StoneLock REM Installation And User Manual

Reader expansion module

Advertisement

Quick Links

StoneLock Reader Expansion Module (REM)
1 Out of the Box
Qty 1
REM-PCB
Qty 1
Cabinet (DSC p/n PC5002C)
Qty 1
Cabinet lock with 2 keys (DSC p/n L-1)
Qty 1
Tamper Switch (GRI p/n TSC-20)
Qty 2
6 Position Terminal Block Plugs
(CUI p/n TBP02P1-381-06BE)
Qty 2
8 Position Terminal Block Plugs
(CUI p/n TBP02P1-381-08BE)
Qty 5
Plastic Standoffs (Keystone Electronics p/n 9067)
Qty 1
Installation and User's Manual
2 Installation
2.1.1 Mounting the Cabinet and the REM
1. Remove the knockout from the front door of the cabinet and mount the lock.
2. Remove any additional knockouts on the box to support cabling for the specific
installation.
3. Install the tamper switch.
4. Insert the 5 plastic standoffs through holes in the back of the cabinet as shown in the
image below.
5. Using the 4 countersunk holes in the back of the cabinet, mount the cabinet to a
secure structure. It is recommended to mount the cabinet using #8 or #10 screws or
equivalent which are a ½" in length minimum, or #8 or #10 or equivalent wall anchors.
6. Mount the REM to the plastic inserts as shown in the image below.
STANDOFF HOLE
COUNTERSUNK HOLE
STANDOFF HOLE
STANDOFF HOLE
COUNTERSUNK HOLE
J1
STANDOFF HOLE
COUNTERSUNK HOLE
STANDOFF HOLE
COUNTERSUNK HOLE
TB1
TB2
TB3
TB4
2.2 Connecting to the REM
On the back side of this sheet, an image shows the terminal block connections on the
REM followed by a table which summarizes the type of cabling/wiring to be used with
the terminal blocks.
____________________________________________________________________________
J1
Lan Port: PoE+ (Power Over Ethernet) RJ45 Connector.
PoE/Network input to the REM.
____________________________________________________________________________
J2
Reader Port PoE (Power Over Ethernet) RJ45 Connector.
PoE/Network output to the GO.
____________________________________________________________________________
TB1
CUI P/N: TBP02P1-381-06BE (Supplied with unit)
PWR+
(12VDC @ 2.14A, or 24VDC @ 1.07A, 25.5W input power + to REM)
PWR-
(12VDC @ 2.14A, or 24VDC @ 1.07A, 25.5W input power – to REM)
LK NO
(Normally Open Contact from the Lock Relay of the Access Control Panel)
COM
(Common Contact from the Lock Relay of the Access Control Panel)
TMPR+
(Cabinet Tamper Switch)
TMPR-
(Cabinet Tamper Switch)
____________________________________________________________________________
TB2 (Access Control Panel Connections)
CUI P/N: TBP02P1-381-08BE (Supplied with unit)
D0/D-
(Wiegand Data 0/OSDP D- Output to the Access Control Panel)
D1/D+
(Wiegand Data 1/OSDP D+ Output to the Access Control Panel)
GND
(Ground for Wiegand communication from the Access Control Panel)
+V
(+V from the Access Control Panel for the Card Reader)
RED
(RED LED signal from the Access Control Panel for the Card Reader)
GRN
(GRN LED signal from the Access Control Panel for the Card Reader)
BUZZ
(Buzzer signal from the Access Control Panel for the Card Reader)
(Card Reader Tamper signal to the Access Control Panel)
TMPR
____________________________________________________________________________
TB3 (For future use)
CUI P/N: TBP02P1-381-06BE (Supplied with unit)
(Auxiliary Output 1)
OUT1
(Common for Auxiliary Outputs 1 and 2)
COM
(Auxiliary Output 2)
OUT2
In1
(Auxiliary Input 1)
COM
(Common for Auxiliary Inputs 1 and 2)
IN2
(Auxiliary Input 2)
____________________________________________________________________________
TB4 (Card Reader Connections)
CUI P/N: TBP02P1-381-08BE (Supplied with unit)
D0/D-
(Wiegand Data 0/OSDP D- Input from the Card Reader)
D1/D+
(Wiegand Data 1/OSDP D+ Input from the Card Reader)
GND
(Ground for Wiegand communication to the Card Reader)
+V
(+V from the Access Control Panel to the Card Reader)
RED
(RED LED signal from the Access Control Panel to the Card Reader)
GRN
(GRN LED signal from the Access Control Panel to the Card Reader)
BUZZ
(Buzzer signal from the Access Control Panel to the Card Reader)
TMPR
(Tamper signal from the Card Reader to the Access Control Panel)
J2
When connecting SWH-4100 or similar card readers that do not include internal pull-up
resistors, two external pull-up resistors are required. A pull-up resistor between D0/D-
and +V as well as a pull-up resistor between D1/D+ and +V. Pull-up resistor values of
5.1k-ohm to 7.5k-ohm are acceptable; 6.2k-ohm recommended.
____________________________________________________________________________
2.2.1 Power and Ethernet Connections
The REM should be powered by a Power Limited/Class 2, PoE+ (Power over Ethernet)
IEEE802.3at compatible network switch over a Cat 5 or better network cable terminated
by an RJ45 plug connected to the LAN port. A Cat 5 or better network cable should be
connected between the REM Reader Port and the PoE RJ45 port on the StoneLock GO.
Installation and User Manual

Advertisement

loading
Need help?

Need help?

Do you have a question about the REM and is the answer not in the manual?

Questions and answers

Summary of Contents for StoneLock REM

  • Page 1 On the back side of this sheet, an image shows the terminal block connections on the Qty 1 REM-PCB REM followed by a table which summarizes the type of cabling/wiring to be used with Qty 1 Cabinet (DSC p/n PC5002C) the terminal blocks.
  • Page 2 • The RED terminal is the RED LED signal from the Access Control Panel to the Card Reader. • The PWR+ and PWR- terminals can be used to power the REM when PoE+ (Power • The GRN terminal is the GREEN LED signal from the Access Control Panel to the Card over Ethernet) is not available.