governance Power Grassland irrigation Power grid Soil erosion protection pool drinking water Generator Water pump SI200 Series Solar VFD Wiring Method(For mini power 0.4-7.5kw)
  • Page 231 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix Three phase 380 VAC Alternate AC power supply, for example, wiring diagram such as following: Spare AC input, Pump AC DC cannot When reverse, input at the change any same time two cables Remote floating...
  • Page 232 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix Max DC input Rated output Applicable water Model ( 380V) current ( A) current ( A) pump ( KW) 4T0055G/0075P 23.9 14.0 4T0075G/0110P 30.6 17.0 4T0110G/0150P 39.2 4T0150G/0185P 3. Installation and Commissioning Instructions for Phot ovoltaic Water Pumps 3.1 Wiring:...
  • Page 233 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix 3.2 Set the working mode of the photovoltaic water pump: There are two working modes for the photovoltaic water pump. The first one is CVT mode. In this working mode, only two parameters need to be set (F16.00 is set to 1, which is used to select CVT working mode;...
  • Page 234 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix 3.5 Introduction to related faults of photovoltaic water pump: Œ Sleep display U-L1 When the inverter panel displays this code, it means that the inverter enters sleep mode (not a fault). It will enter sleep mode only when the inverter is running at low speed for a long time.
  • Page 235 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix 5. Photovoltaic Pump Special Function Parameter Table Factory Function Description Name code (setting range) Default Group F0 0: No PG vector control (SVC); Speed Control F0.00 1: PG vector control (FVC);...
  • Page 236 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix Factory Function Description Name code (setting range) Default Wake up delay time 0.0s~6500.0s 300.0s F9.51 0.00Hz~ Awakening frequency (F08.52) Sets the sleep frequency higher than the lower limit of the operating frequency;...
  • Page 237 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix Factory Function Description Name code (setting range) Default 0.00~100.00 (Scale factor 2 of the target Proportional gain frequency) The larger the value, the grea- 70.0 F10.15 ter the effect and the faster the adjustment.
  • Page 238 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix Factory Function Description Name code (setting range) Default MPPT voltage F16.02 The unit is second 10.0s search interval MPPT search Coarse adjustment 5.0V F16.03 voltage step 1 MPPT search F16.04 Fine-tuning 1.0V...
  • Page 239 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix Factory Function Description Name code (setting range) Default The unit is percentage, 0.0~100.0% When the detected water level control analog signal is greater than the water level threshold, and continues this state after the delay time of F16.10, it reports full...
  • Page 240 Peaco Support FC280 Series VFD User Manual Chapter 8 Appendix Factory Function Description Name code (setting range) Default 0~60000s Pump under load Operation time setting. Under the condition of Underload running F16.13 continuous under- load, when the running time time arrives, an under-load warning (E-Pt) will be reported.
  • Page 241 Peaco Support FC280 Series VFD User Manual www.peacosupport.com sales@peacosupport.com Free Shipping Worldwide Reliable Supplier...
  • Page 242 Peaco Support FC280 Series VFD User Manual WARRANTY Œ The company solemnly promises that users will enjoy the following warranty services from the date of purchase of products from our company (hereinafter referred to as the manufacturer).  Since the product was purchased by the user from the manufacturer, enjoy the following three guarantee services: ³...
  • Page 243 Peaco Support FC280 Series VFD User Manual WARRANTY CARD User information User name User address Postal code Contact person Machine type Machine code Agent / Reseller Information Supplier Contact Delivery date CERTIFICATE OF QUALITY QC test: This product has been tested by our company's quality department, and its perf- ormance meets the standards, passes the inspection, and is approved to leave the factory.
  • Page 244 Peaco Support FC280 Series VFD User Manual Feedback Note www.peacosupport.com sales@peacosupport.com Free Shipping Worldwide Reliable Supplier...