HPD0460BN Multi-Function Room Units, BACnet MS/TP
FW4.02
The HPD0460BN devices may be used as BACnet networked HVAC devices or standalone; as an HMI
for control and display of multiple controllers on a local network, as a controller with high flexibility for
user configuration to suit a wide variety of control applications or as a network manager including multi-
zone annual time scheduling. The display is programmable to indicate user specific text and dynamic
data points. Data points may be adjusted directly at the LCD (parameters such as set-points, fan-
speeds and manual overrides). The text and dynamic values for each of the 32 user lines may be set as
small font size or large font size.
The user push-buttons, indication LED's and an audible sounder may be independently programmed to
suit the user application. Physical I/O points may be used in the system independently or, subject to the
version, by the internal control loops and logic blocks.
Depending on the version, logic function blocks enable easy configuration of a variety of functions
including Economy Changeover (temperature or enthalpy), VAV Volume, Occupancy, Hours Run
monitoring, Minutes Run monitoring, Lead/Lag changeover, instantaneous Power calculation (kW, BTU)
and a wide array of hysteresis & dead-band/live-band choices (Compare function).
The time clock version features a 365 day clock/calendar with four channel time-switch, 20 holidays
(one-off or annually recurring) and summer/winter time.
Common Features
32 line user programmable dot matrix LCD display with pop-up alarm text feature
1 Room temperature sensor on-board
1 Input programmable as DI or 10k NTC
2 Universal inputs (DI, 10k NTC, 100k NTC, 0-10Vdc or 4...20mA)
6 Digital outputs (ON/OFF, single or multi stage, 3-point floating, PWM)
4 User programmable operator buttons
4 User programmable indication LED's
1 User programmable audible alert beeper
48 Network Interface Objects (NIO's) for Peer-to-Peer communication
8 Virtual Digital Inputs (VDI)
8 Virtual Universal Inputs (VUI)
Typical Applications
Temperature, humidity, pressure, IAQ, universal
On/off, 3-point modulating, PWM (Pulse Width Modulation), step control, DX
Residential, Commercial, Hotels
Local User Interface, network interface, networked or standalone controller
Time-clock & calendar / time-switch, networked or standalone
Versions
HPD0460BN
HPD0460BNC
HPD0460BNCT
HPD0460BNT
HRW Limited
Network HMI, 10 Point, 24Vac
Network HMI / Universal Controller, 10 Point, 24Vac
Network HMI / Universal Ctrl / Scheduler, 10 Point, 24Vac
Network HMI / Scheduler, 10 Point, 24Vac
Unit E, 11/F, Sun Ying Industrial Centre
9 Tin Wan Close, Tin Wan
Hong Kong
Ph +852 2546 7402
Fax +852 2546 7403
www.hrw.hk

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the HPD0460BN and is the answer not in the manual?

Questions and answers

Summary of Contents for HRW HPD0460BN

  • Page 1 HPD0460BN Multi-Function Room Units, BACnet MS/TP FW4.02 The HPD0460BN devices may be used as BACnet networked HVAC devices or standalone; as an HMI for control and display of multiple controllers on a local network, as a controller with high flexibility for user configuration to suit a wide variety of control applications or as a network manager including multi- zone annual time scheduling.
  • Page 2 Upload text file data for retrieving lost application settings, for re-use in other controllers ©  = Available in Controller versions = Available in Time Clock versions HRW HPD0460BN V402 Manual 150622.docx E. & O. E. / Subject to change without notice Page 2 of 33...
  • Page 3: Table Of Contents

    ORDERING INFORMATION ..........................32   ............................... 32   CCESSORIES HP_BN S .......................... 32   THER ERIES EVICES DOCUMENT UPDATE HISTORY ........................33   HRW HPD0460BN V402 Manual 150622.docx E. & O. E. / Subject to change without notice Page 3 of 33...
  • Page 4: Operation Overview

    This means the HPD0460BN may be used as a user interface to a single controller or as a user interface to multiple controllers on the network.
  • Page 5: Bacnet Object Instances

