Summary of Contents for Ventilair Comair Aquacom
Page 2
All rights reserved. The information and instructions in this manual are subject to print errors and misspelling. No rights can be derived from the information contained herein. Version 2.0 Ventilair Group Nederland...
Table of Contents Glossary ....................................... 4 Introduction ....................................5 Why should you ventilate?................................5 System D with ground heat exchanger ............................5 Operation of the Aquacom ................................5 Aquacom advantages ..................................5 Safety ......................................5 Warranty ...................................... 6 Liability ......................................6 Deliveries ......................................
Glossary To use the Aquacom correctly, it is important to amount of supplied and extracted air is adjusted by know the following definitions first. the valves. Ground heat exchanger That is why it is important to keep the same A ground heat exchanger is used to preheat the settings of the valves and to keep the valves at the supply air in the winter and to cool it in the same place.
Introduction Read this entire manual carefully before installing and/or using the Aquacom. This guide gives you step by step guidelines for proper and safe installation, operation and maintenance of the Aquacom. Installation must be performed by a qualified installer. Incorrect or incomplete installation may cause the system not working properly, which may affect air quality in the house.
Installing, operating effectuating 3. Major maintenance unit maintenance of the Aquacom must always be committed by an unauthorized maintenance done by a certified installer, unless minor technician. maintenance is concerned and is indicated as 4. There are signs of abuse or modifications on such in this manual.
User's manual This section of the manual provides the failure occurs, Aquacom will restart in the same information to operate the Aquacom correctly, mode in which it was before the power failure. what to do with an error and how to effectuate maintenance.
Sub menu 3 – Time the Aquacom unit). When this amount is After entering this menu, the value of the hour will higher, more ground energy will start blinking. Using the buttons, this transferred to the ventilation air. The achieved value can be changed.
operation of the Aquacom needs to be checked on Clean the plate on which the filter rests. the basis of the different meters. For the Possibly there are larger contaminations like appropriate designation and the location of every stones and leaves. meter you are referred to section 6.3.
Installers manual This section of the manual provides the Check whether the brackets are attached information needed to install, program and correctly and whether its positions are correct. maintain the Aquacom unit correctly. Information Remove both covers which are fixed by the about errors and reports can be found in section clip closures.
The depth of the duct network does not During installation of the duct network, the matter for the pump, since it is a closed roll wants to return to the original, rolled up, system. state. To prevent this, sand or bent reinforcing The depth of the duct network has a large bars can be applied to the duct.
unit, follow the steps as indicated in section sprout and lid, and reattach them by turning 4.1. them clockwise. Level the unit using the adjusting bolts at the Place the inlet of fresh air preferably on the bottom. This ensures a proper disposal of the shady side of the house;...
4.2 Setting the Aquacom Once the unit is mounted and the system is filled, the control unit has to be set. Check again that all air pipes and electrical connections are connected properly. 4.2.1 Setting the Aquacom In this part of the manual, sub menu 6 will be explained further.
Page 14
6.1 T summer removed manually by pressing one of the buttons. When this menu is chosen, it is possible to change Also see section 5.2.4. this value between 11 and 30 °C. The entered value 6.5 P summer is confirmed by pressing .
button all messages can be required, the pump will start switching on and off. Every three minutes the pump will be activated for viewed. By pressing when 'rem. errors?' is shown, all saved error messages will be deleted. X percent of the time. The percentage X for the time the pump is active Error messages will be shown as following: Fx F = yy dd.mm...
Fill the hose with water to avoid air in the 4.4.3 Check the heat exchanger system Open the front cover. Then check if the fins are not Attach the hose to the filling unit and open the bent and/or the seams are not open. Also check water connection completely whether the copper tubes are not bent or leaking.
Error Messages This section explains which error messages can The error schemes are meant for the installer. Do occur and how these can be repaired. Also, for not perform these actions if you are an end user. every action it will be note who should carry out The message is shown until the error is repaired.
5.2 Error schemes This scheme meant 5.2.1 General error installer only. The unit no longer works properly or the Maintenance performed error is not indicated in the table. by the end user is not only dangerous, but also has disadvantageous conse- Reset the unit by pulling out the plug during 10 seconds quences for the warranty.
This scheme 5.2.2 Sensor error meant installer only. Wire break or short circuit on Maintenance performed by the end user is not only sensor (T1 of T2) dangerous, but also has disadvantageous conse- quences for the warranty. Pull the plug out of the socket Open the front cover using the clip locks and open the control unit...
This scheme 5.2.3 Error data transfer meant installer only Error data transfer Maintenance performed by the end user is not only dangerous, but also has Pull the plug out disadvantageous conse- of the socket quences for the warranty. Replace the control unit and put the plug back in the socket...
This scheme 5.2.4 No heating meant installer only. Maintenance performed Also see ‘frost limit’ in section 4.2.1. by the end user is not only dangerous, but also has disadvantageous conse- Tempdiff. < 0,5K quences for the warranty. Press one of the buttons on the display Does the flow meter indicate a flow?
6.2 Drawings These are the drawings for the dimensions of the the left and right side will be switched. All Aquacom for the recommended setup. This measures are in mm. composition is easiest to perform maintenance. If the mounting brackets are turned to the other TNV = Supply towards fan side, the front will be the back and vice versa.
The next table lists the same components as the previous figure. In this table, also the item numbers are specified to make reorders at the supplier. Note that for some parts also the gaskets need to be replaced. Number Part Item number Necessary gaskets Heat exchanger...
Appendix I: Connecting glycol water duct with PE connector If the ends of the ducts are not completely perpendicular, cut them off perpendicular without contaminating the inside of the duct. Also remove burrs from the duct without contaminating the inside of the duct Unscrew the coupling nut so 75% of the thread is visible.
Appendix II: Maintenance by the end user This appendix provides you, as an end user, information about the maintenance of your unit. Cleaning/replacing the filters Make sure you carefully follow all steps from section 3.3 of the scheme on the next page when performing maintenance on the filters.
Page 27
Filter change necessary Pull the plug out of the socket of both the Aquacom and the eternal fan Open the front cover using the clip locks Replace the filter, make sure the arrow on the filter points towards the heat exchanger Clean the sheet metal on which the filter rests...
Appendix III: Maintenance overview When you performed maintenance on the unit, write this down below, to keep an overview of it. The first table shows which maintenance should be performed and what maintenance has been performed in the past. The bottom table can be used to keep track when you changed the filter.