USER MANUAL
HIGH FREQUENCY ONLINE UPS
1KVA/2KVA/3KVA/6KVA/10KVA
PF 1.0

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 1K and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for ProStar 1K

  • Page 1 USER MANUAL HIGH FREQUENCY ONLINE UPS 1KVA/2KVA/3KVA/6KVA/10KVA PF 1.0...
  • Page 3: Table Of Contents

    Table of Contents CHAPTER 1 SAFETY INSTRUCTIONS ..........................1 1.1 About This Manual ............................1 1.2 Transportation ..............................1 1.3 Preparation ............................... 1 1.4 Installation ................................1 1.5 Operation ................................2 1.6 Maintenance ..............................2 1.7 Deenergizing Safety ............................3 1.8 Standards ................................3 CHAPTER 2 SYMBOLS DESCRIPTION ......................... 4 2.1 General Introduction ............................
  • Page 4: Chapter 1 Safety Instructions

    CHAPTER 1 SAFETY INSTRUCTIONS 1.1 About This Manual Purpose Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully the following instructions before installing the unit. Scope This manual provides safety and installation guidelines as well as information on wiring. 1.2 Transportation Transport the unit only in suitable packaging to protect it from jolts and shocks.
  • Page 5: Operation

    1.5 Operation Do not disconnect the mains cable on the UPS system or the building wiring outlet (shockproof  socket outlet) during operations since this would cancel the protective earthing of the UPS system and of all connected loads. The UPS system features its own, internal current source (batteries). The UPS output sockets or ...
  • Page 6: Deenergizing Safety

    Batteries may cause electric shock and have a high short-circuit current. Please take the precautionary measures specified below and any other measures necessary when working with batteries: remove wristwatches, rings and other metal objects.  use only tools with insulated grips and handles. ...
  • Page 7: Chapter 2 Symbols Description

    CHAPTER 2 SYMBOLS DESCRIPTION 2.1 General Introduction This series UPS, available in 1kVA, 2 kVA, 3 kVA, 6 kVA and 10 kVA, is an advanced online and double-conversion UPS providing reliable and consistent pure sine-wave quality power to your equipment. It supports personal computers, networks, servers, telecommunication equipment and a variety of other facilities.
  • Page 8: Chapter 3 Installation And Setup

    CHAPTER 3 INSTALLATION AND SETUP There are two different types of online UPS: short-backup and long-run models. Please refer to the following model table. Model Type Model Type Long-run Online UPS Short-backup Online UPS 10KB 3.1 Unpacking and Inspection Unpack the package and check the package contents. The shipping package contains: ●One UPS ●One user manual ●One battery cable (only for long-run models)
  • Page 9 Universal Type Schuko Type IEC Type Universal Type Schuko Type IEC Type Universal Type Schuko Type IEC Type...
  • Page 10 6K-10K Universal Type Schuko Type IEC Type Universal Type Schuko Type IEC Type...
  • Page 11 Universal Type Schuko Type IEC Type 6KB-10KB 3.2.2 Rear for Rack Mount...
  • Page 12 Universal Type Schuko Type IEC Type Universal Type Schuko Type IEC Type Universal Type Schuko Type IEC Type...
  • Page 13 6K-10K Universal Type Schuko Type IEC Type Universal Type Schuko Type IEC Type...
  • Page 14 Universal Type Schuko Type IEC Type 3.2.3 Rack Mount Battery Pack 2U Battery Pack 3U Battery Pack 1. Smart slot 10. Maintenance bypass switch (option) 2. RS-232 port 11. Cooling fan 3. Output receptacles 12. AC Input terminal 4. Ground terminal 13.
  • Page 15: Rack Mount Ups Installation

    3.3 Rack Mount UPS Installation This UPS can be mounted in the 19”rack chassis. Please follow below steps to position this UPS. 3.4 Setup the UPS Before installing the UPS, please read below to select proper location to install UPS. ...
  • Page 16 Prepare wires based on the following table: Model Wiring spec (AWG) Input Output Battery Ground 10KB * NOTE 1: It is recommended to use suitable wire in above table or thicker for safety and efficiency. * NOTE 2: The selections for color of wires should be followed by the local electrical laws and regulations.
  • Page 17 (3) Connect the battery cable attached to the external battery pack (optional) to the UPS’s battery pack connector. (4) Set the battery pack’s circuit breaker to the ON position. STEP 2: UPS INPUT CONNECTION  For Socket - Plug the UPS into a two-pole, three-wire and grounded receptacle only. Avoid using extension cords.
  • Page 18 STEP 3: UPS OUTPUT CONNECTION For socket-type outputs, simply connect devices to the outlets. For terminal-type input or outputs, connection as below: Output Neutral Output Line Ground STEP 4: COMMUNICATION CONNECTION Communication port: USB port RS-232 port Intelligent slot USB Port After connect UPS and computer by USB cable,you can use computer monitor UPS status by remote control.
  • Page 19 Pin 1 and pin 2 are always connected. Pin 1 closed to pin 2, UPS shutdown When pin 3 and pin 4 disconnected, UPS immediately. Pin 3 and pin 4 float. shutdown immediately. STEP 5: TURN ON UPS Press button on the front panel for two seconds to power on the UPS. Note: The battery charges fully during the first five hours of normal operation.
  • Page 20: Chapter 4 Operation

