  • Page 2: Table Of Contents

    Fault analysis at device level ETS communication objects General objects Objects for the time control module Objects for energy saving Group objects ECG objects Objects for scene control ETS parameters General Group ECGs DALI channel selection Manual DALI gateway S64 KNX/S128 KNX...
  • Page 3 Testing a scene event 12.5 Testing the whole scene 12.6 Export/import/delete Time control 13.1 Configuration 13.2 Action types 13.3 Disabling/enabling 13.4 Manual override 13.5 Timer 13.6 Export/import Extras 14.1 Menu – edit descriptions DCA OSS Contact Manual DALI gateway S64 KNX/S128 KNX...
  • Page 4: Using The Application Program

    The application description is valid for firmware version 0.2.5 and higher. Product family: Gateways Product type: DALI Manufacturer: Theben AG Name: DALI gateway S64 KNX (1 channel gateway KNX) Order number: 4940301 Number of communication objects: 566 Number of group addresses: 830 Number of associations: 830 Product family: Gateways...
  • Page 5: General Product Information

    For a detailed description of the DALI system, please see the DALI handbook a https://www.digitalilluminationinterface.org  Product overview The DALI gateway is available in 2 product variants: • DALI gateway S64 KNX (1 channel gateway KNX) 4940301 Manual DALI gateway S64 KNX/S128 KNX...
  • Page 6: Product Features

    Flexible DALI commissioning concept in the ETS5 • Coloured light control with the help of device type 8 ECGs (DT-8) • Colour light control depending on ECG sub-type: Colour temperature (DT-8 Sub-Type Tc)  XY colour (DT-8 Sub-Type XY)  Manual DALI gateway S64 KNX/S128 KNX...
  • Page 7: Improvements To The Previous Firmware 0.2

    Firmware 0.3.3 also introduces a new ETS application and a new DCA. This firmware requires the ETS application program and DCA in version "V2" DALI Gateway S64 KNX V2 or DALI Gateway S128 KNX V2 and the associated DCA DALI gateway S KNX V2 Commissioning with the old application and the old DCA is not possible.
  • Page 8 There, the texts can also be easily imported or exported from other file formats. 2.4.6 Manual override in schedules An automatic schedule can be manually overridden for certain requirements. More information can be found in chapter 13.5 Manual Override. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 9: Installation And Commissioning Concept

    All required program data are automatically created when the App is imported. Therefore click on Button „App“ in the footer of ETS5 and then the „plus“ sign in order to add an ETS App to your ETS5 system: Manual DALI gateway S64 KNX/S128 KNX...
  • Page 10: Parameter Configuration

    The "Download" key is available in the DCA tab, see chapter 11 DALI commissioning. In the last step, the parameters and the links to the group addresses should be loaded into the device using normal ETS download. The device is now ready for operation. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 11: Devices For Colour Control (Dt-8)

    By means of the XY coordinates any point in this space is accessible and as a result any colour can be defined. The diagram used in the DALI standard is the colour space chromaticity diagram according to the 1931 CIE standard. (Cambridge University Press) which is shown in the following graphic. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 12: Colour Dislay Via Colour Temperature

    A subset of all possible colours in the colour space are the different white tones. The white tones are found on one line across the whole colour space. Figure 2: White tone on Black-Bodyline (Source: Wikipedia) Manual DALI gateway S64 KNX/S128 KNX...
  • Page 13: Colour Dislay Via 3 Or 4 Colour Channels (Rgbwaf)

    According to DALI standard EN 62386-209, up to six colours (RGBWAF) can theoretically be drawn upon. The DALI gateway KNX, however, only supports a maximum of 4 colours, in line with the ECGs that are currently available on the market. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 14: Manual Mode

    5 Manual Mode 1 channel device The DALI gateway S64 KNX has 9 operating buttons and LEDs on the front side, which offer numerous possibilities for manual control and broadcast and analysis functions. The buttons and LEDs are accessible without having to remove the cover. During KNX bus operation and in the absence of any errors, all 9 LEDs are switched off.
  • Page 15: Channel Device

