Summary of Contents for Meanwell DLC-02-KN

  • Page 1 DLC-02-KN Installation manual KNX DALI Gateway...
  • Page 2 DLC-02-KN is a KNX to DALI gateway, used to connect a digital DALI lighting system to the KNX installation. Room-based lighting control is conveniently incorporated into the higher-level KNX system building management system. The device transforms switch and dim commands from the connected KNX system into DALI telegrams and status information from the DALI bus into KNX telegrams.
  • Page 3: Table Of Contents

    Contents 1 Safety Guidelines 6.ETS Parameters 6.1 General 2.Overview 6.2 ECGs enable 2 1 . Overview evice 6 3 . Groups enable Information at the ETS- 6 4 . Timers enable Software 6 5 . Effects enable 2 3 . Features 2 4 .
  • Page 4: Safety Guidelines

    Risk of fatal injury from electrical current all work carried out on the unit may only be performed by skilled electricians. Observe the The manual refers to the following devices: regulations valid in the country of use, as well as the valid KNX DLC-02-KN: INPUT: 100 305Vac – guidelines. Model Encoding...
  • Page 5 2. Displays and operating elements 2. Status LEDs LED Indicator Status Normal working POWER NOT connected to AC Relay ON (short) μ μ μ μ POWER K1, K2, K3, K4 DLC-02 -KN Relay OFF (open) DALI Controller MOVE Prog.>1s Bus voltage normal L M N DALI-A, DALI-B DALI-A...
  • Page 6: Installation

    54.4 Wiring of the DALI segments Load ETS database and install μ μ μ μ (or devices to the relays) DAC app POWER DLC-02-KN DALI Controller Prog.>1s MOVE DALI-A DALI-B ETHERNET KN- KN+ Connect the gateway to ETS-DCA DALI commissioning...
  • Page 7: Mounting

    Web browser end (optional) ( ) e Shake the unit slightly to check the locking action. The maximum length is 100m. μ μ μ μ POWER DLC-02-KN DALI Controller MOVE Prog.>1s DALI-A DALI-B KN- KN+ ETHERNET KNX BUS KNX system...
  • Page 8: W Iring

    Use wires with an adequate cross-section. This etsapp file can be downloaded from the official Mean Well Use suitable mounting tools to do the wiring. website or link below: https://building.meanwell.com/Upload/PDF/KNX_Application%20Database.pdf AC and relay terminals DALI terminals KNX bus terminal Type...
  • Page 9: Parameter Configuration

    4.DALI Commissioning 3.6 Parameter Configuration The parameters and the corresponding group addresses can then be Following the physical installation and wiring of the DALI ECGs and configured as with any other KNX product. The DALI specific lights and the electronic commissioning, the connected ECGs need to configuration is performed in the DCA tab.
  • Page 10 To identify the devices switch the corresponding lamp on and off. If Hit2: There are 16 scenes available to be used. Check a scene to activate you select an ECG and press the right mouse button, a context menu appears from which you can select the required function. Group assigning and scene editing also can be done in the context menu.
  • Page 11: Communication Objects

    5.Communication Objects Please remember that at this point all operations that have been performed are only displayed in the work space. They are not Communication objects available for communication of the device via immediately loaded onto the DALI gateway. To start the process the KNX are shown in the table below.
  • Page 12 Object Object Flag Flag Length Function Description Length Function Description Function Function DALI Bus A - Night Reports the [Dali A] 1 bit Start/Stop Activate/Stop [Dali A] 1 bit Alarm 0 = No Error; mode. presence of a ECG Active Night (DPT 1.010) (DPT 1.005) 1 = Error...
  • Page 13 Object Object Flag Flag Length Function Description Length Function Description Function Function Sends the on/off DALI Bus B [Dali A] 4 bytes Bit-combined Status [Dali B] 1 byte Percentage Absolute status for ECG 1 - broadcast absolute On/Off info on/off Broadcast (DPT5.001) Dimming...
  • Page 14 Object Object Flag Flag Length Function Description Length Function Description Function Function DALI Bus B - Test [Dali B] 1 bit Start/Stop Activate/Stop This object is used [Dali B] 1 bytes Diagnostics mode. Activate (DPT1.010) to send the error value Diagnostics Test Mode Activates or...
  • Page 15 Object Object Flag Flag Length Function Description Length Function Description Function Function Sends the on/off This object is used [Dali B] 4 bytes Bit-combined Status [Central 3 bytes Time of day Time status for ECG 17 - to set the time. The On/Off info on/off Function]...
  • Page 16 Object Object Flag Flag Length Function Description Length Function Description Function Function Sends the on/off Sends the dimming [A:ECG 1] 1 bit Switch CRT 0 = Off; [A:ECG 1] 1 byte percentage CRT 0 - 100% status of the ECG. value of the ECG.
  • Page 17 Object Object Flag Flag Length Function Description Length Function Description Function Function This object is used Reports the [A:ECG 1] 1 bit Enable 0 = Unlock; [A:ECG 1] 1 bit Alarm 0 = No Error; to lock/unlock the Failure presence of an ECG Lock (DPT1.003) 1 = Lock...
  • Page 18 Object Object Flag Flag Length Function Description Length Function Description Function Function Converter Mode. [A:ECG 1] 2 bytes Dali converter CRT Status [A:ECG 1] 6 bytes Dali CRT Result LTRF LTRD LTRP 0 SD SP This object is used r r r Converter status of A...
  • Page 19 Object Objects of ECG 2 to ECG 64 in DALI Bus A segment, please refer to descriptions of Flag Length Function Description Function those objects in ECG1 Object SF, SD, SP: Start Flag Length Function Description Function method of last Functional / [A:Group1] 1 bit...
  • Page 20 Object Object Flag Flag Length Function Description Length Function Description Function Function This object is used [A:Group1] 1 byte Percentage CRT 0 - 100% [A:Group1] 1 bit Enable 0 = Unlock; Sends the dimming to lock/unlock the Dimming (DPT5.001) Lock (DPT1.003) 1 = Lock value of the group.
  • Page 21 Object Object Flag Flag Length Function Description Length Function Description Function Function This object is used 2184 Forced control [A:Group1] 1 bit Alarm [Relay 1] 2 bit Switch 2-Bit 0 = No Exeeded; 1 = Exeeded to report that the function: Operation (DPT1.005)
  • Page 22: Ets Parameters

