Explosion-proof led-emergency light fitting with built-in battery
Table of Contents

Advertisement

6.4 How to replace the emergency battery
 Follow the instructions of section 6.1!
!
 Only original batteries as per the type plate on the battery must be used for replacing
the battery (see Chapter 3, Technical Data)!
Version without battery box:
open the light fitting as described in section 4.1.
turn the wing nuts of the reflector by 90° so that the reflector can be removed from the housing.
push the detent at the connection assembly and unplug the battery conductor plug from the battery
socket.
put the protective cap back onto the battery conductor plug.
loosen the screws of the battery fixing bracket, but do not remove them completely.
push the battery fixing bracket to release the battery.
remove
battery.
put new battery back into the fitting.
secure battery with battery fixing bracket and fasten screws. Make sure that the battery is securely
fixed.
remove protective cap from battery conductor plug.
insert battery conductor plug into the socket in the light fitting housing. Make sure that the plug is
locked in place to avoid an accidental separation of the plug connection.
Put the reflector into the housing and lock it into position by use of the wing nuts.
close the light fitting as described in section 4.4.
Alert the emergency light unit to the presence of a new battery:
Open and close the light fitting twice within a 60-second period. Opening and closing must occur
within 10 seconds of each other. During this time the emergency light unit must be supplied by the
mains supply.
If this procedure is done correctly, immediately after the light fitting is closed for the second time,
the signal LED will display an acknowledgement light. The five-second long red-green
acknowledgement light confirms that a operational life test will be conducted 12 hours later.
Version with battery box:
Loosen the locking screws of the battery box.
The emergency battery is located in the lid of the battery box. Take care when opening it.
Press down the catch on the plug connection and pull the connector of the battery cable out of the
socket.
Insert the protective cap hanging on the connector of the battery cable into the battery connector.
Loosen but do not fully unscrew the locking screws of the battery fixing bracket.
Slide the fixing bracket in the keyhole towards the hinge until the battery is released.
Remove the emergency battery from the lid.
Insert a new emergency battery into the lid.
Return the battery fixing bracket to the original position and screw down. Check that the battery is
positioned securely.
Remove the protective cap of the battery connector.
Attach the battery connector to the socket in the battery box. Check the catch mechanism of the
plug connection.