GE GSTG024D Installation Instructions
GE GSTG024D Installation Instructions

GE GSTG024D Installation Instructions

Entelliguard g circuit breaker accessories

Advertisement

Quick Links

Introduction
Shunt Trip (Extended Range):
A device designed to switch the Power Circuit
Breaker OFF remotely. When energized a Shunt
Release instantaneously activates the circuit
breaker mechanism ensuring a rapid
disconnection of the main contacts.
Two Shunt trips can be mounted in each Power
Circuit Breaker. The devices are available as
factory mounted components or as field
mountable devices. It is an easy-to-fit, clip-on unit,
with simple plug-in connectors to the Secondary
Disconnect Block.
Table 1. Catalog Numbers and Ratings
Catalog
DC
No.
Voltage
GSTG024D
24V
GSST024D
24V
GSTG048
48V
GSTG072
70-72V
GSTG120
110-125V
GSST120
110-130V
GSTG208A
GSTG240
220V
GSST240
220-240V
GSTG250D
250V
* Momentary Rated shunt trip requires wiring one or more NO
(Normally Open) breaker aux contact(s) in series with the accessory to
avoid coil damage.
AC
Rating*
Voltage
Continuous
Momentary
48V
Continuous
Continuous
120-125V
Continuous
110-130V
Momentary
208V
Continuous
240V
Continuous
220-240V
Momentary
Continuous
Use the following procedure to install the Shunt
Trip accessory into the circuit breaker.
1. Verify that the rating on the Shunt Trip
Mechanism identification plate matches the
voltage rating required for the application, as listed
in Table 1.
2. Turn the breaker off and discharge the closing
springs by depressing the OFF and ON buttons in
the sequence OFF-ON-OFF. Verify that the breaker
OFF-ON indicator shows OFF on a green
background and that the charge indicator shows
DISCHARGE on a white background. If installing in
a draw-out type breaker remove breaker from
adaptor (cassette) before continuing.
3. Loosen the 6 screws on front cover (fascia) using
a posidrive screw driver as shown in Fig 1.B
Rotate the charging handle down and slide the
front cover over the handle to remove the front
cover as shown in Fig. 1.C .
1

Advertisement

loading

Summary of Contents for GE GSTG024D

  • Page 1 OFF-ON indicator shows OFF on a green Catalog Rating* background and that the charge indicator shows Voltage Voltage DISCHARGE on a white background. If installing in GSTG024D Continuous a draw-out type breaker remove breaker from GSST024D Momentary GSTG048 Continuous adaptor (cassette) before continuing.
  • Page 2 rear hooks engage in the slots on the mechanism top support plate as shown in Fig. 4. Figure 1. (A) Front Cover (B) Screw Removal (C) Handle Rotation 4. This accessory is mounted on the mechanism top plate at 1st or 4th location as shown in Figure 3.
  • Page 3 Figure 5. Wiring. 7. Ensure that the plug in connection is firm and that the plug is inserted into the correct terminals. Figure 6. 8. To reinstall the breaker cover rotate the charging handle down and slide the front cover over the handle to assemble the front cover to 10.
  • Page 4 Reference: GSTG type Continuously Rated Shunt Trip Connection Scheme...
  • Page 5 These instructions do not purport to cover all details or variations in equipment nor, to provide contingency to be met in connection with installation, operation, or maintenance. Should further information be desired, or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to GE. 41 Woodford Ave, Plainville, CT 06062 www.geindustrial.com...