Zentox Photox 500 Operation And Maintenance Manual

Advanced indoor air purification system

Advertisement

Quick Links

Zentox Pure Air
by Photox™
Operations and Maintenance
Manual
for
Model 500
Advanced Indoor Air Purification
System
Please read and follow all instructions prior to operation
of the unit.
1

Advertisement

Table of Contents
loading

Summary of Contents for Zentox Photox 500

  • Page 1 Zentox Pure Air by Photox™ Operations and Maintenance Manual Model 500 Advanced Indoor Air Purification System Please read and follow all instructions prior to operation of the unit.
  • Page 2 This Page Intentionally Blank...
  • Page 3: Table Of Contents

    VII. REPLACEMENT PARTS LIST VIII. WARRANTY SERVICE RECORD Zentox Corporation cannot be held responsible for any accidents or injuries as a result of misuse or abuse of the equipment covered by this manual. Zentox Corporation 600 Elm Ct. Hopewell VA 23860 USA (804) 668-5644 info@zentox.com...
  • Page 4 © Zentox Corporation 2009 The Zentox Pure Air™ purification system is manufactured by Zentox Corporation in Virginia. The Photox™ unit is covered by U.S. Patents No. 5,766,455 and No. 5,834,069; Canadian Patents No. 2253706 and No. 2253707 as well as patents in the...
  • Page 5: Operation Principle

    The CRM’s are pleated to maximize the reactive surface area. The Zentox Pure Air 500 unit is equipped with four (4), 36-watt, Germicidal UV lamps, one directed at each CRM for maximum efficiency. Air is circulated through the unit by means of a variable speed fan that is capable of moving up to 500 scfm.
  • Page 6: Specifications

    four different directions. This design facilitates effective air circulation in the room and accomplishes a complete turnover of the room air every 7 minutes in a 20’ X 20’ X 10’ room. The unit has only one moving part, a fan to draw in the air to be treated, and recirculated in the room.
  • Page 7 C. Place the unit in a dry, out of the way area. Make sure that there is a minimum of six (6) inches of clearance around the unit to allow for a proper airflow. The attached wheels allow for easy maneuverability of the cabinet.
  • Page 8: Scheduled Maintenance

    Advanced Air Purification System. Failure to replace CRM as recommended will reduce the efficiency in the operation of the Zentox Pure Air™ Advanced Air Purification System. The UV lamps have an operating life of 8,500 hours. This equates to approximately one year of operation at twenty-four hours a day.
  • Page 9 Dust will also accumulate on the surface of the lamps, thus decreasing effectiveness. It is suggested that the lamps be checked periodically for particle build-up and cleaned with a soft, dry cloth. When handling a UV lamp, wear clean gloves or wrap a cloth around lamp to avoid oil from hands getting on surface of lamp.
  • Page 10 Unplug before servicing Avant de debrancher le service CAUTION / ATTENTION This Unit contains Ultraviolet Lights. CAUTION / Avoid UV exposure to eyes or skin ATTENTION Eviter l’exposition aux UV pour les yeux ou la peau...
  • Page 11 Figure 1. Screw Removal 2. Open the cabinet by lifting lid and allow it to rest on its hinge in an upright position. (See Figure 2)
  • Page 12 Figure 2. Opening Lid CAUTION: Unit is top heavy when lid is open for service. B. Removing the CRMs 1. After opening the cabinet, remove all 4 CRM’s by sliding modules upward and out of their retaining sleeves. (See Figure 3)
  • Page 13 Figure 3. Removal of CRM’s Install new CRM’s by reversing the process of removal. Use caution when the lid is open to prevent injury from falling lid. The CRMs cannot be cleaned and re-used. The CRMs should be installed so the indicator arrow on the CRM points towards the UV lamps.
  • Page 14 Replace UV lamps and CRM(media) after one year or cumulative use of a maximum of 8,000 hours. C. Removing the UV Lamps 1. Lift the Light Shield out and set it aside (see Fig. 4). Figure 4. Removing the Light Shield 2.
  • Page 15 Figure 5. Disconnecting Lamp from Lamp Support 3. Press the button on the Lamp Base. The UV lamp will spring forward and allow the UV lamp to be lifted out. (see Figure 6).
  • Page 16 PRESS Figure 6. Lamp Removal 4. Repeat steps 2 and 3 for all 4 lamps before installing any new UV Lamps. NOTE UV lamps may be disposed of in a similar manner as fluorescent lamps. Installing new UV Lamps NOTE...
  • Page 17 Be sure to install a genuine Zentox Pure replacement lamp. When handling the new UV lamps, wear clean gloves or wrap a cloth around lamp to avoid oil from hands getting on surface of lamp. If lamp picks fingerprints other...
  • Page 18 Figure 7. Attaching Lamp to Lamp Support 3. Carefully reach down and place the four pins on the end of the lamp into the slots in the lamp socket (see first image Figure 8). 4. While holding the lamp GENTLY slide the lamp backwards until you feel the spring-loaded latch catch.
  • Page 19 6. Return the Light Shield to its proper position as shown (see Figure 9) Figure 9. Proper Light Shield Installation WARNING: Improper installation of light shield can cause exposure to harmful Ultra-violet light. The light shield must be returned to its proper position before operation of the unit.
  • Page 20: Unscheduled Maintenance

    VI. UNSCHEDULED MAINTENANCE Unplug unit from power source before servicing. A. Power Protection: The Zentox Pure Air™ unit has a fuse for electrical protection. If the fuse has blown, check and if necessary correct the condition that caused the fuse to blow. A new fuse can be easily installed in its receptacle located near the power cord at the rear bottom of unit.
  • Page 21: Replacement Parts List

    If the owner is not able to perform UNSCHEDULED MAINTENANCE, please contact Zentox Corporation for Return Authorization shipping information. VII. REPLACEMENT PARTS PART ZENTOX PART NUMBER UV Lamp 40-1101-101 Catalytic Reaction Module, (CRM) 40-4001-101 Service Kit (Includes 4 UV Lamps 40-1201-101 and 4 CRM’s)
  • Page 22: Warranty

    60 months with the purchase of an extended maintenance agreement. B. The Customer agrees that the liability of Zentox for a breach of the Warranty contained herein shall be limited to replacing, repairing, or issuing credit for, at Zentox’s sole discretion, any Equipment which is returned FOB Zentox’s designated facility within the Warranty Period...
  • Page 23 Zentox written instructions, shall be deemed unauthorized unless it is made (i) by Zentox or a duly authorized agent of Zentox or (ii) with the prior written consent of Zentox. D. THIS WARRANTY IS THE SOLE WARRANTY...
  • Page 24: Service Record

    ECONOMIC LOSS, WHETHER BASED CONTRACT, TORT OR ANY OTHER LEGAL THEORY. F. THE REMEDIES PROVIDED HEREIN CUSTOMER’S SOLE AND EXCLUSIVE REMEDIES. Rev. A-1 06.15.07 SERVICE RECORD Date of Start-Up _____________ Service Dates Lamp Date Hour Meter Reading   ___/___/______ __________ ...

Table of Contents