Operation and maintenance manual
NCA Series 400H hand operated single blade leakage rated fire damper
Regular inspection and maintenance of fire dampers is essential to
ensure they remain in good working condition. It is the system owner's
responsibility to ensure this is carried out.
In accordance with EN 15650:2010 fire damper maintenance routines,
such as that given below, must be carried out at intervals not exceeding 6
months.
Some automatic systems may allow more frequent testing (48 hours or
less) and this may be required by national regulation.
Please note: This document is relevant only to hand operated S400
dampers. For S400 dampers equipped with an actuator
please see the relevant document.
Periodic maintenance procedure
Damper type:
Thermal link rated temperature:
Delete as appropriate
Damper reference (if applicable):
Damper location (within site):
Date of inspection:
Step Operation
1
Is the damper open?
2
Is the handle mechanism secure and
undamaged?
3
Remove access door/s to access the inside of
ductwork and damper blade
4
Is the damper blade in the fully open position
and secure?
5
Is the damper blade unobstructed?
6
Is the thermal link clean and free from
damage and corrosion?
7
Is the damper blade and case clean and free
from damage and corrosion?
8
Does the damper close correctly?
9
Does the damper open correctly?
10
Do you have any concerns about the
installation?
11
Refit access door/s securely
If any of questions 1 - 9 is answered 'no', or if the answer to
question 10 is 'yes', please see troubleshooting overleaf.
Installation guide: NCA Series 400 hand operated single blade leakage rated fire damper
Operation and maintenance manual
Page 1 of 3 - Issue A - 03/03/2022
NCA Series 400H hand operated single blade leakage rated fire damper
68°C (red bulb in link) or 93°C (green bulb in link)
Notes
The damper handle should be parallel with the damper body, indicating the
damper is open
Using a pozi-drive screwdriver, ensure the machine screw inside the spindle
cap is secure
Both sides of the damper blade should be easily accessible
The damper blade should be in the fully open position.
Gently try to move the blade by hand, it should not rotate.
Ensure there is nothing present which is obstructing or could obstruct the
damper blade operating
Thermal links must be cleaned with care and if damaged or heavily soiled
must be replaced
Caution - Thermal links are fragile
Use a damp cloth, brush or vacuum cleaner to remove any dirt and debris.
If damaged or corroded dampers must be replaced
Caution - Blade sealing fabric is sharp, PPE should be used
Pull the test handle on the external mechanism, the damper should close
Rotate the setting handle 90° anti-clockwise until the underside of the handle
latches onto the thermal link
Is there anything that does not look correct, do you have any doubts etc.?
N/A
Yes/No
N/A
N/A
www.h-v-c.com
Need help?
Do you have a question about the NCA Series and is the answer not in the manual?
Questions and answers