    During programming (e.g. during installation) all LEDs light up in red and flash slowly. Activate the manual mode with a long keypress on the button in the bottom right-hand corner. The manual mode ends automatically 60 seconds after the last time the button has been activated. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 16 LED on Man. button flashes red/blue Briefly press button 1/9 to trigger a broadcast command. Whether the command that is sent first is an on or off command depends on the status of group 1. Each further keypress toggles Manual DALI gateway S64 KNX/S128 KNX...
  • Page 17 The LED is constantly lit up in red. The faults are as follows: LED Button 2/10  Converter fault LED Button 3/11  ECG fault LED Button 4/12  Lamp fault LED Button 7/15  DALI short-circuit LED Button 8/16  KNX fault Manual DALI gateway S64 KNX/S128 KNX...
  • Page 18: Operating Modes

    If the night object is not set (day), the group behaves as in normal mode. If the object is set (night), the ECG or group either switches off after a programmable time or it changes into permanent mode. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 19: Panic Mode (Exceptional Case)

    Manual operation is activated by default. It can be deactivated rep. disabled by an ETS parameter, see chapter 9.1 General Parameter page: Special functions. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 20: Analysis And Service Functions

    An alarm object is sent when a certain error rate is exceeded. A complex object with a summary of the data further adds to the analysis options. For details of group-specific communication objects, please see the communication objects description below. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 21: Fault Analysis At Device Level

    The alarm threshold for the error rate can be individually set for ECG, light and converter errors. For further details regarding the communication objects, please see chapter 8 ETS communication objects. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 22: Ets Communication Objects

    Object list for 1 channel device: Object list for 2 channel device: For time-controlled sequencing, the current date and time are required. These need to be made available via the bus. Two objects are available for this purpose. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 23 This object is used to invoke or program scenes. Up to 16 scenes are available on the DALI gateway. To program a selected scene, you need to set the top Bit: Start Program Scene 1 Scene 2 …………. Scene 15 Scene 16 Manual DALI gateway S64 KNX/S128 KNX...
  • Page 24 Value 1 Byte 5.001 Alternatively, the failure rate can be reported as a percentage of the total number of ECGs in the DALI segment via this object. Status Switching Lamp Status 4 Byte 27.001 Manual DALI gateway S64 KNX/S128 KNX...
  • Page 25 The gateway responds with the current error status of the queried ECG. Bit 7 6 5 4 3 2 1 0 ECG 5 / ECG error 1 0 0 0 0 1 0 1 Manual DALI gateway S64 KNX/S128 KNX...
  • Page 26: Objects For The Time Control Module

    If the associated groups or ECGs are controlled again with a value > 0%, this object is switched on again before. In this case, a minimum time delay is programmed so that the ECGs are ready for operation again. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 27: Group Objects

    A dim time of 10 s is coded as follows: 10 s = 10x10x100 ms Object 74 is shown for the following parameter: G1  General  Function of the additional object G1, Enable Yes/No 1 Bit 1.003 Manual DALI gateway S64 KNX/S128 KNX...
  • Page 28 | Number of Converters Bit 7 | Bit 6 | Bit 5...0 n.b. | n.b. | Number of ECGs Object 79 is shown for the following parameter: G1  Analysis and maintenance  Additional error objects Manual DALI gateway S64 KNX/S128 KNX...
  • Page 29 Other ECG types will not react to the command. Please remember to only assemble ECGs with the same colour control in a group. Colour temperature Depending on the type of colour control, different objects are shown: Figure 3: Colour temperature (Source: Wikipedia) Manual DALI gateway S64 KNX/S128 KNX...
  • Page 30 Sends the relative colour temperature between 0..100% as status of the group. RGB (DPT 232.600) The RGB colour spectrum is called additive colour spectrum as the colour perception is created by mixining the three basic colours. Figure 4: RGB cube (Source: Wikipedia) Manual DALI gateway S64 KNX/S128 KNX...
  • Page 31 Use this object to send the set colour green as status of the group. G1, Colour (RGB) Blue Status 1 Byte 5.001 Use this object to send the set colour blue as status of the group. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 32 G1, Colour (HSV) Hue Status 1 Byte 5.003 Sends the selected hue as status of the group. G1, Colour (HSV) Saturation Status 1 Byte 5.001 Sends the selected saturation as status of the group. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 33 Bit 0 to 3 deleted is interpreted as a stop telegram. G1, Colour (RGB) Fading Brighter/Cooler 4 Bit Green 3.007 See colour change red. G1, Colour (RGB) Fading Brighter/Cooler 4 Bit Blue 3.007 Manual DALI gateway S64 KNX/S128 KNX...
  • Page 34 The colour is identified through an XY value between 0 and 1. This value range is converted into a range from 0 to 65535 (2 Byte floating point) in the KNX. The value 65535 corresponds to value 1 in the diagram. Figure 7: XY-colour spectrum (Source: Wikipedia) Manual DALI gateway S64 KNX/S128 KNX...
  • Page 35 Sets the Y value in a range from 0 to 65535. G1, Colour X Status 2 Byte 7.001 Sends the set X value as status of the group. G1, Colour Y Status 2 Byte 7.001 Manual DALI gateway S64 KNX/S128 KNX...
  • Page 36: Ecg Objects

