mercor mcr OMEGA pro Technical Manual

Power and control panel

Advertisement

Quick Links

mcr OMEGA pro
Centrala Sterująco-Zasilająca
ul. Grzegorza z Sanoka 2
80-408 Gdańsk
tel. (58) 341 42 45
tel./fax (58) 341 39 85
TECHNICAL MANUAL
Power and Control Panel
mcr OMEGA pro
mcr OMEGA pro & mcr OMEGA proF Power Supply Unit
mcr OMEGA pro revision 06.03.20.3
FIRE VENTILATION SYSTEMS
_

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the mcr OMEGA pro and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for mercor mcr OMEGA pro

  • Page 1 Grzegorza z Sanoka 2 80-408 Gdańsk tel. (58) 341 42 45 tel./fax (58) 341 39 85 TECHNICAL MANUAL Power and Control Panel mcr OMEGA pro mcr OMEGA pro & mcr OMEGA proF Power Supply Unit mcr OMEGA pro revision 06.03.20.3 FIRE VENTILATION SYSTEMS...
  • Page 2: Table Of Contents

    OMEGA pro Power and Control Panel CONTENTS INTRODUCTION ..........................3 INTENDED USE..........................3 DESIGN AND OPERATING PRINCIPLE..................5 3.1. ENCLOSURE ..........................5 3.1.1. INTERNAL TEMPERATURE CONTROL ................6 3.2. MAINS POWER SUPPLY ......................7 3.3. AUTOMATIC TRANSFER SWITCHING MODULE (ATS) ............. 7 3.4.
  • Page 3: Introduction

    This Technical Manual is addressed to the operators of the mcr OMEGA pro modular Power and Control Panels for operation of fire ventilation systems and the mcr OMEGA pro / mcr OMEGA proF Power Supply Units for fire alarm systems and smoke and heat control systems. This document is intended to provide guidelines on the application, design, commissioning and operation of these products.
  • Page 4 The mcr OMEGA pro Power and Control Panel features an integrated fire equipment power supply unit type mcr OMEGA pro or mcr OMEGA prof (with load transfer switching). The power section of the mcr OMEGA pro Power and Control Panel meets the standard EN 12101-10:2005+AC:2007 "Smoke and heat control systems –...
  • Page 5: Design And Operating Principle

    2) A mains power supply unit and surge protection units (optional). 3) Dedicated microchip-based MMS monitoring and control modules. 4) The mcr OMEGA pro Power Supply Unit, which may contain the following, depending on the actual version: a. A 24 VDC power adapter for microchip systems and fire protection devices;...
  • Page 6: Internal Temperature Control

    Hence, the cable glands can be installed on the top, the bottom or the sides of the Power and Control Panel. The mcr OMEGA pro Power and Control Panel enclosure may feature optional single or toggle switches for manual control of the interfaced devices, and an emergency stop device switch.
  • Page 7: Mains Power Supply

    Panel and coupled directly to the main power switch which is used to isolate the Power and Control Panel from live voltage for e.g. servicing. The mcr OMEGA pro Power and Control Panel requires uninterruptible (secure or redundant) power supply which shall be provided from a separate fire power supply section of the building's main switchboard to guarantee continued operation, even in the event of a fire.
  • Page 8: Electrical Protections Of Connected Devices

    Power and Control Panel 3.4. ELECTRICAL PROTECTIONS OF CONNECTED DEVICES All devices interfaced with the mcr OMEGA pro Power and Control Panel and fed by the mcr OMEGA pro/proF Power Supply Unit are protected against shorting and/or overload. The specific protection types installed depend on the duty and specifications of the interfaced devices.
  • Page 9: Mcr Mms/Evco Monitoring And Control Modules

    Power and Control Panel system. The number of the mcr MMS modules depends on the installation system specifications. The mcr OMEGA pro have 3 types of monitoring and control modules that can be used to develop the control system.
  • Page 10 OMEGA pro Power and Control Panel A flashing LED indicator signals a timeout has occured for monitoring inputs (e.g. limit switch signals). For algorithm inputs (e.g. FAS signals, venting) the flashing LED signals the active algorithm. The mrc MMS module controller identifies the specific input statuses with resistance measurement values.
  • Page 11: Optional Monitoring And Control Modules Mcr Mms 63

    OMEGA pro Power and Control Panel 3.6.2. OPTIONAL MONITORING AND CONTROL MODULES mcr MMS 63 The mcr MMS 63 module has 6 digital inputs and 3 relay outputs. Each of them can feature one of the available extension modules by linking them together via dedicated communication tapes connected to...
  • Page 12: Optional Monitoring And Control Modules Evco C-Pro

    OPTIONAL MONITORING AND CONTROL MODULES EVCO C-pro In mcr OMEGA pro units it is possible to install EVCO C-pro 3 PLC devices in two versions: kilo + and node kilo +. According to the driver version, they have: 9 or 13 digital inputs 9 or 10 analog inputs...
  • Page 13: Mcr Omega Pro Fire Protection Devices Power Supply Unit

    3.7. mcr OMEGA pro FIRE PROTECTION DEVICES POWER SUPPLY UNIT The mcr OMEGA pro Power and Control Panel for operation of the fire protection devices in heat and smoke control systems features a power supply unit that complies with: EN 12101-10:2005+AC:2007 and EN 54-4:1997+AC:1999+A1:2002+A2:2006.
  • Page 14: Fan Starting Contactor Systems

