GENERAL DESCRIPTION
This product is a resettable fire emergency call point compatible with control panels implementing the Vega intelligent protocol.
After use, the alarm activating button can be restored with the supplied key and made ready for immediate reutilization.
AI-CPW-R-01 is composed by a back box, an intelligent loop interface plate and a front manual activation element.
IMPORTANT INSTALLATION NOTES
-
The location of call points must follow recognised national or international application codes of practice.
-
This product is to be used in conjunction with compatible control panels employing the Vega protocol.
-
Connections to loop terminals are polarity sensitive: check them by referring to the wiring instructions contained in this manual.
-
Disconnect the loop from the control panel during installation.
-
Reconnect the loop to the control panel after installation completion.
-
Test the device to check that it actually works.
-
Take care that every single device on the loop is programmed with a unique address.
INSTALLATION
1. Program a unique analogue address into the loop's interface plate belonging to the call point.
2. Record on the device's appropriate label the loop number and device address.
3. Fix the back box using the 2 provided screws: insert them in the diagonally opposite screw holes.
4. Use suitable IP rated cable glands (not supplied). Install the cable conduit plus gland into the back box entry hole.
5. Feed the loop's cables into the back box's inner space; allow sufficient length so you can perform loop wiring comfortably.
6. If present, connect the loop's shield wires to the terminal block in the back box's inner space.
7. Connect the loop's cables to the call point's interface plate.
8. Position the interface plate onto the back box; its locking hooks must be positioned on the bottom side.
9. Fix the interface plate to the back box using the supplied screws.
10. Hook the upper rear side of the front activation element onto the interface plate.
11. Push the bottom of the activation element; this will lock it together with the interface plate.
Pic. 1 - Fix the back box using the
screw holes highlighted.
ARGUS SECURITY S.R.L. - Via del Canneto, 14 - 34015 - Muggia (TS) - Italy
AI-CPW-R-01
ALTAIR INTELLIGENT WATERPROOF RESETTABLE
SHIELD
CALL POINT
Pic. 2 - Connect the loop shield wires (if they are
present) to the terminal block present in the back
box.
928h/03