- Manual - MGRS12S4P176-300, MGRS14S3P132-300, MGRS16S3P132-300, MGRS24S2P088-300, MGRS12S4P176-500, MGRS14S3P132-500, MGRS16S3P132-500, MGRS24S2P088-500, MG Energy Systems B.V. Revision: Date: 10-06-2020 MG Energy Systems B.V. | Foeke Sjoerdswei 3 | 8914 BH Leeuwarden | The Netherlands +31 (0)58 750 89 47 | info@mgenergysystems.eu | www.mgenergysystems.eu...
Page 2
PRICE OF THE MG ENERGY SYSTEMS B.V. PRODUCTS DESCRIBED HERE IN. MG Energy Systems B.V.. reserves the right to revise and improve its products as it sees fit. This publication describes the state of this product at the time of its publication and may not reflect the product at all times in the future.
Controller Area Network bus; CAN-bus is a standard serial databus that provides data communication between two or more devices. MG Energy Systems B.V. | Foeke Sjoerdswei 3 | 8914 BH Leeuwarden | The Netherlands +31 (0)58 750 89 47 | info@mgenergysystems.eu | www.mgenergysystems.eu...
Page 7
State-of-Health; is a figure of merit of the condition of a battery (or a cell, or a battery pack), compared to its ideal conditions. MG Energy Systems B.V. | Foeke Sjoerdswei 3 | 8914 BH Leeuwarden | The Netherlands +31 (0)58 750 89 47 | info@mgenergysystems.eu | www.mgenergysystems.eu...
Make sure the locale health and safety regulations for working on battery systems are followed. MG Energy Systems B.V. | Foeke Sjoerdswei 3 | 8914 BH Leeuwarden | The Netherlands +31 (0)58 750 89 47 | info@mgenergysystems.eu | www.mgenergysystems.eu...
Check the local safety rules and guidelines they have higher preference over the manufacturers specification in case of regulatory conflicts. Instruction and training can be carried out by MG Energy Systems B.V. by order of the user company. Non-compliance risks Failure to comply with all safety precautions can result in the following conditions: ...
Applying the above notes on storage of the battery module will cause every six months a decrease in SoC of 5%. MG Energy Systems B.V. | Foeke Sjoerdswei 3 | 8914 BH Leeuwarden | The Netherlands +31 (0)58 750 89 47 | info@mgenergysystems.eu | www.mgenergysystems.eu...
Power cables and connectors (details can be found in chapter 6.3.2). Communication cables and connectors (details can be found in chapter 6.3.1). Exhaust parts. MG Energy Systems B.V. | Foeke Sjoerdswei 3 | 8914 BH Leeuwarden | The Netherlands +31 (0)58 750 89 47 | info@mgenergysystems.eu | www.mgenergysystems.eu...
MG Master HV. 4.2 Functional description MG Energy Systems battery system philosophy is to have one master BMS, e.g. a MG Master HV, per string of battery modules which communicates with one or more slave BMSs integrated in the Lithium-Ion battery module(s).
MG Master HV, please refer to the data sheet and manual. Figure 3 - 350 VDC system with 4x MGRS24S2P088 in series MG Energy Systems B.V. | Foeke Sjoerdswei 3 | 8914 BH Leeuwarden | The Netherlands +31 (0)58 750 89 47 | info@mgenergysystems.eu | www.mgenergysystems.eu...
MODELS 5.1 Models and configurations The RS series lithium-ion battery features 4 configuration varying in voltage and capacity. This makes a system scaleable to the needs of the application. All configurations have the same enclosure dimensions, safety features and components. For a complete overview of the specifications and features of each configuration please refer to chapter 11.
Page 16
Selection of the battery strategy is done in the master BMS, pleae refer to the manual of the specific master BMS for details. MG Energy Systems B.V. | Foeke Sjoerdswei 3 | 8914 BH Leeuwarden | The Netherlands +31 (0)58 750 89 47 | info@mgenergysystems.eu | www.mgenergysystems.eu...
The connectors used for connecting the battery, auxiliary, and diagnostics CAN-bus are all of the same type, namely a circular M12 connector with 5 positions and A-coded keying. MG Energy Systems B.V. | Foeke Sjoerdswei 3 | 8914 BH Leeuwarden | The Netherlands +31 (0)58 750 89 47 | info@mgenergysystems.eu | www.mgenergysystems.eu...