    6.ETS Parameters Object Flag Length Function Description Function The ETS parameters of the device are distributed across different 2201 This object is used [Timer 1] 1 byte percentage 0 - 100% parameter pages. To simplify the overview, only the parameter pages to send dimming Percentage (DPT5.001)
  • Page 23 .1. General setting The chart shows the dynamic range for this parameter: There are SYSTEM, KNX FAILURE, AFTER MODE, BROADCAST, ETS-text Dynamic range Comment RELAY CONTROL and RCT in the page [default value] Startup timeout 2 60s – All functions run after [2s] startup timeout finished.
  • Page 24 The chart shows the dynamic range for this parameter: 6.1.1.3 General setting - AFTER MODE ETS-text Dynamic range Comment default value default value Behavior after broadcast off Uses this parameter to set ● KNX Bus power broadcast on the behaviors of the ●...
  • Page 25 .1.1. General setting - BROADCAST .1.1. General setting - RELAY CONTROL The chart shows the dynamic range for this parameter: ETS-text Dynamic range Comment default value default value Dali n Broadcast Unchecked Unchecked Use this parameter to ● n=A or B Checked enable the broadcast ●...
  • Page 26 The following chart shows the objects that belong to general The chart shows the dynamic range for this parameter: setting: ETS-text Dynamic range Comment Number Name Length Usage default value default value [Central Function] 1 bit Output mode normally opened normally opened This object is use to Defines the default...
  • Page 27 .1.1. General setting - RTC ETS-text Dynamic range Comment default value default value Priority/ no change no change Activates or deactivates ● the function. Force control 2Bit forced control ● The chart shows the dynamic range for this parameter: 1Bit priority ON ●...
  • Page 28: Ecgs Enable

