VCP 984M Series Manual page 4

Air differential pressure transmitters

Advertisement

Switches and jumper settings
M = Mode
S = SET LED
___________________________________________________________________________________________________________
M = Mode
S = SET LED
Error messages
sensor
defect
measurement
exceeding
___________________________________________________________________________________________________________
M = Mode
___________________________________________________________________________________________________________
*Square root = 984M can be used for volume flow measurement, this product feature is at extra cost and have to be requested when ordering
(SQUARE ROOT FUNCTION NOT AVAILABLE YET).
Ventilation Control Products
Sweden
Air Differential Pressure Transmitters
with 0-10 Vdc or 4-20 mA Output
984M.5x3104, 0-10 Vdc/4-20 mA without LED display
Pressure range
Response
Mode
Output signal
Offset Calibration
This function can be used to correct the zero-point deviation (offset)
of the output signal in depressurised state (example: to 0 V/4mA at zero Pa).
Disconnect the unit from the pressure by opening both hose nozzles or removing the hoses.
Then press the "M" button for 5 s.
Setting of Switching Output
This function is used to set the switching output to "switched through" for a pressure you have defined.
Apply the pressure or pressure differential at which the switching output is to be connected.
Then press the "S" button for 5 s until the LED flashes quickly (= value is saved).
The LED lights up as soon as the defined pressure is reached or exceeded.
984M.5x3114, 0-10 Vdc/4-20 mA with LED display
Pressure range
Response
Mode
Output signal
Offset Calibration
This function can be used to correct the zero-point deviation (offset)
of the output signal in depressurised state (example: to 0 V/4mA at zero Pa).
Disconnect the unit from the pressure by opening both hose nozzles or removing the hoses.
Then follow the programming instructions on the next page.
Setting of Switching Output
This function is used to set the switching output to "switched through" for a pressure you have defined.
The LED lights up as soon as the defined pressure is reached or exceeded.
Peak Value
The shown low/high peak value is the value that was ever set at the sensor.
A resetting of the peak value can take place only at the manufacturer.
984M.5x3204, 4-20 mA
Pressure range
Response
Mode
Offset Calibration
This function can be used to correct the zero-point deviation (offset) of the output signal in
depressurised state (example: to 0 V/4mA at zero Pa).
Disconnect the unit from the pressure by opening both hose nozzles or removing the hoses.
Then press the "M" button for 5 s.
Phone: +46-(0)31-811666
Fax:
+46-(0)31-812766
984M-
series
open
switched
low
high
slow
fast
linear
*square root
0-10 Vdc
4-20 mA
open
switched
low
high
slow
fast
linear
*square root
0-10 Vdc
4-20 mA
open
switched
low
high
slow
fast
linear
*square root
E-mail:
Web:
Mar 11
info@vcp.se
www.vcp.se

Advertisement

loading

This manual is also suitable for:

984m.523104984m.533104984m.543104984m.553104984m.573104984m.593104 ... Show all