    Object = 0  Enable operation Object = 1  Operation disabled ECG1, Status On/Off 1 Bit 1.001 Sends the ECG switch status. Each value >0% is interpreted as ON. ECG 1, Status Value 1 Byte 5.001 Sends the ECG value status. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 37: Objects For Scene Control

    This object is used to invoke or program scenes. Up to 16 scenes are available on the DALI gateway. To program a selected scene, you need to set the top Bit: Start Program Scene 1 Scene 2 …………. Scene 15 Scene 16 Scene1, Dimming Brighter/Darker 4 Bit 3.007 Manual DALI gateway S64 KNX/S128 KNX...
  • Page 38 Bits 1 to 3 refer to the increment size. Bit 0..2 deleted is interpreted as a stop telegram. Attention: The Min- /Max-Setting already defined in the group configuration are taken into account. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 39: Ets Parameters

    Behaviour on KNX Voltage Recovery No Action Switch to Last Value Switch to On-Value Switch to Off-Value Use this parameter to set the behaviour of the connected ECGs/lamps on KNX voltage recovery or bus reset. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 40 If you use ‘Switch to Last Value’, the value prior to the panic mode is saved and the lamp returns to this value afterwards. 9.1.2 Parameter page – analysis and service Manual DALI gateway S64 KNX/S128 KNX...
  • Page 41 100 % Configures a threshold value for the ECG failure alarm object (object 18). The threshold value considers all lamp errors in relation to the total number of connected ECGs in the DALI segment. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 42 If RGB colour is selected: RGB (3 Byte combined Object) Selection of Object Type RGB (separated Object) HSV (separated Object) Determines which type of colour control is to be used. If RGBW colour is selected: Manual DALI gateway S64 KNX/S128 KNX...
  • Page 43 The colour temperature set via this parameter is automatically adjusted for a light value at the upper limit [100%]. For light values between the lower limit [0%] and the upper limit [100%], the automatically set colour temperature is adjusted interpolated. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 44: Group

