KNX Communication
for ETAtouch control system
Operating instructions

Advertisement

loading

Summary of Contents for eta KNX

  • Page 1 2020-05-25 0000000488 V.001 X.49.0 939112-001 KNX Communication for ETAtouch control system Operating instructions...
  • Page 2 ETA Heiztechnik Gewerbepark 1 A-4716 Hofkirchen an der Trattnach Tel: +43 (0) 7734 / 22 88 -0 Fax: +43 (0) 7734 / 22 88 -22 info@eta.co.at www.eta.co.at...
  • Page 3: General Information

    General information General information Copyright DANGER! All contents of this document are property of ETA On non-compliance with this safety instruction, there is Heiztechnik GmbH and are protected by copyright. a risk of major physical injury. Any reproduction, transfer to third parties or use for other purposes is prohibited without written permission from the owner.
  • Page 4 Chapter "Appendix". The assembly and installation may be performed by specialist personnel with the corresponding Plug the KNX USB interface stick into a free USB port qualifications only. on the ETAtouch control panel. Use the supplied USB extension for this.
  • Page 5 Fig. 2-5: Overview of the KNX interface 4. The [Programming button] button must be pressed to allow the KNX USB interface stick to be identified. An address can then be assigned to the USB interface stick using the "ETS" programming software.
  • Page 6: Adjustable Parameters

    Adjustable parameters Adjustable parameters Parameters from the ETAtouch control system for communication via the KNX bus The following applies to all parameters: If a value greater than 0 is set at [Transmit cyclical?], the ETAtouch control system sends the values at the set interval. The value "0" deactivates the regular transmission of the values. It can also be set for all parameters if there is a change in value (e.g., temperature change of 1°C), regardless of whether...
  • Page 7 Adjustable parameters Boiler (maximum 2) Designation Description Flag Boiler temp. Transmits the temperature of the boiler. 9.001 C, R, T Flue gas temp. Transmits the exhaust temperature. 9.001 C, R, T Transmits the residual oxygen content of the flue Residual O2 5.001 C, R, T gas.
  • Page 8 Transmits the feed temperature of the heating Flow temp. circuit. Communication objects: Transmits the room temperature from an ETA Actual room temp. 9.001 C, R, T room sensor to the ETAtouch control system. C, R, W, Target room temp.
  • Page 9 Adjustable parameters Heating circuit (maximum 8) Designation Description Flag Switches the heating circuit to reduced-tempera- C, R, W, Set-back button ture mode (lower temperature and outside the 1.001 set heating times). C, R, W, On/off button For switching the heating circuit on and off. 1.001 Ends the current operation and switches the heating circuit to heating mode until the next set...
  • Page 10 This object must not be used for on-off ac- tuators. For on-off actuators, use the "Valve Valve value 2 5.001 C, R, T Status" object instead. The second valve is only required if a room is supplied by two heating circuits. www.eta.co.at...
  • Page 11 Valve state Transmits the status (open/closed) of the control 1.003 C, R, T valve which is controlled via a heating actuator (via KNX bus). Valve state 2 1.003 C, R, T The second valve is only required if a room is supplied by two heating circuits.
  • Page 12 To switch the burner on and off in ready mode. C, R, W, The ETAtouch control system can only re- On/off button 1.001 quest this if the burner is switched on (i.e., ready for operation). State Transmits the operating condition. 16.001 C, R, T www.eta.co.at...
  • Page 13 Display of the operating condition of the heat Producer ready 1.011 C, R, T producer (e.g., boiler) for the heat consumer. Transmission of a heat request via the KNX bus C, R, W, Demand from bus to the ETAtouch control system (on/off or yes/ 1.003 no).
  • Page 14 Description Flag Specification of the required temperature for the C, R, W, Temp. demand from bus heat consumer using the KNX actuator to the 9.001 ETAtouch control system. C, R, W, On/off button For switching the heat consumer on and off.
  • Page 15 Transmits the outside temperature from the tem- Outside temp. 9.001 C, R, T perature sensor to the ETAtouch control system. Transmission of a fault message from a KNX ac- External fault message from bus 1.001 C, W, T tuator to the ETAtouch control system.
  • Page 16 Appendix Appendix www.eta.co.at...
  • Page 17 Bei fehlendem USB-Anschluss ist das Gerät ohne Funk- Schnittstellen“ ausgewählt und konfiguriert werden. tion. Nachdem das KNX USB Interface an den PC und den KNX Bus angeschlossen wurde, erscheint automatisch in der ETS im KNX Programmiermodus Menüpunkt „Bus“ unter „gefundene Schnittstellen“.
  • Page 18 Die KNX USB Schnittstelle unterstützt den Busmonitormodus, der auch mit der ETS verwendet werden. Im Busmonitormodus Die KNX USB Kommunikation basiert auf dem HID/cEMI- wird der gesamte Verkehr auf dem KNX-Bus mit ACK-, NACK- Protokoll entsprechend der KNX-Spezifikation. Um die KNX USB und BUSY-Zeichen angezeigt.
  • Page 19 Appendix WARNUNG ƒ Das Gerät darf nur von einer zugelassenen Elektrofachkraft installiert und in Betrieb ge- nommen werden. ƒ Die geltenden Sicherheits- und Unfall- verhütungsvorschriften sind zu beachten. ƒ Das Gerät darf nicht geöffnet werden. ƒ Bei der Planung und Errichtung von elektri- schen Anlagen sind die einschlägigen Richtli- nien, Vorschriften und Bestimmungen des je- weiligen Landes zu beachten.
  • Page 20 DOWNLOAD www.eta.co.at...