    OMEGA pro Power and Control Panel 3.7.2. FAN STARTING CONTACTOR SYSTEMS W centralach mcr OMEGA pro do rozruchu wentylatorów i silników stosowane są klasyczne metody stycznikowe:  DOL (Direct On Line): The interfaced motor (e.g. of a fan) is connected directly to the mains by switching the contactor coil, switching over the contactor contacts, and feeding the rated voltage to the motor input terminals.
  • Page 15: Softstarters

    Frequency converters, or inverters, help control the operation of electric motors whenever speed or torque must be controlled. The inverters used in the mcr OMEGA pro Power and Control Panels control the air fan output. Depending on the application, the air fans can be controlled in steps with dry contact outputs of external systems, as used for ventilating garage rooms, or variable-controlled by 0–10 V or...
  • Page 16: Kli Line Continuity Monitoring Module

    Power and Control Panel 3.8. KLI LINE CONTINUITY MONITORING MODULE The mcr OMEGA pro can be enabled to monitor power supply line continuity of the interfaced devices to detect breaks or shorting. Damper actuators are monitored based on the feedback from their position limit switches, while the fan motors are controlled with a KLI module installed in the Power and Control Panel.
  • Page 17: Technical Specifications

    OMEGA pro Power and Control Panel 4. TECHNICAL SPECIFICATIONS __________________________________________ TECHNICAL PARAMETERS Enclosure protection rating IP 54 lub IP 55 -25ºC ÷ 75ºC Working temperature range Environment Class Primary power: supply voltage 230/400/690 VAC (-15%, +10%) Max. mains current draw...
  • Page 18: Installation And Connections

    The outfeed bays and protections for the mcr OMEGA pro shall be properly labelled (with red colour and the panel number, or with a text sign). It is recommended to have one mains current breaker connected per each Power and Control Panel.
  • Page 19 Fig. 14.Return spring actuator diagram, spring actuator opening. . closing . Double action electric actuator, e.g. Double action electric actuator e.g. BELIMO type BE BELIMO type BE For MERCOR brand dampers only. For MERCOR brand dampers only. Cabinet Cabinet T-Box T-Box Damper Damper Fig.
  • Page 20 OMEGA pro Power and Control Panel ACTUATOR GROUP WIRING Return-spring actuators, e.g. BELIMO type BF, BFG, BFL or BFN (spring-action closing movement) NO or NC Cabinet T-Box T-Box T-Box Damper Damper Damper Fig. 18. Wiring diagram: return spring actuators, spring closing, NO or NC.
  • Page 21 OMEGA pro Power and Control Panel Double-action electric actuators, e.g. BELIMO type BE NO. For MERCOR brand dampers only. Cabinet T-Box T-Box T-Box Damper Damper Damper Fig. 20. Wiring diagram: electric actuators NO. CAUTION: Connect all S1 and S3 contacts in parallel.
  • Page 22 (monitoring position) shall be open in the monitoring position. CONNECTIONS OF FIRE ALARM SYSTEM SIGNALS The mcr OMEGA pro requires connection with the fire alarm system via dry NC contact relay (this contact status is in the monitoring mode). The specified contact type shall be bridged with a 10 kΩ...
  • Page 23: Fire Protection Device Conection Cables

    The table below lists recommendations for cable types for connection of control actuators (i.e. detectors, dampers, fans, etc.) to the mcr OMEGA pro. This list has been developed in line with Polish SITP WP- 02:2010 Guidelines, and the Polish Regulation of the Ministry of Infrastructure concerning the Technical Requirements for Buildings and Locations Thereof (consolidated text of 17 July 2015).
  • Page 24: Operation

    Due to the modular design of the mcr OMEGA pro Power and Control Panel, the operating instructions and requirements are customised to the specific application site, fire scenario, fire protection requirements and user requirements.
  • Page 25: Testing

    7. TESTING ____________________________________________________________________ The mcr OMEGA pro features a function of testing the fire algorithms. Inside the Power and Control Panel are TEST switches, each for one fire algorithm programmed. The Power and Control Panel must be in the monitoring mode to test a fire algorithm. Start the test by operating the TEST switch of choice and monitor the operation of the controller and the interfaced equipment.
  • Page 26: Servicing And Maintenance

    21 days from serving the written warranty claim with the proof of purchase or sales contract, subject to Item 6. „MERCOR” S.A. has the right to extend the time of repair if the defect removal is complicated or requires purchasing custom components or spare parts.
  • Page 27 The equipment and/or parts thereof with removed or damaged nameplate (rating plate) and/or warranty seals. Submit each warranty claim to „MERCOR” S.A. in 7 days from the date of discovery of a warranty eligible defect. Submit warranty claims by calling +48 58 341 42 45, by fax at +48 58 341 39 85, by e-mail at reklamacje@mercor.com.pl or by mail at the following address: „MERCOR”...
  • Page 28 OMEGA pro Power and Control Panel ul. Grzegorza z Sanoka 2 80-408 Gdańsk, Poland tel. (58) 341 42 45 tel./fax (58) 341 39 85 „MERCOR” S.A. – 28/28 The company reserves the right to modify and amend this document without notice.