    Use this parameter to define a group description. To simplify the overview, this description will be displayed for all communication objects. For example: Test group Operation Mode Normal Mode Permanent Mode Normal /Night Mode Staircase Sets the operating mode of the group. If “Permanent“ Mode is selected. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 45 Delayed switch-off in 2 steps: After the set time is set to 50% of the previous value. After a further minute, the switch-off value is set. Delayed dimming: After the set time, the switch-off value is dimmed within one minute. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 46 Determines whether the group is to be enabled for panic mode. The panic mode is controlled via central object No. 7. Value in Panic Mode 50 % 100 % Use this parameter to select the value for this operating mode. 0..100 % [100] Value on DALI Power Fail Manual DALI gateway S64 KNX/S128 KNX...
  • Page 47 95 % 100 % Last Value Use this parameter to set the switch-on value. If you select ‘last value‘, the value is set to the dim value prior to the lamps being switched off. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 48 Dim to Value in 30 Seconds Dim to Value in 1 Minute Dim to Value in 2 Minutes Dim to Value in 5 Minutes Dim to Value in 10 Minutes Sets the switch-off behaviour. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 49 Use this parameter to configure the maximum dim value that can be set through relative dimming. Min. Value for Dimming 0.5 % … …. 50 % Use this parameter to configure the minimum dim value that can be set through relative dimming. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 50 Determines whether to send the total number of errors within the group or the error rate in %. This parameter is only visible if you select “Failure number / rate“ as additional failure object. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 51 Determines whether the last valid colour value or the colour temperature set in the ETS are to be used. Note in case “Keep last object value“: Please remember that the colour set in the ETS will be used if the object value is invalid. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 52 Selects the objects that will be used for the colour control. Colour Value when Switching On Colour selection Use this parameter to define the colour for switching on. An ETS window appears from which the colour can be selected. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 53 5 Manual Mode (RGBW, DPT 251.600). Colour Value when Switching On Colour selection Use this parameter to define the colour for switching on. An ETS window appears from which the colour can be selected. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 54 0…1 [0.33] Use this parameter to define the x-colour for switching on. The value range is between 0 and 1. X= 0.33 and Y=0.33 corresponds to the white point. Figure 8: XY-colour spectrum (Source: Wikipedia) Manual DALI gateway S64 KNX/S128 KNX...
  • Page 55: Ecgs

    The settings for the ECGs are made on two parameter pages, provided that this ECG is defined as an individual ECG and has not been assigned to a group. The parameters of these pages are described below. 9.3.1 ECG 1 (2..64) Manual DALI gateway S64 KNX/S128 KNX...
  • Page 56 Behaviour on Disable No Chance Switch to ON-Value Switch to OFF-Value This parameter is displayed when an additional object is selected. The behaviour during deactivation can be defined here.. Value in Permanent Mode 1..100% [50%] Manual DALI gateway S64 KNX/S128 KNX...
  • Page 57 Determines whether a group should be considered during panic mode. The panic mode is controlled via central object number 9. Value in Panic Mode 1..100% [50] Use this parameter to select the value for this operating mode. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 58 9.1 General. Note: The 1 Byte object is a NON DPT type and will not be implemented in future versions. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 59 Dim to Value in 2 Minutes Dim to Value in 5 Minutes Dim to Value in 10 Minutes Use this parameter to set the switch-on behaviour. Switch-OFF Value … … Use this parameter to set the switch-off value. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 60 Use this parameter to set the dim time for relative dimming in relation to a value range from 0 to 100%. Max. Value for Dimming …. 100% Use this parameter to configure the maximum dimming value that can be set through relative dimming. Min. Value for Dimming 0.5% … …. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 61 Switch ON with Dimming & Value Object Use this parameter to select whether a switched off group should be switched on when receiving a relative 4 Bit dimming object, a value setting object or both. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 62: Dali Channel Selection

    The selection buttons can be used to select between channel 1 and channel 2 (only in case of using a 2-channel device). DALI-Gateway KNX The following description refers to the commissioning of one channel. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 63: Dali Commissioning

    Once an ECG has been assigned to a group via drag and drop, the group number is automatically dis-played in the ‘group number‘ field of the ECG configuration table. If a group assignment has to be solved again, the command is in the context menu of the ECG configuration table. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 64 'Commissioning' page and the "New installation" button. Once the teach-in process is complete, all ECGs that have been found are displayed in the list of non-identified devices on the right-hand side. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 65 ECGs. At the same time the ‘PLAN‘ flag in the configuration table shows that the ECG has been assigned to the planned element. The last column in the table shows the real ECG short address. Please make sure that the short address is between 0 and 63. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 66 ECGs. The actual ETS application with parameter settings and group addresses still has to be downloaded onto the device. This is done, as usual, via the normal down-load process in the ETS. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 67: Ecg Info And Errors

    During the commissioning lamps/ECGs are identified visually (ON, OFF, flashing). It is therefore crucial that all lamps and ECGS operate correctly. If the gateway identifies a lamp or ECG fault during the installation process, the ECG concerned is highlighted in red. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 68: Ecg And Group Detail Info

