Flat Sensato v2 KNX Humidity and Temperature sensor for flush mounting ZSFSENV2 Application Program Version: [1.3] User Manual Version: [1.3]_a www.zennio.com...
Flat Sensato v2 1 INTRODUCTION 1.1 FLAT SENSATO V2 Flat Sensato v2 is a sensor with a flat design to measure ambient temperature, relative humidity and to calculate dew point for the sending of humidity, temperature and condensation. The most outstanding features and functions of the device are: Measurement of dry air temperature.
The Programming LED (4) will then light in red. On the contrary, if this button is held while the device gets connected to the bus, Flat Sensato v2 will enter the safe mode. In such case, the programming LED will blink in red colour.
Flat Sensato v2 2 CONFIGURATION After importing the corresponding database in ETS and adding the device into the topology of the desired project, the configuration process begins by entering the Parameters tab of the device. 2.1 GENERAL From the “General” tab enabling additional functions available for the device is possible.
Page 6
Flat Sensato v2 (“[Heartbeat]Object to Send ‘1’”) that will be sent periodically with value “1” to notify that the device is still working (still alive). Figure 3. Heartbeat (Periodical Alive Notification) Note: The first sending after download or bus failure takes place with a delay of up to 255 seconds, to prevent bus overload.
Flat Sensato v2 2.2 HUMIDITY Flat Sensato v2 is capable of measure and monitor humidity measurements, as well as send these values to the bus and report high / low humidity situations. To that end, it is necessary to configure a set of parameters.
Flat Sensato v2 2.3 INTERNAL TEMPERATURE SENSOR Flat Sensato v2 is capable of measure and monitor temperature measurements, as well as send these values to the bus and report high / low temperature situations. To that end, it is necessary to configure a set of parameters.
Page 9
Flat Sensato v2 ➢ [Overheating]: overheating protection is required. Two extra parameters will come up: • Overheating Temp. [-30…40…125] [ºC]: maximum temperature permitted. Temperature readings greater than this will be considered overheat, and therefore a “1” will be periodically sent through object “[Internal Temp.
Page 10
Flat Sensato v2 • Hysteresis. The three of them are analogous to those already explained separately. https://www.zennio.com Technical Support: https://support.zennio.com...
2.4 NOTIFICATION LED 2.4.1 CONFIGURATION Flat Sensato v2 has a LED to notify, through colours, the ranges of the current humidity values. The colour to notify the humidity ranges can be two (green and yellow) or three (green, yellow and red).
Page 12
Flat Sensato v2 Figure 6. Notification LED – Green, Yellow and Red The parameters available in this tab are: Colours Shown [Green and Yellow/Green, Yellow and Red]: allows selecting whether the notification LED comprises two or three colours. Red / Yellow / Green: humidity value (0-100%) from which the notification LED will display the indicated colour.
Zennio website (www.zennio.com). 2.5.3 MOTION DETECTOR It is possible to connect motion detectors from Zennio to the input ports of Flat Sensato Please refer to the “Motion Detector” user manual, available in the Flat Sensato v2 product section, at the Zennio website (www.zennio.com).
KNX bus, which can be done every time the function is executed, periodically or only when the result differs from the last one. Please refer to the “Logic Functions” user manual (available in the Flat Sensato v2 product section at the Zennio homepage, www.zennio.com) for detailed information about the functionality and the configuration of the related parameters.
Flat Sensato v2 ANNEX I. COMMUNICATION OBJECTS “Functional range” shows the values that, with independence of any other values permitted by the bus according to the object size, may be of any use or have a particular meaning because of the specifications or restrictions from both the KNX standard or the application program itself.
Page 16
Flat Sensato v2 Protection 1 Bit C R - T - DPT_Switch [Ix] Presence State (Binary) Binary Value 22, 51 1 Bit C R - T - DPT_Start [Ix] Presence: Slave Output 1 = Motion Detected Binary Value to Trigger the...
Page 17
Flat Sensato v2 0x8 (Stop) 0xD (Inc. by 100%) 0xF (Inc. by 1%) 0x0 (Stop) 0x1 (Dec. by 100%) 0x7 (Dec. by 1%) 4 Bit C - - T - DPT_Control_Dimming [Ix] [Short Press] Darker Decrease Brightness 0x8 (Stop) 0xD (Inc. by 100%) 0xF (Inc.
Page 18
Flat Sensato v2 1 Bit C - - T - DPT_UpDown [Ix] [Long Press] Move Down Shutter Sending of 1 (Down) [Ix] [Long Press] Move Up/Down 1 Bit C - - T - DPT_UpDown Switching 0/1 (Up/Down) Shutter 1 Bit...
Page 19
Flat Sensato v2 (Percentage) [Ix] [Long Press] Constant Value 1 Byte C - - T - DPT_Value_1_Ucount 0 - 255 0 - 255 (Integer) 79, 85 1 Bit C - - T - DPT_Trigger [Ix] [Long Press/Release] Stop Shutter Release -> Stop Shutter...
Page 20