    CHAPTER 4 OPERATION 4.1 Button Operation Button Function Turn on the UPS: Press this combined button for at least 2 seconds to turn on the UPS. Turn off the UPS: Press this combined button at least 2 seconds to turn off the UPS. This combined button has two functions.
  • Page 21: Lcd Display Icons

    4.2 LCD Display Icons ICON Function When UPS in overload, the icon will be flashing. Indicates the load level by 0-25%, 26-50%, 51-75%, and 76-100%. Indicates battery capacity by 0-25%, 26-50%, 51-75%, and 76-100%. Indicates the UPS connects to the mains. It will flash when battery capacity low or disconnect battery.
  • Page 22: Led Indicators

    Indicates the input voltage, frequency, battery voltage, current or temperature. I/P: input, VAC: input voltage, Hz: frequency, VDC: battery voltage, %A: input current, ℃: temperature Indicates the output voltage, frequency, capacity or current. O/P: output, VAC: output voltage, Hz:frequency, KVA: output capacity in KVA, KW: output capacity in KW, %A: output current Indicates the ECO mode is enabled.
  • Page 23: Audio Alarm

    4.3 Audio Alarm Sounding every second Battery Mode Sounding every second Low Battery Sounding every second Overload Continuously sounding Fault Sounding every 2 minutes Inverter is not turned on Sounding every 4 seconds Other alarms 4.4 UPS Working Status Working status LED indicator BATTERY BYPASS...
  • Page 24 ITEM LCD display UPS input/output voltage UPS input/output frequency Battery voltage and capacity(%) UPS output voltage and power (W) UPS output voltage and capacity (VA) UPS output voltage and load (%)
  • Page 25: Ups Operation

    ITEM LCD display UPS software version Battery number Alarm information 4.6 UPS Operation 4.6.1 Turn on the UPS with utility power supply 4.6.1.1 After power supply is connected correctly, connect the breaker of the battery bank. Then, set the input breaker at “ON” position. At this time, the UPS supplies power to the loads via the bypass. The UPS is operating in Bypass mode.
  • Page 26 NOTE: When the UPS is running out battery, it will shut down automatically at Battery mode. When the utility power is restored, the UPS will auto restart in AC mode. 4.6.2 Turn on the UPS without utility power supply 4.6.2.1 Make sure that the breaker of the battery bank is at “ON” position. 4.6.2.2 Press and hold the button for 2s to turn on the UPS, and the buzzer will beep once.
  • Page 27 automatically except in Battery mode or during battery self-test. 4.6.4.2 It’s suggested to charge batteries at least 10 hours before use. Otherwise, the backup time may be shorter than expected time. 4.6.4.3 The charging current can be changed from 1A to 12A for long run model via LCD or software. Please make sure that the charging current is suitable to battery specification.
  • Page 28: Ups Setting

    4.6.7.2 Then UPS will cut off power to output and there is no display shown on the display panel. 4.6.8 Mute the buzzer 4.6.8.1 To mute the buzzer, please press the button for at least 2s. If you press it again after the buzzer is muted, the buzzer will beep again.
  • Page 29 Interface Setting Enter the function setting page, turn to output voltage setting page[OPU], you may choose the following output voltage: 208: presents output voltage is 208Vac 220: presents output voltage is 220Vac (Default) 230: presents output voltage is 230Vac 240: presents output voltage is 240Vac Set output voltage to 230VAC 4.7.2 Expert mode settings (EP) Interface...
  • Page 30 4.7.3 Battery number setting (PCS) Interface Setting When EP is ON, turn to battery number setting page[PCS], it’s required password to enter page(default password: 135). 1KVA/1KW 3PCS(default) >> 1KVA/1KW 2PCS 2KVA/2KW 6PCS(default) >> 2KVA/2KW 4PCS 3KVA/3KW 8PCS(default) >> 3KVA/3KW 6PCS 6KVA/6KW 16PCS(default) >>...
  • Page 31 4.7.5 Battery end of discharge voltage setting (EOd) Interface Setting When EP is ON, turn to battery end of discharge voltage setting page[EOd]. You can set EOd as below value: dEF(default), 9.8V, 9.9V,10V,10.2V,10.5V. Battery end of discharge voltage varies with load: 10.5V: @load<25%, 10.2V: 25%<@load<50%, 10V: @load >...
  • Page 32: Operation Mode Description

    4.7.7 Battery charging current setting (CHG) Interface Setting When EP is ON, turn to battery charging current setting page[CHG]. You can set battery charging current as below value: Long-run: 1A - 12A, 5A default. 2KVA/3KVA short backup: 1A - 4A, 1A default. 1KVA short backup: only for 1A.
  • Page 33: Fault And Alarm Information

    frequency are within the range of rating voltage +/-10% and rating frequency +/-5Hz, the connected loads are supplied by the utility power; if out of the range, the connected loads are supplied by the inverter. 4.9 Fault and Alarm Information Fault code or Alarm code Fault icon Alarm icon...
  • Page 34: Ups Parallel

