ITT GT 8 Series Instruction And Maintenance Manual

Milliamp i/p transducer

Advertisement

Quick Links

CAUTION: These instructions should be read and
understood prior to installation, use or maintenance.
GENERAL PRODUCT OVERVIEW
This I/P transducer is a force-balanced unit which uses a fixed
filtered air inlet pressure, accepts a DC milliamp input signal
and converts it to a proportional air output pressure.
Models are available with an integral relay booster (GT28,
GT48, and GT68) or without the booster (GT18, GT38, and
GT58). All models are available in FM approvals
explosionproof (XP) housings.
SPECIFICATIONS
Input Range:
4-20 or 10-50 mA DC
Nominal Impedance: 4-20 mA model: 145 ohms
10-50 mA model: 60 ohms
Output Signal:
3-15, 3-27 or 6-30 PSIG
(21-103, 21-186 or 41-207 kPa)
Required Air Supply: GT18, GT28: 25 PSIG (172 kPa)
GT38, GT48, GT58 or GT68:
35 PSIG (241 kPa)
Air Consumption:
GT18, GT28: 0.20 scfm (6 slpm) max
GT38, GT48, GT58 and GT68:
0.30 scfm (8.5 slpm) max
Air Delivery Rate:
GT18: 0.15 scfm (4.3 slpm) max
GT28: 5 scfm (142 slpm) max
GT38: 0.15 scfm (4.3 slpm) max
GT48: 5 scfm (142 slpm) max
GT58: 0.15 scfm (4.3 slpm) max
GT68: 5 scfm (142 slpm) max
Exhaust Rate:
GT18: 0.17 scfm (5 slpm) max
GT28: 1.7 scfm (50 slpm) max
GT38: 0.2 scfm (6 slpm) max
GT48: 2.3 scfm (65 slpm) max
GT58: 0.2 scfm (6 slpm) max
GT68: 2.3 scfm (65 slpm) max
THIS INFORMATION IS SUBJECT TO THE CONTROLS OF THE EXPORT ADMINISTRATION REGULATIONS (EAR). THIS INFORMATION SHALL NOT BE PROVIDED TO
NON-US PERSONS OR TRANSFERRED BY ANY MEANS TO ANY LOCATION OUTSIDE THE UNITED STATES CONTRARY TO THE REQUIREMENTS OF THE EAR.
Conoflow
ITT
105 Commerce Way
Westminster, SC 29693
Tel: (864) 647-9521
Fax: (864) 647-9568
INSTRUCTION AND MAINTENANCE MANUAL
GT_8 Series Milliamp I/P Transducer
3
3
3
3
3
3
GT_8-IOM Rev. 0
7/19
Conoflow's products are designed and
manufactured using materials and workmanship
required to meet all applicable standards. The use
of these products should be confined to services
specified and/or recommended in the Conoflow
catalogs, instructions, or by Conoflow application
engineers.
To avoid personal injury or equipment damage
resulting from misuse or misapplication of a
product, it is necessary to select the proper
materials of construction and pressure-
temperature ratings which are consistent with
performance requirements.
Linearity:
+/- 1.5% of output span
Temperature Effect:
0.2% of output span / 10 °F change
For a 2 °F / minute rate of change
Temperature Range:
0 °F to 150 °F (-18 °C to 66 °C)
Approximate Weight:
Approx. 7 lb (3.2 kg) – Std. Units
Approx. 13 lb (5.9 kg) – XP Units
Piping Requirements:
3/8" Tubing or 1/4" Pipe (minimum)
NOTES:
1.
A Conoflow FR95 Airpak filter regulator or equivalent
is recommended for the filtered air supply.
2.
Models without a booster relay have a temperature
effect rating of approximately 0.1% of output span / 10
°F for a 2 °F / minute rate of change.
3.
Low volume models (GT18, GT38, GT58) do not have
a booster relay and should only be used in low
volume flowrate applications.
Prior to installation, inspect the package and
product for damage. Do not use if damaged. Verify
operation, and calibrate the transducer using the
procedure on page 4.
INSTALLATION
See figure 1 (page 2) for location of connection interfaces
ELECTRICAL CONNECTION: The electrical connection for
the input signal is made through a ½" NPSM or ½" NPT
conduit connection on the side of the transducer housing body.
Unscrew the cover and connect the positive lead to terminal 2
and negative to terminal 1.
For reverse acting models, connect the positive lead to
terminal 1 and the negative lead to terminal 2.
Printed in USA
WARNING
2

Advertisement

loading
Need help?

Need help?

Do you have a question about the GT 8 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for ITT GT 8 Series

  • Page 1 WARNING Conoflow’s products are designed and Conoflow manufactured using materials and workmanship required to meet all applicable standards. The use 105 Commerce Way of these products should be confined to services Westminster, SC 29693 specified and/or recommended in the Conoflow catalogs, instructions, or by Conoflow application Tel: (864) 647-9521 engineers.
  • Page 2 PNEUMATIC CONNECTION: Connect the supply pressure CAUTION: Teflon tape is the preferred thread sealant line to the ¼” NPT inlet port (stamped “IN”). A clean, filtered for the 1/4” NPT connections. Liquid thread sealant can air supply (25 psi for the GT18 or GT28; 35 psi for the GT38, migrate to the fixed orifice of the transducer and create GT48, GT58 or GT68 model) is required.
  • Page 3 PRINCIPLE OF OPERATION A decrease in the input signal allows the coil to move into the An increase in coil signal current drives the coil downward, out magnet assembly, which moves the beam away from the pilot of the magnet assembly, pushing the balance beam toward the nozzle.
  • Page 4 TROUBLESHOOTING section of this document. It is important current to this transducer. Verify the input DC mA signal that clean, dry air be supplied to the unit at all times. An ITT using a digital ammeter. Conoflow FR95 series Airpak (filter regulator) or equivalent...