The diameter of the exhaust is dimensioned to connect piping with an inner diameter of 80 mm. MG Energy Systems B.V. | Foeke Sjoerdswei 3 | 8914 BH Leeuwarden | The Netherlands +31 (0)58 750 89 47 | info@mgenergysystems.eu | www.mgenergysystems.eu...
PPS connection is not connected to a pressurized container with at least 12 liters of PPS fluid. MG Energy Systems B.V. | Foeke Sjoerdswei 3 | 8914 BH Leeuwarden | The Netherlands +31 (0)58 750 89 47 | info@mgenergysystems.eu | www.mgenergysystems.eu...
Depending on the battery module configuration and space available in the vessel, different physical setups can be created. Figure 9 - Battery arrangement examples MG Energy Systems B.V. | Foeke Sjoerdswei 3 | 8914 BH Leeuwarden | The Netherlands +31 (0)58 750 89 47 | info@mgenergysystems.eu | www.mgenergysystems.eu...
Each battery module must be fused separately when paralleld, e.g. in the junction box. MG Energy Systems B.V. | Foeke Sjoerdswei 3 | 8914 BH Leeuwarden | The Netherlands +31 (0)58 750 89 47 | info@mgenergysystems.eu | www.mgenergysystems.eu...
Page 26
A separate document is available which contains an overview of all standard available cables and ordering information, ask MG Energy Systems for a copy. MG Energy Systems B.V. | Foeke Sjoerdswei 3 | 8914 BH Leeuwarden | The Netherlands +31 (0)58 750 89 47 | info@mgenergysystems.eu | www.mgenergysystems.eu...
The use of the fluid cooling system is mandatory in case of a marine project where a class register is involved. It will add safety and will mitigate risks. MG Energy Systems B.V. | Foeke Sjoerdswei 3 | 8914 BH Leeuwarden | The Netherlands +31 (0)58 750 89 47 | info@mgenergysystems.eu | www.mgenergysystems.eu...
: ≥ Ø80 mm or equivelant area; Temperature resistance : ≥ 75 °C; Material : steel of stainless steel. MG Energy Systems B.V. | Foeke Sjoerdswei 3 | 8914 BH Leeuwarden | The Netherlands +31 (0)58 750 89 47 | info@mgenergysystems.eu | www.mgenergysystems.eu...
Page 29
The output of the exhaust ducting must be routed to an area where the released toxic and flammable gasses cannot harm people or be ignited. MG Energy Systems B.V. | Foeke Sjoerdswei 3 | 8914 BH Leeuwarden | The Netherlands +31 (0)58 750 89 47 | info@mgenergysystems.eu | www.mgenergysystems.eu...
Pressurized tank volume must be at least 1.5 times the PPS fluid volume; Tank pressure must be between 2 Bar and 3 Bar; MG Energy Systems B.V. | Foeke Sjoerdswei 3 | 8914 BH Leeuwarden | The Netherlands +31 (0)58 750 89 47 | info@mgenergysystems.eu | www.mgenergysystems.eu...
If a fire exthinguishing system is required in the battery room the system using freshwater sprinklers is preferred. MG Energy Systems B.V. | Foeke Sjoerdswei 3 | 8914 BH Leeuwarden | The Netherlands +31 (0)58 750 89 47 | info@mgenergysystems.eu | www.mgenergysystems.eu...
During installation a check form needs to be used to log the installation procedure. This log will be checked during commissioning. MG Energy Systems B.V. | Foeke Sjoerdswei 3 | 8914 BH Leeuwarden | The Netherlands +31 (0)58 750 89 47 | info@mgenergysystems.eu | www.mgenergysystems.eu...
Make sure a toothed contact washer is used to make a good connection through the powder coating. MG Energy Systems B.V. | Foeke Sjoerdswei 3 | 8914 BH Leeuwarden | The Netherlands +31 (0)58 750 89 47 | info@mgenergysystems.eu | www.mgenergysystems.eu...
This cannot be switched because connectors are keyed. 2. Push the orange/black lip forward to lift the locking mechanism. MG Energy Systems B.V. | Foeke Sjoerdswei 3 | 8914 BH Leeuwarden | The Netherlands +31 (0)58 750 89 47 | info@mgenergysystems.eu | www.mgenergysystems.eu...
To avoid EMC issues it is recommended not to route CAN-bus cables along side power cables. MG Energy Systems B.V. | Foeke Sjoerdswei 3 | 8914 BH Leeuwarden | The Netherlands +31 (0)58 750 89 47 | info@mgenergysystems.eu | www.mgenergysystems.eu...
