3.7 Other setting

Temperature setting

Press
or
to set temperature. Set point temperature is shown on temperature display area.
Press
to confirm settings and exit. If no operation within 6 seconds, it will automatically exit and the setting will not be saved.
When DIP SW1=ON, set point temperature is fixed. In cooling mode, set point temperature is 24℃. In heating mode, set point
temperature is 21℃.
When DIP SW1=OFF, temperature can be set from 16℃ to 30℃.
When DIP SW2=ON, set point temperature is shown on temperature display area.
When DIP SW2=OFF, room temperature is shown on temperature display area.

Mode setting

Press
to set COOL, HEAT, FAN, DRY or AUTO (Display both COOL and HEAT icons) mode alternatively.

Key Lock

Press
and
to set key lock function. Key lock icon is on or off when key lock function is set to on or off.

Fan speed setting

Press
to set LOW, MEDIUM, HIGH or AUTO speed.

ON/OFF setting

Press
to turn on or off the unit.

Temperature unit setting

Press
and
at the same time to change temperature unit between Celsius and Fahrenheit.

4. ERROR CODES

When unit error is detected, unit number blinks on real time hour area and Error code blinks on real time minute area. The Error
codes display alternately if more than one error is detected.
If there is no slave unit online, only error code is shown in real time minute area.
Error code table:
Error reason
Indoor coil sensor 2 faulty
Return air sensor faulty
Indoor coil sensor 1 faulty
Indoor coil low temperature Protection
Indoor coil over heat protection
Water pump faulty
Local communication error

5. EC MOTOR RPM SETTING (NOT AVAILABLE IN AC MOTOR UNIT)

DIP SW3 is used to set EC motor RPM.
When DIP SW3=ON, wired wall pad enters setting interface. D1/D2/D3 is shown in temperature display area and EC motor RPM
is shown in real time display area.
Press
and
to select motor speed (D1, D2 or D3). Press
valid.
When DIP SW3=OFF, wired wall pad resumes normal display.
Error code
E2
E3
E4
E5
E6
E7
EC0
or
Cod. 3QE46840 - Rev. 00 - 12/2020
to set EC motor RPM. After 3 seconds, the setting is
11