    4.9.2 Alarm Code Alarm code Alarm information Alarm code Alarm information Battery disconnection Fans lock Battery low voltage EEPROM fail Battery charger short circuit Overload warning Input L/N wiring reversed or PE Overload lock in bypass disconnect Battery high voltage EPO active Battery charger fail MBS active...
  • Page 35 4.10.2.2 Connect the output wire of the parallel UPS to an output terminal block, load connect to the output terminal block via load wire. 4.10.2.3 The parallel UPS input terminal panel and output terminal panel see below, the wires of each parallel UPS must follow the wire requirement for single UPS.
  • Page 36: Chapter 5 Troubleshooting

    CHAPTER 5 TROUBLESHOOTING If the UPS system does not operate correctly, please solve the problem by using the table below. Fault Possible Causes Solutions Press the button on Power on switch not pressed. the front panel. Check that the power cable is Main connection cable missing.
  • Page 37 Fault Possible Causes Solutions The display shows code: 2, icon flashing, and Battery voltage is too low. Contact your dealer. alarm is continuously sounding. The display shows code: Fans is locked or not working. Check the fans back of the UPS. 12, icon is flashing.
  • Page 38: Chapter 6 Storage And Maintenance

    CHAPTER 6 STORAGE AND MAINTENANCE 6.1 Prior to Installation If the UPS needs to be stored prior to installation, it should be placed in a dry area. The allowable storage temperature and relative humidity (non-condensing) are -15°C ~+60°C and 5~95% respectively.
  • Page 39: Chapter 7 Specifications

    CHAPTER 7 SPECIFICATIONS 7.1 Specification of Tower Type UPS 1KVA - 3KVA MODEL CAPACITY 1KVA/1KW 2KVA/2KW 3KVA/3KW 24V / 36V 48V/72V 72V/96V Battery Voltage (default) (default) (default) Size, DxWxH (mm) 290x143x222 395x143x222 395x143x222 390x190x330 Net Weight (kgs) INPUT Nominal Voltage 208/220/230/240VAC Input Voltage Range 110-300VAC...
  • Page 40: Specification Of Tower Type Ups 6Kva - 10Kva

    MODEL Charging Voltage 41VDC 27VDC 81VDC 54VDC 108VDC 81VDC Charging Mode 2-stage or 3-stage (settable) INDICATORS Load level, Battery level, AC mode, Battery mode, Bypass mode,and Fault conditions ENVIRONMENT Ambient temperature 0- 40°C Operation Humidity 5%-95% (non-condensing) Storage temperature -15~60℃ (no battery inside) Altitude <1000m ( the height above 1000m should be reduced to a maximum of 4000m.) Noise Level...
  • Page 41 MODEL 10KB Waveform (Batt. Mode) Pure Sine Wave EFFICIENCY AC Mode 95.5% Battery Mode 95.3% BATTERY Battery Type Sealed Maintenance-free Battery Numbers 16x12V7AH 16x12V7AH (default) (default) 5A (Default) 1A (Default) 5A (Default) 1A (Default) Charging Current 1A-4A adjustable 1A-12A adjustable 1A-12A adjustable 1A-4A adjustable Charging Voltage...
  • Page 42: Specification Of Rack Mount Ups 1Kva - 3Kva

    7.3 Specification of Rack Mount UPS 1KVA - 3KVA MODEL CAPACITY 1KVA/1KW 2KVA/2KW 3KVA/3KW 24V/36V 48V/72V 72V/96V Battery Voltage (default) (default) (default) Size, DxWxH (mm) 440x420x88 440x420x88 440x600x88 Net Weight (kgs) 21.5 INPUT Nominal Voltage 208/220/230/240VAC Input Voltage Range 110-300VAC Frequency Range 50Hz:44Hz~56Hz or 60Hz:54Hz~66Hz Phase...
  • Page 43: Specification Of Rack Mount Ups 6Kva - 10Kva

    MODEL Storage temperature -15~60℃ (no battery inside) Altitude <1000m ( the height above 1000m should be reduced to a maximum of 4000m.) Noise Level Less than 50dBA @ 1 Meter COMMUNICATION Communication Interface Standard: RS232, USB; Option: Dry contact, EPO Smart Slot Optional SNMP Card 7.4 Specification of Rack Mount UPS 6KVA - 10KVA...
  • Page 44: Specification Of Rack Mount Battery Pack

    MODEL 10KB Battery Type Sealed Maintenance-free Battery Numbers 16x12V7AH 16x12V7AH (default) (default) 5A (Default) 1A (Default) 5A (Default) 1A (Default) Charging Current 1A-12A adjustable 1A-12A adjustable 1A-12A adjustable 1A-12A adjustable Charging Voltage 216VDC Charging Mode 2-stage or 3-stage (settable) INDICATORS UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions ENVIRONMENT...
  • Page 45 Version: 220625...