    Commands from the network to Proportion Band & Integral Time points of Control Loops are written to those objects if other than null priority HRW HPD0460BN V402 Manual 150622.docx E. & O. E. / Subject to change without notice Page 5 of 33...
  • Page 6: User Interface

    The dynamic point’s unit tag may be customised The time switch display above indicates ‘1 34’ which tells us that switch channels 1, 3 & 4 are ON HRW HPD0460BN V402 Manual 150622.docx E. & O. E. / Subject to change without notice...
  • Page 7: Interface Operation

    Right side cursor indicates point now Adjustable using the up/down buttons › ‹ › HRW HPD0460BN V402 Manual 150622.docx E. & O. E. / Subject to change without notice Page 7 of 33...
  • Page 8: Large Font Display

    8 which is active on holidays  Wintertime/Summertime shift may be set to occur automatically  European or North American date format may be set HRW HPD0460BN V402 Manual 150622.docx E. & O. E. / Subject to change without notice Page 8 of 33...
  • Page 9 Holiday date setting with year =0 will occur every year  Holiday date setting with year >0 will occur once only, in the set year HRW HPD0460BN V402 Manual 150622.docx E. & O. E. / Subject to change without notice Page 9 of 33...
  • Page 10: Function Block Objects & Sub-Parameters

    * Digital 1 = 1000 (100%) when applied to these analogue logic functions. Analogue values will act as a Output Minimum when applied to an Output OR and Output Maximum when applied to an Output AND. HRW HPD0460BN V402 Manual 150622.docx E. & O. E. / Subject to change without notice...
  • Page 11 * Digital 1 = 1000 (100%) when applied to these analogue logic functions. Analogue values will act as a Output Minimum when applied to an Output OR and Output Maximum when applied to an Output AND. HRW HPD0460BN V402 Manual 150622.docx E. & O. E. / Subject to change without notice...
  • Page 12 LED/beeper will be on for 3sec, off 2sec, on 3sec, and so on. The minimum applied value for an output reaction is 20% (1sec on, 4sec off). In HPD0460BN these outputs may be driven by peer-to-peer controllers on the network or via the internal NIO’s reading in object values from other controllers on the network.
  • Page 13: Terminal Mode

    The HPECOMU data cable with USB connection is used for terminal mode between the device and a PC running a terminal program. HyperTerminal is recommended. The driver for the HPECOMU cable may be downloaded from www.hrw.hk, Resources / Tools, section. HyperTerminal Settings For successful communication between HyperTerminal and the device, initial Properties setup of HyperTerminal should be as per the screen prints below.
  • Page 14: Additional Settings

    In either case, after the Write action, you will need to reconnect the terminal program at the new baud rate if you wish to continue the terminal session. HRW HPD0460BN V402 Manual 150622.docx E. & O. E. / Subject to change without notice...
  • Page 15: Break In To Terminal Mode

    (TTTTTTT…). After five (5) T’s have been sent to the device it will switch to terminal mode. At this point the BACnet activity on the network will be halted and the device will display the default user screen. HRW HPD0460BN V402 Manual 150622.docx E. & O. E. / Subject to change without notice...
  • Page 16: Administration Commands

    Auto X after 240sec without key entry. After Exit HyperTerminal no longer eXit unplug the HPECOM cable to allow communication active network communication to take place HRW HPD0460BN V402 Manual 150622.docx E. & O. E. / Subject to change without notice Page 16 of 33...
  • Page 17: Display Navigation

    5 digit point format is standard. 8 digit point format would normally be for pulse counts or other metering related values read in via NIO HRW HPD0460BN V402 Manual 150622.docx E. & O. E. / Subject to change without notice Page 17 of 33...
  • Page 18: Manual Override / Release

    R=1…152 Example 2: R=9 to ‘Auto’ * commanded DO1 (point 9) only return to Auto HRW HPD0460BN V402 Manual 150622.docx E. & O. E. / Subject to change without notice Page 18 of 33...
  • Page 19: Operational Displays

    You may use SLL settings for alarm or warning text that will only appear when the assigned point has a value >0. HRW HPD0460BN V402 Manual 150622.docx E. & O. E. / Subject to change without notice Page 19 of 33...
  • Page 20: Download Text File

