Advertisement

RT 45
Operating Instructions
Zertifiziertes
Qualitätssystem
ISO 9001
Reg. Nr.
11265
SWISS MADE

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the RT 45 and is the answer not in the manual?

Questions and answers

Summary of Contents for REGLOPLAS RT 45

  • Page 1 RT 45 Operating Instructions Zertifiziertes Qualitätssystem ISO 9001 Reg. Nr. 11265 SWISS MADE...
  • Page 2 English Operating Instructions Valid from software version 345 Pages 75–109 Subject to change without notice...
  • Page 3: Table Of Contents

    Operating Instructions Control System RT 45 Contents 1. General Comments 2. Range of Application 3. Operating elements and displays 4. Switching on 5. Switching off 6. Displays Operational displays section 6.1 Malfunction displays 6.2 7. Programming SEt SEL section 7.1 SEt Fun section 7.2...
  • Page 4: General Comments

    2. Range of Application The RT 45 control system was developed for use in temperature control units (hereafter referred to as “unit”). It enables dialog between one or more units and the processor of the production facility via an interface as well as operation independent of the processor.
  • Page 5: Switching On

    6 dots will appear in the two display fields (Section 6.1, display 1). If another display lights up, see Section 6.1. After the test has been run successfully, the dots will disappear; the RT 45 is ready for operation. In the right display field, “oFF” will appear.
  • Page 6: Switching Off

    “PtE” (see Section 7.2). The pump and control system are then switched off. The RT 45 switches to stand-by mode. All displays are extinguished, with the exception of the alarm display and “oFF”.
  • Page 7: Malfunction Displays

    SUCTION LEAK STOP Suction mode (except P 140S) or drainage by compressed air is activated when the upper lamp is lit. SUCTION LEAK STOP Leak-stop mode is activated when the lower lamp is lit (except P 140S). In normal operation, the temperature set value SP1 is displayed. Indicates the set value temperature when input externally (0 to 10 V or 0/4 to 20 mA).
  • Page 8 The display indicates when servicing is due (SErV). The display disappears when the unit is switched on via the “On/Off” key, but will reappear as soon as the unit is switched off. When servicing has been completed, the elapsed time to the next service must be entered (see Sec- tion 7.2, Programming “S.”).
  • Page 9 ALARM RESET a) One or more phases are missing. b) The motor contactor has not picked up as it should. c) The motor contactor has not released as it should. – OVER ALARM TEMP RESET The electromechanical safety thermostat in the unit has been tripped. The cooling system is switched on.
  • Page 10 Water as circulating fluid: if the level has dropped below the upper limit, the lamp “Low Level” will flash during refilling. When the level has dropped below the lower limit, the alarm will appear immediately. Pump and heat- ing are switched off. Thermal oil as circulating fluid: if the level has dropped below the upper limit, the lamp “Low Level”...
  • Page 11 – ALARM RESET The programmed upper limit value of the sensor Sn2 (consumer temperature) has been exceeded (see Section 11.1, Fig. 2). Unit and control will continue to run normally. – ALARM RESET The temperature registered by sensor Sn2 (fluid temperature) has fallen below the laver limit pro- grammed (see Section 11.1, Fig.
  • Page 12 ALARM RESET Analog/Digital-Converter defective. St.1 ALARM RESET EPROM defective. St.2 ALARM RESET RAM microprocessor defective. St.3 ALARM RESET External RAM defective. ALARM RESET Calibration values lost. The control insert has to be recalibrated in the factory. ALARM RESET Unit data in memory print has disappeared or flat cable not connected. ALARM RESET Battery timer module defective.
  • Page 13 ALARM RESET The initialising data are lost. The control system has to be reajusted in our workshops. ALARM RESET Undervoltage. Check power supply with rating plate. Two different flow meters are mounted. The heating is switched off.
  • Page 14: Programming

