Technical documentation U-19
AP11-34-x-...
AP11-35-x-...
AP11-36-x-...
www.apoelmos.cz
ISO 9001

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the AP11-34 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for APOELMOS AP11-34 Series

  • Page 1 PANELMETER AP11 Technical documentation U-19 AP11-34-x-... AP11-35-x-... AP11-36-x-... www.apoelmos.cz ISO 9001...
  • Page 2 November 2018, TD-U-19-12 A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 3: Table Of Contents

    Configuration of bargraph - BAR-1 up to BAR 4 ............37 9.2.8 Configuration of display - DIS-1 up to DIS-4 ............38 A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 4 ..................42 11 ES Declaration of conformity ..............43 12 Quality certificate ..................44 13 Warranty conditions ................. 44 A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 5: Introduction

    PC, as limit switches, simp- le two-state regulator, apparatuses for failure signalling or as mathematical units. A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 6: Ordering Code

    Example of order: AP 11 - - 2 - 1 - 5 - 1 - 4 - A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 7: Technical Data

    0 – 10 V, loading resistance min. 10 kΩ Communication RS485 without galvanic separation or with galvanic separation, two way communication RS232 without galvanic separation A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 8 Electromagnetic compatibility ČSN EN 61326 Seismic resistibility ČSN IEC 980: 1993, čl. 6 Electric safety ČSN EN 61010-1: 2003 A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 9: Panelmeter Description

    Indicators OUT 1 to OUT 4 indicates state of individual outputs in the following manner: indicator flashing – output switched, indicator is not flashing – output is off. A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 10: Dimensions Of Panelmeter And Assembly Opening

    Dimensions for power supply 18 - 36 VDC / 18 - 36 VAC, 50 Hz (fig. 3b) fig. 3b A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 11: Connection

    41 to 46 – relay output connectors 51 to 56 - relay output connectors 61 to 63 – power supply A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 12: Connection To Feeding Voltage

    Feeding voltage ge 80 - 253 VAC, 50 Hz 18 - 36 VDC 18 - 36 VAC fig. 5 A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 13: Connection Of Input Signals

    During apparatus configuration select type of input signal in menu SEN-1, SEN-4 parameter TYP !!! A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 14: Passive Current Signal (Input Code 34)

    Start of range define in MENU with function STRS, and ending of the range with function ENDS. A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 15: Voltage Signal (Input Code 35)

    Then setup range of measurement. Start of range define in MENU with func- tion STRS, and ending of the range with function ENDS. A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 16: Active Current Signal (Inlet Code 36)

    . Then setup range of measurement. Start of range define in MENU with function STRS, and ending of the range with function ENDS. A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 17: Analogue Output

    2-10 V 4-20 10-0 V 20-0 10-2 V 20-4 fig. 14 fig. 13 With 2 communication lines connected, or RS2332 A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 18: Block Diagram Of Analogue Output Function

    SUBIN: Is defined as difference of input signals on inputs 1 and 2. I.e. input 1 - input 2 ADDIN: Is defined as sum of input signals on inputs 1 and 2. A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 19: Communication

    Communication line RS485 Diagram of communication line RS232 connection to PC (connector Canon 9 pin) fig. 19 A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 20 (interconnect connectors 31, 32 and 33, 34 for line 1, connectors 35, 36 and 37, 38 for line 2) A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 21: Connecting Of Contact Outputs

    Unplug panelmeter from power supply. Keep key SET pressed and connect the apparatus to power supply. Keep the key pressed until sign RESET appears on display. Default parameters are restored after reset! A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 22: Limit Switch Functions

    - Zero regulation deviation cannot be achieved - Measured value oscillates in characteristic manner around required value fig. 23b A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 23: Panelmeter Functions And Limit Switch Setting

    1) Limits of limit switches in mode STATE are set in absolute values. 2) Limits of limit switches in mode SHIFT are set as deviations from required value SP. A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 24 MENU key and enter setting mode and assign state ON or OF to respective input. Confirm the setting by pressing SET. Function of limit switch is shown with characteristics on Fig. 25, 26, 27, 28. A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 25: Functional Characteristics Of Limit Switches

    RELE menu to ON. Set deactivating of limit switch in menu HYST to value 2. Confirm and leave the setting by pressing key SET. A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 26 HYST to value 2. Confirm and leave the setting by pressing key SET. A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 27: Display Setting

    When coloured display is required, this option has to be indicated with panelmeter order. On single-coloured display menu DIS- (x) is not displayed. A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 28: Bargraph

    If any key is not pressed in configuration mode during the period of 1 minute regulator switches by means of TIME OUT function to working mode without saving of selected pa- rameters! A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 29: Simplified Block Diagram Of Panelmeter Menu

    FUNCTIONS OF PANELMETER MENU Simplified block diagram of panelmeter menu A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 30: Configuration Of Desired Value -Sp

    Press SET key to return to configuration menu. Press SET key again to return to working menu and to save selected parameters. Beware of TIME OUT function! A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 31: Configuration Of Limit Switches - Ala-1 Up To Ala 4

    Press SET to return to submenu of required function. Press key SET again to return to configuration menu. Press SET key again to return to working menu and to save selected parameters. A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 32: Configuration Of Sensor - Sen-1 Up To Sen-4

    Voltage signal 0 - 10V 0 - 10 fig. 11 Without sensor -no- deactivates sensor and zero is -no- displayed A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 33 Generally it is possible to compensate any inaccuracy of measurement with offset. If it is not necessary to set any offset or compensation, set the value to 0. A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 34: Configuration Of Analogue Output - Daco

    That means that start STR has to be set to 100, END has to be set to 200 and OUT 0-20. A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 35: Configuration Of Output State In Breakdown Condition -Error

    Icon displays only options that are connected (E.g.: If only one relay module and analogue output is con- nected, items ERR-1,ERR-2,ERR-A are displayed. A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 36: Configuration Of Parameter -Ostat

    ADDR Setting of panelmeter address (active only when communication connected) A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 37: Configuration Of Bargraph - Bar-1 Up To Bar 4

    LEDs start flashing. For detail description of setting refer to page 28, chapter „Bargraph“. A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 38: Configuration Of Display - Dis-1 Up To Dis-4

    Setting of display brightness (25%, 50%, 75%, 100%) For detail description of setting refer to page 27, chapter „Display setting“. A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 39 ON, OFF tral-2 Signalling of limit switch out- ON, OFF tral-3 Signalling of limit switch out- ON, OFF tral-4 A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 40 2 Setting of display brightness 25, 50, 75, 100 light Setting of display range STATE, SHIFT STATE mode A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 41 Keyboard lock MEN-1, MEN-2, menu (interconnect terminals 17, MEN-3, MEN-4 MEN-1 Setting of regulator address 1 to 126 A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 42 Software available on www.apoelmos.cz. Software / Hardware requirements and installation: -> TD-U-19-19 (PAP Software) Communication protocol -> TD-U-19-20 (Communication protocol) A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 43 Place of issue: Nová Paka Name: Ing. Libor Lukeš Date of issue: 22.7.2014 Position: Company director Stamp: ........Signature: ........ A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...
  • Page 44 Guarantee and after guarantee service is provided exclusively by A.P.O. – ELMOS. Date of purchase: .......... Signature: ..........Stamp A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01 tel. +420 493 504 261, fax: +420 493 504 257, e-mail: apo@apoelmos.cz...

This manual is also suitable for:

Ap11-35 seriesAp11-36 series