    Device subtype (important for emergency ECGs DT-1) • SW: switchable emergency lights • NSW: non switchable emergency lights • Error status For DT-8 ECGs with colour temperature control the following are also displayed: • Min. temperature • Max. temperature Manual DALI gateway S64 KNX/S128 KNX...
  • Page 69 11.2.2 ECG info in the ECG table Double-click to open another window with further details. 11.2.3 Group info in the group tree Additional information for the group is displayed via tooltip in the group tree. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 70: Ecg And Group Detail Info

    The DCA offers different options to activate these commands. The gateway must be commissioned and a connection to the gateway must be available for all of the options. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 71 DALI commissioning Group menu in the left-hand side tree: Context menu in the ECG table: ECG menu in the right-hand side tree: The following commands are available: • • • Blink • Initialize ECG Manual DALI gateway S64 KNX/S128 KNX...
  • Page 72: Post Installation

    As the position (short address) of a newly found device is allocated randomly, you need to identify the lights and if required assign them to groups. Afterwards the ECGs can be assigned to a group. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 73: Ecg Easy Replacement

     It is therefore essential to carry out a normal ETS download for the ETS parameters and communication objects.  We recommend you do an ETS back-up after you have completed the configuration. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 74: Scenes

    Select the required scene from the drop down on the left-hand side. A „tick“ means that the scene has already been defined. Use drag and drop to pull the groups that are part of the scene into the scene window in the middle. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 75 To delete an entry, select a group and use drag and drop to move it back to the tree on the right-hand side. Alternatively, use the context menu (right click with the mouse) to delete an entry: Manual DALI gateway S64 KNX/S128 KNX...
  • Page 76: Colour Entries

    Each group can only support one type of colour control. The following window is shown for “colour temperature“. For RGB (RGBW) or HSV the window is as follows: For the XY option, the following window appears: Manual DALI gateway S64 KNX/S128 KNX...
  • Page 77: Programming Scenes

    XML file can be saved separately to be used again in another project or in another template. The com-mands for export or import can be found in the context menu. The template is saved as an XLM file in the desired target directory. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 78: Time Control

    Use the description field to enter a user-friendly name for the template. The name can be up to 20 characters long and is displayed in brackets in the dropdown list for information purposes. You can also define the behaviour of the template: Manual DALI gateway S64 KNX/S128 KNX...
  • Page 79 Creates a new action and adds it to the end of the list. Insert action Creates a new action and inserts it between two existing list entries. Copy and add action Copies a selected action and adds it to the end of the list. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 80: Action Types

    This function sets the colour temperature of DT-8 devices that support the colour temperature setting (TC). On the ECG the colour is also changed if the light is turned off at the time of the action. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 81 The permitted value range for R, G and B is between 0 and 100 %. The final colour is a mixture of the different primary colours according to their percentage. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 82: Disabling/Enabling

    It is even easier to control time-dependencies externally via external objects. If you select this setting for a template, you can control it via the external objects 23ff. The value on receipt of the object determines whether a template is disabled or enabled. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 83: Manual Override

    To reuse a previously created template it is possible to export the template. The resulting xml file can be saved separately so that it can be reused in another project or template. The export and import commands can be found in the context menu. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 84 Time control The template is saved as an xml file in the desired target directory. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 85: Extras

    The description texts of the ECGs, the groups and input devices can be defined separately under this menu item. 14.1 Menu – edit descriptions For each category the description texts can be entered separately. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 86 (txt): When using the txt format, it should be noted that this file is read in line by line. An entry that is not to be changed must therefore be defined as an "empty" line. An entry that is to be deleted is marked with single quotation marks. Manual DALI gateway S64 KNX/S128 KNX...
  • Page 87: Dca Oss

    Lesser General Public License, the modified BSD license and the MIT license. In the event of conflicts between Theben license conditions and the Open Source Software license conditions, the Open Source Software conditions shall prevail with respect to the Open Source Software portions of the software.
  • Page 88: Contact

    Contact 16 Contact Theben AG Hohenbergstr. 32 72401 Haigerloch GERMANY Tel. +49 7474 692-0 Fax +49 7474 692-150 Hotline Tel. +49 7474 692-369 hotline@theben.de www.theben.de Manual DALI gateway S64 KNX/S128 KNX...