    6.2.1 ECG (out group) 6.2 ECGs enable This page only appears when the ECG is not assigned to a group. A: ECGs enable and B:ECGs enable pages are used to display ECGs There are NAME&TYPE, FAILURE&RECOVERY, DIMMING CURVE, status and cannot be parameterized. It is the DCA that can be used to SWITCH, DIMMING, STATUS, LOCK and FUNCTIONS in the page.
  • Page 29 6 2 1 . . .1 ECG (out group) - NAME&TYPE ETS-text Dynamic range Comment default value default value Prolong time on 0 – 20 min Sets the time to remain in recovery ★ [0min] the extended emergency mode after main voltage recovery.
  • Page 30 The following chart shows the objects that belong to general Number Name Length Usage setting: [A:ECG 1] 1 bit Converter Mode. This Converter Number Name Length Usage object is used to send Status the status of a converter [A:ECG 1] 1 byte This object is used to with the following...
  • Page 31 Number Name Length Usage Number Name Length Usage [A:ECG 1] 6 bytes Bit 2: Started by LTRF LTRD LTRP 0 SD SP Converter r r r Gateway. LDTR LPDTR Test Result Bit 3: Reserved. U U U U U U U U LDTR: Last Duration This object is used to Test Result.
  • Page 32 The chart shows the dynamic range for this parameter: The chart shows the dynamic range for this parameter: ETS-text Dynamic range Comment ETS-text Dynamic range Comment default value default value default value default value Value on DALI switch-off value Dimming curve Uses this parameter to set Sets the dimming curve for ●...
  • Page 33 The following chart shows the objects that belong to general The following chart shows the objects that belong to general setting: setting: Number Name Length Usage Number Name Length Usage [A:ECG 1] 1 bit [A:ECG 1] 4 bit Use this object to switch This object is used for On/Off Relative...
  • Page 34 The following chart shows the objects that belong to general Number Name Length Usage setting: [A:ECG 1] 1 byte Sends the dimming Dimming Number Name Length Usage value of the ECG. Value (Status) 1.The parameter: Send [A:ECG 1] 1 bit Sends the on/off status dimming value status On/Off...
  • Page 35 The following chart shows the objects that belong to general .2.1. ECG (out group) LOCK – setting: Number Name Length Usage [A:ECG 1] 1 bit This object is used to Lock lock/unlock the ECG. .2.1.8 ECG (out group) FUNCTIONS – The chart shows the dynamic range for this parameter: ETS-text Dynamic range...
  • Page 36 ETS-text Dynamic range Comment Panic mode ● default value default value The chart shows the dynamic range for this parameter: Auto-off disable/ no object no object Utilizes an object to ● ETS-text Dynamic range Comment enable object ★ 0=disable; enable/disable Auto-off ●...
  • Page 37 6.2.2 ECG (in group) The following chart shows the objects that belong to general setting: This page only appears when the ECG is in a group. There are NAME&TYPE and OPERATION HOURS in the page. Number Name Length Usage [A:ECG 1] 1 bit Resets the operating Operation...
  • Page 38 The chart shows the dynamic range for this parameter: ETS-text Dynamic range Comment default value default value ETS-text Dynamic range Comment Duration test 0 – 52 weeks default value default value Sets the periodic time for interval ★ [2weeks] automatic execution of the ECG Name ----- You can enter a user-...
  • Page 39: 3 . Groups Enable

    ETS-text Dynamic range Comment Number Name Length Usage default value default value [A:ECG 1] 1 bit This object is used to Select data type ● 4 Byte value in 4 Byte value in Operation Sends status signals from report that the operation second second Hours Exeeded...
  • Page 40 ETS-text Dynamic range Comment default value default value Value 0 -100% Use this parameter to set a [100%] desired value. [This option only exists when “ defined value “ “Value on DALI Power Fail “ is chosen]. 6 3 1 .
  • Page 41 6 3 3 . . Group SWITCH – The following chart shows the objects that belong to general setting: Number Name Length Usage [A:Group1] 1 bit This object is used to On/Off switch the group on or off. 6 3 4 .
  • Page 42 The following chart shows the objects that belong to general The following chart shows the objects that belong to general setting: setting: Number Name Length Usage Number Name Length Usage [A:Group1] 4 bit [A:Group1] 1 bit This object is used for This object is used to Relative On/Off(Status)
  • Page 43 Number Name Length Usage ETS-text Dynamic range Comment default value default value 3.The parameter: Send Value 0 100% – dimming value status Use this parameter to set a [100%] desired value. is always at input of telegram send [This option only exists telegram in every when “...
  • Page 44 6 3 7 . . Group FUNCTIONS – The following chart shows the objects that belong to general setting: Number Name Length Usage [A:Group1] 1 bit This object is used to Auto Off enable/disable the Auto Off function of the group.
  • Page 45: 4 . Timers Enable

    Operation hours calculation Number Name Length Usage ● The chart shows the dynamic range for this parameter: [A:Group1] byte The operating hours of Operation Hours the group in seconds are ETS-text Dynamic range Comment Value sent via this object. The default value default value internal counter can be...
  • Page 46 The chart shows the dynamic range for this parameter: Control type ● The chart shows the dynamic range for this parameter: ETS-text Dynamic range Comment [default value] ETS-text Dynamic range Comment default value default value Timer n function Unchecked Unchecked Use this parameter to ●...
  • Page 47 ETS-text Dynamic range Comment The following chart shows the objects that belong to general setting: default value default value Wednesday ★ Unchecked Unchecked Whether to trigger the ● Number Name Length Usage Checked timer on Wednesday. ● 2200 [Timer 1] 1 bit This object is used to Tuesday...
  • Page 48 The chart shows the dynamic range for this parameter: ETS-text Dynamic range Comment default value default value ETS-text Dynamic range Comment Effect Repeating Unchecked Unchecked Decide whether to repeat ● [default value] Checked the effect functions or not. ● Channel ●...
  • Page 49: Warranty

    MEAN WELL possesses the right to adjust the content of this manual. ※ Please refer to the latest version of our manual on our website. https://www.meanwell.com MEAN WELL WEB...
  • Page 50 N o . 2 8 , W u q u a n 3 r d R d . , W u g u D i s t . , N e w Ta i p e i C i t y 2 4 8 , Ta i w a n...