    7. Programming Programming is done via the “∆” and “∇” keys to raise or lower the alignment values or to reach the desired align- ment in the appropriate level (e.g. “Ltr” or “GAL”, see Sec- tion 7.2, fig. “VAL”). 7.1 Operator Level “SEt SEL” For programming the temperature-probe limit values (SEt SEnsor Limits, see Section 11.1, Fig.
  • Page 15 Appears only when the external sensor Sn2 is not connec- 1 to 11 ted. Address of the RT 45 unit with interface. Appears only when the unit is connected to the computer. 0 to 99 Setting ranges SPI 32 to 99.
  • Page 16 20 °C in mm /s. With water as heat 1.0 to 200 transfer fluid (Programming “H2O yES”), the value 1.0 is aligned automatically. Appears only if the RT 45 is equipped with interface. Proto- cols: 1 to... 1 Arburg 4800 Bd...
  • Page 17 7.3 Alarm Level “SEt ALA” Activates the alarm relay (common alarm), if present, follow- ing malfunction. The alarm relay is always activated when the limit values “S¯ ¯”, “¯te”, “S P” are exceeded, upon sensor break down (Pt100-probe also with short circuit), and when “S 1”, “S 2”...
  • Page 18 Programmed pump motor current has been exceeded. ALA. ALA/ALA. The upper limit value S1 of sensor Sn1 (fluid temperature) – ALA. has been exceeded. ALA/ALA. The value registered by sensor Sn1 has fallen below its ALA. – lower limit. ALA/ALA. –...
  • Page 19 7.4 Offset Level “SEt OFS” Offset compensation (deviations from measuring lines, measurement errors from sensors, etc.) The desired position can be reached by pressing the “∆” key or “∇” key. To move backwards: press the “P” key for a maximum of 2 s. To return to the operating level with display of the set and ∆...
  • Page 20 7.5 Parameter Level “SEt PAr” If none of the 10 parameter sets in “SEt SEL” are satisfac- ∆ ∇ tory, an individual control parameter set can be adjusted at this level. The values entered at “SEt PAr” become active only if no external sensor Sn2 is attached and the value “PAr”...
  • Page 21 7.6 System Level “SEt SyS” For programming functions and defining hardware. ∆ ∇ This level can be reached by pressing the key with the timer symbol 3 times while pressing the “∆” and “∇” keys. The desired setting can be achieved by pressing the “∆” and “∇”...
  • Page 22 Number of times the fluid level may fall below the level set n.LE until alarm is triggered. Reset to 1 approximately 30 minutes 0 to 40 after the most recent alarm. 0 = Alarm counter off. Appears only if H2O = yES (→ SEt Fun, Section 7.2). Relays 1 to 3 are used to acknowledge the following operat- ing conditions: “rEG”...
  • Page 23 Programming of relays 2 and 3. Please consult “r1” display. if in → Section 7.7 etc. Number of heating stages in the unit. “0.10” Analog recorder output “1” of the actual value of S1 0.10 or S2 in V. 0.10/0.20/ Range 0 to 10 V.
  • Page 24 – Upper measuring range value of recorder output “2”, e.g. 300 °C/572 °F. 0 to 500 (°C) 32 to 932 (°F) “S1” Recorder output “2” corresponds to actual value S1 (fluid temperature). S1/SP1 “SP1” Recorder output “2” corresponds to set value SP1. S2/SP2 “S2”...
  • Page 25 Set value (SP1, SP2) can be selected when switching on the unit via the “On/Off” key or timer. 0/1/2 “0” When the unit is switched off, the active set value is used. “1” SP1 is always used. “2” SP2 is always used. Cavity control.
  • Page 26 7.8 Level for the Timer “SEt CLC” If the RT 45 is equipped with a timer, it can be programmed at this level to switch the unit on and off. The timer is pro- tected against power failure for about 10 years.
  • Page 27 7.8.1 Setting the Timer * = programming steps 1–5 Current day. “1” = Monday 1 to 7 Current hour. 0 to 23 Current minute. 0 to 59 Display of values entered. The display shows: Wednesday, 3.10 10 h 45 min. Entry confirmation.
  • Page 28 Switch-on hour. 0 to 23 Switch-on minute 0 to 59 Second switch-on/off time Switch-off hour. 0 to 23 Switch-off minute 0 to 59 if «dAy» = 1 to 7 In options “0”, “8” and “9”, the program returns to pro- gram step 6;...
  • Page 29 Switch-off minute. Day (Tuesday). – Switch-on hour. – Switch-on minute. Switch-off hour. – Switch-off minute. – Switch-on hour. Switch-on minute. Switch-off hour. Switch-off minute.
  • Page 30 8. Controlling and Servicing In the following two levels, the most important data and unit settings can be read but not changed. 8.1 Control Level “Con L1” This level can be reached by pressing the “P” key while ∆ ∇ pressing the “∆”...
  • Page 31 “FLC yES” = optional “Measurement of Flow Rate” pre- sent. Otherwise “FLC no”. If interface Ser CL, 422, 232 485, CAN or PB present. Otherwise “SEr no”. 8.2 Control Level “Con L2” This level can be reached by pressing the “P” key while ∆...
  • Page 32 8.3 Settings Level Factory “rES Et” The factory alignments are stored at this level; values are also updated, e.g. after modified programming or undefined status of RT 45. ∆ ∇ Note: Do not switch off the unit under any circumstances when “rES Et”...
  • Page 33 9. Control Methods The RT 45 microprocessor uses the following processing programs (control algorithms): Cascade control: The control system switches automatically to cascade control when the tempera- ture probe Sn2 is installed in the consumer. This type of control system is very accurate, fast, and stable.
  • Page 34 Note: The set value will be reached more quickly if the actual value overshoots it slightly. If overshoot- ing is unacceptable, a somewhat longer heating-up time is to be expected. 11.4 Terminal Markings for the RT 45 1 Input Acknowledgement “Heating 1”...
  • Page 35 59 Output N Solenoid valve air intake 102 Output Analog 2 (+) 60 Output L Solenoid valve air intake 103 Output Thermocouple TC (+) 61 Output PE Solenoid valve air intake 104 Input Analog set value (+) 62 Relay 3 105 Common Analog for 101–104 (–) 63 Relay 3...
  • Page 36 11.5 Technical Data RT 45 Setting range 0 to 420 °C/32 to 788 °F. (SOF 333: –40 to 420 °C/–40 to 788 °F). Control behaviour PI/PID. Cascade, fixed programmed parameter group or indi- vidually programmable parameters. Entry of control parameters By fixed parameter groups, depending on application, or indi- vidual.
  • Page 37 Time switch on/off. Set value 1 or 2. Sensor 1 or 2. Address of unit. Fault signal lamps: Overtemperature. Level. Flow. Pumpmo- tor. Commonalarm. Phase failure. Phasesequence, etc. All disturbances in the unit are indicated on the RT 45 display. Operation Operating surface Membrane keyboard with strong polyester membrane print- ed on reverse, short-stroke keys and switch point.
  • Page 38 Regloplas AG Flurhofstrasse 158 CH-9006 St. Gallen Tel. + 41 71 282 58 00 Fax + 41 71 282 58 40 E-mail regloplas@regloplas.com Internet www.regloplas.com BA RT 45/0201/de/fr/en...

Table of Contents

Save PDF