Installation - Watts LFM110-AS Installation Operation & Maintenance

Modulating float control valve with solenoid (on-off) feature

Advertisement

LFM110-AS (Globe) Modulating Float Control Valve with Solenoid
(On-Off) Feature
Standard Components
1 – Main Valve (M100 – Single Chamber)
2 – Modulating Float Control
3 – Adjustable Closing Speed
4 – 2-Way Solenoid
X – Isolation Cocks
Operation
The Modulating Float Control Valve with Solenoid (On-Off) Feature
is designed to automatically maintain a constant liquid level in a
tank or reservoir, and open, allowing level control action, or close
drip-tight as commanded by the Solenoid Pilot. It is controlled by
a remote mounted Modulating Float Pilot designed to: 1) Modulate
Open (allowing fluid out of the main valve cover chamber) when
reservoir level decreases, and, 2) Modulate Closed (allowing fluid
to fill the main valve cover chamber) when reservoir level increases.
A decrease in reservoir level causes the valve to modulate towards
an open position, allowing reservoir level to increase. An increase
in reservoir level causes the valve to modulate towards a closed
position, allowing reservoir level to decrease.
The Solenoid Pilot will either open to allow regulating action, or
close the valve drip-tight when energized. Specify energize to
open or close the Main Valve and voltage PRIOR to ordering.
If desired, the float modulating action of the valve can be "re-
versed" by inverting or "reversing" the action of the Modulating
Float Pilot. The Modulating Float Control is remotely mounted from
the valve, and field connected with 3/8" minimum copper tubing in
accordance with factory piping schematic.

Installation

Start-up of an automatic control valve requires that proper procedures be followed. Time must be allowed for the valve to react to
adjustments and the system to stabilize. The objective is to bring the valve into service in a controlled manner to protect the system
from damaging over-pressure.
1.
Prior to installation, flush line to remove debris.
2.
Install valve so the flow arrow matches flow through the line, and gauges to monitor valve inlet and outlet pressures. A Position
Indicator can be installed to provide visual indication of valve position and operation without disassembly.
3.
Install isolation valves upstream and downstream of the main valve.
4.
Provide adequate clearance for valve servicing and maintenance. Refer to valve servicing dimensions on next page. Avoid installing
valves 6" and larger in the vertical position (main valve stem horizontal). Automatic Control Valves (ACVs) are designed for horizon-
tal in-line installation, with the cover facing up (main valve stem vertical). Slow operation or premature stem and guide wear may
occur if valve is not installed according to factory recommendations. Consult factory for detailed engineering review prior to order-
ing if valve is to be installed other than horizontally in-line.
5.
If valve is equipped with a pilot control system, extra precautions should be made during installation to protect the piping circuit
from damage. Only remove the pilot control system from the valve if necessary. Tubing and fittings should be kept clean and
replaced exactly as removed. Consult appropriate hydraulic schematic to ensure proper re-assembly.
6.
Install float control onto tank and connect lines to valve per schematic.
7.
Adjust float arm to the high-level setting – the float pilot should be closed.
8.
Connect solenoid wiring leads to desired switching device, using safe, standard electrical practices.
2
IOM-ACV-110-AS_6110-AS 2115
(AOS)
3
EDP#1917117
4
P/L
X
X
Y/FC
1
FLOW
CLOSES VALVE
OPENS VALVE
2