    Column 4 = The dynamic point value  Column 5 = Units related to the dynamic point value (as configured in the linearization table) HRW HPD0460BN V402 Manual 150622.docx E. & O. E. / Subject to change without notice Page 20 of 33...
  • Page 21: 'Main' Physical I/O Display

    Enter P to display the first 21 active points. The listing will include any active logic connections and, in the case of the UI’s the present calibration offset if used. HRW HPD0460BN V402 Manual 150622.docx E. & O. E. / Subject to change without notice...
  • Page 22: Control Loop (Cl) Display

    Point 37, a Digital Logic block 1, is set as the start signal for the control loop and as the enabling point for the DO’s (DO sub-parameter #02 – AND). HRW HPD0460BN V402 Manual 150622.docx E. & O. E. / Subject to change without notice...
  • Page 23: Digital Logic (Dl) & Analogue Logic (Al) Display

    AL2, Point 54 – Proportion (shift) function; CL3 output (point 71, room heating demand) proportionally shifts the supply air heating set point from 22°C up to 35°C HRW HPD0460BN V402 Manual 150622.docx E. & O. E. / Subject to change without notice...
  • Page 24: Network Interface Object (Nio) Display

    Sensor Type being shared is to be sent settings HRW HPD0460BN V402 Manual 150622.docx E. & O. E. / Subject to change without notice Page 24 of 33...
  • Page 25: Reset To Factory Default

    Notepad. Whatever the process, the 10000=nnn line must be added if the file is to be used for Down Load in future. HRW HPD0460BN V402 Manual 150622.docx E. & O. E. / Subject to change without notice...
  • Page 26: Universal Inputs

    100kΩ 0-10Vdc Link 2 to 7 Link 4 to 5 100kΩ 4…20mA Link 1 to 2 Link 3 to 4 250Ω HRW HPD0460BN V402 Manual 150622.docx E. & O. E. / Subject to change without notice Page 26 of 33...
  • Page 27: Linearisation Table

    4 and change Units display characters 134=-2 14=V (row 1 column 4) 24=d (row 2 column 4) 34=c (row 3 column 4) HRW HPD0460BN V402 Manual 150622.docx E. & O. E. / Subject to change without notice Page 27 of 33...
  • Page 28: Passive Sensor Definition

    7. If an intercept other than zero (0) is applied then raw count measurements must be at reference values shifted an equivalent amount Reset to Factory Default The FD=1 reset command also resets changes to the linearization tables HRW HPD0460BN V402 Manual 150622.docx E. & O. E. / Subject to change without notice Page 28 of 33...
  • Page 29: Installation & Commissioning

    24Vac power supplies cannot be guaranteed, we recommend that a repeater be used to provide isolation of the sections of the network having differing earth potential HRW HPD0460BN V402 Manual 150622.docx E. & O. E. / Subject to change without notice...
  • Page 30: Connections

    Connections Dimensions HRW HPD0460BN V402 Manual 150622.docx E. & O. E. / Subject to change without notice Page 30 of 33...
  • Page 31: Technical Data

    122mm H x 92mm L x 29mm D Dimensions 8 line dot matrix 62mm x 29mm visible 54mm x 24mm usable HRW HPD0460BN V402 Manual 150622.docx E. & O. E. / Subject to change without notice Page 31 of 33...
  • Page 32: Ordering Information

    BACnet gateway for M-Bus devices, 250 point, 24Vac HPE-BNMOD BACnet gateway for Modbus devices, 250 point, 24Vac HPE-BNMR10 BACnet gateway for 1 Modbus device, 10(20) point, 24Vac HRW HPD0460BN V402 Manual 150622.docx E. & O. E. / Subject to change without notice Page 32 of 33...
  • Page 33: Document Update History

    V4.02 150622 HRW address updated V4.02 141030 Minutes Run, Compare functions, upload application text-file, download network settings in text-file, isolated RS485 HRW HPD0460BN V402 Manual 150622.docx E. & O. E. / Subject to change without notice Page 33 of 33...