Page 37
2. Bring the connections face of the cable connector up the device connector in such a way that the position of the key matches to that of the opposing connector. MG Energy Systems B.V. | Foeke Sjoerdswei 3 | 8914 BH Leeuwarden | The Netherlands +31 (0)58 750 89 47 | info@mgenergysystems.eu | www.mgenergysystems.eu...
Depending on the required certification, it might be necessary to test the ducting system for approval, e.g. pressure test the ducting system for leakage. MG Energy Systems B.V. | Foeke Sjoerdswei 3 | 8914 BH Leeuwarden | The Netherlands +31 (0)58 750 89 47 | info@mgenergysystems.eu | www.mgenergysystems.eu...
1. Place the unpinched hose clamp over the hose end. Figure 18 - Hose clamp in place before fitting MG Energy Systems B.V. | Foeke Sjoerdswei 3 | 8914 BH Leeuwarden | The Netherlands +31 (0)58 750 89 47 | info@mgenergysystems.eu | www.mgenergysystems.eu...
Page 40
4. Hoses in place and secured. Pinch the hose clamp according the manufacturers instruction and with appropriate tooling. MG Energy Systems B.V. | Foeke Sjoerdswei 3 | 8914 BH Leeuwarden | The Netherlands +31 (0)58 750 89 47 | info@mgenergysystems.eu | www.mgenergysystems.eu...
PPS fluid comes out. Check the pressure after bleeding the system and bring it back to 2-3 bar gage pressure. MG Energy Systems B.V. | Foeke Sjoerdswei 3 | 8914 BH Leeuwarden | The Netherlands +31 (0)58 750 89 47 | info@mgenergysystems.eu | www.mgenergysystems.eu...
MG Diagnostic Tool software. The frequency on which the SoH check is carried out depends on the applicable rules, but must be done at least annually. MG Energy Systems B.V. | Foeke Sjoerdswei 3 | 8914 BH Leeuwarden | The Netherlands +31 (0)58 750 89 47 | info@mgenergysystems.eu | www.mgenergysystems.eu...
+20 sec. Clear < 60 °C 20 sec. Over temperature critical Failsafe >= 80 °C +60 sec. MG Energy Systems B.V. | Foeke Sjoerdswei 3 | 8914 BH Leeuwarden | The Netherlands +31 (0)58 750 89 47 | info@mgenergysystems.eu | www.mgenergysystems.eu...
>= 10 °C Clear Difference highest and lowest cell 4-6 min. temperature < 8 °C MG Energy Systems B.V. | Foeke Sjoerdswei 3 | 8914 BH Leeuwarden | The Netherlands +31 (0)58 750 89 47 | info@mgenergysystems.eu | www.mgenergysystems.eu...
Clear > -38 °C 1 sec. Under temperature critical Interrupt <= -38 °C 75 sec. HVIL MG Energy Systems B.V. | Foeke Sjoerdswei 3 | 8914 BH Leeuwarden | The Netherlands +31 (0)58 750 89 47 | info@mgenergysystems.eu | www.mgenergysystems.eu...
>= 95 °C 1 sec. HVIL Over temperature critical Interrupt >= 95 °C 75 sec. HVIL MG Energy Systems B.V. | Foeke Sjoerdswei 3 | 8914 BH Leeuwarden | The Netherlands +31 (0)58 750 89 47 | info@mgenergysystems.eu | www.mgenergysystems.eu...
End-of-Life is 70% of initial capacity at 25 °C. Charge up to max. 4.05V per cell. Continuous current ratings must be de-rated to ≤ 300 A. Type approval pending. MG Energy Systems B.V. | Foeke Sjoerdswei 3 | 8914 BH Leeuwarden | The Netherlands +31 (0)58 750 89 47 | info@mgenergysystems.eu | www.mgenergysystems.eu...
Page 49
Innovation in energy storage Figure 22 – Dimensions [mm] MG Energy Systems B.V. | Foeke Sjoerdswei 3 | 8914 BH Leeuwarden | The Netherlands +31 (0)58 750 89 47 | info@mgenergysystems.eu | www.mgenergysystems.eu...
Exhaust ducting flange type MGRS00100001 Systems B.V. MG Energy Exhaust ducting sleeve type MGRS00100002 Systems B.V. MG Energy Systems B.V. | Foeke Sjoerdswei 3 | 8914 BH Leeuwarden | The Netherlands +31 (0)58 750 89 47 | info@mgenergysystems.eu | www.mgenergysystems.eu...