Table of Contents 1 Description and Operation ....................... 5 Purpose .......................... 5 Specifications ......................... 6 Standard Delivery ......................7 Arrangement and Operation .................... 7 1.4.1 Outputs ........................7 1.4.2 Polling Loop ......................8 Measuring Instruments, Tools, and Accessories .............. 8 Marking and Sealing ......................
Page 3
The purpose of this User’s Manual is to provide a basic understanding of principles and rules of operation of S2000-SP2 Rev.02 Addressable Two Output Alarm Actuating Unit. Only the personnel who have studied this manual are allowed to operation activities. All activities on mounting, start-up, programming, and testing shall be performed in compliance with the requirements of the regulatory documentation in force at the place of operation.
1 Description and Operation Purpose S2000-SP2 Rev.02 Addressable Two Output Alarm Actuating Unit (hereinafter referred to as SP2.02 or the unit) is intended to: - Control executive appliances (light and sound alarms etc.) and automated fire protection equipment in public address systems and smoke control systems;...
Specifications Table 1.2.1 Parameter Value Power inputs Power input voltage - for executive elements 10.2 through 28.4 V dc - for receive/transmit part via PL, 8 through 12 V Consumed Current - for executive elements 60 mA max(w/o regard to outputs’ current) - for receive/transmit part 1 mA max...
DIN 7982 Flat Head Tapping Screw with Cross Drive 2.2×6.5 2 pcs. MPN Load Connection Module Documentation: S2000-SP2 Rev.02 Addressable Two Output Alarm Actuating Unit Operations Manual 1 pc. Arrangement and Operation 1.4.1 Outputs The unit controls actuating devices by switching voltage from its own contacts U...
1.4.2 Polling Loop The unit receives control commands and sends states of monitored parameters via the digital multiplex addressable polling loop. Current status of communications with the polling loop controller is indicated by the READY indicator as shown in Table 1.4.2. The indicator also indicates conditions of communications with the executive part of the unit.
The unit is composed of a PC board and an enclosure, which is assembled from a plastic base and a cover. The view of the unit along with its overall and mounting dimensions is shown in Figure 2.2.1. READY S2000-SP2 02 Figure 2.2.1. The Unit’s View along with Overall and Mounting Dimensions...
2.2.3 Mounting the Unit Prior to mounting the unit, this one shall be assigned with a unique range of addresses within the polling loop. These addresses shall not coincide with addresses of any devices connected to the same polling loop the unit is connected to. To get more detailed information on changing the unit addresses please see 2.2.5 in this manual.
Page 10
Figure 2.2.4. Drilling Template Mounting on a Wall: - Please ensure that the wall the unit is to be mounted onto is solid, flat, clean, and dry; - Drill three holes in the wall: two upper ones and a lower one; - Insert wall plugs to the holes and screw provided woodscrews into the two upper holes so that distances between a screw head and the wall is about 7 mm;...
2.2.4 Wiring the Unit Figure 2.2.5 shows the general schematic for wiring the unit. Notes: 1. The kinds of actuating devices being connected to the outputs are defined by user and can differ from the ones specified above. 2. Load connection modules (MPN) shall be installed inside the actuating appliances (except for starting circuits of fixed fire extinguishing systems).
I is for the required current of activation, [A]; is for the resistance of the wires between the power supply and the unit, [Ohm]; is for the resistance of the wires between the S2000-SP2 rev.02 and the fixed fire-fighting system, [Ohm];...
Page 13
assigned to two or more devices. To set the unit address, send a relevant command from the network controller specifying an address to be assigned to the first relay. Then within 5 min perform the following combination of presses on the unit tamper switch: three long ones (> 1 sec) and one short press.
Parameter Description Range Default Value The value of relative humidity on Humidity reaching which the output is to be Increased 0…100 % turned on (off) for the control program Threshold 36 (37) Humidity The value of relative humidity at which Decreased the output is turned off (on) for the 0…100 %...
2.2.8 Extreme Situation Actions Warning! If sparks, fire, smoke, or smell of burning is found at the installation site of the product, the product must be de-energized and sent for repair 2.2.9 Troubleshooting Table 2.2.9.1 Fault Possible Cause Solution unit fails control Polling loop failure...
3 Maintenance General The unit is to be maintained under the following schedule: Table 3.1 Task Description Frequency Visual checking Once a year Check for operability Once a year Safety Precautions The unit shall be maintained by personnel qualified for Accident Prevention of Level II or higher. Maintenance Procedures 3.3.1 Visual checking of the unit includes checks for no mechanical damages, fastening reliability, and proper condition of connecting wires and contact joints.
The warranty period is 18 months since putting the product into operation but no more than 24 months from the manufacturer’s date of production. 9 Certification Information S2000-SP2 Rev.02 Addressable Two Output Alarm Actuating Unit meets the requirements of Technical Regulations of Eurasian Economic Union TR EAEU 043/2017 ‘On Requirements for Fire...
Page 18
Technical Regulations of Custom Union ‘Electromagnetic Compatibility of Technical Equipment’ (TR CU 020/2011). It is covered by the conformity declaration ЕАЭС No. RU Д- RU.HP15.B.06633/20. Production of S2000-SP2 rev.02 is awarded with the conformity certificate GOST R ISO 9001. The certificate can be found online at the website http://bolid.ru...