thermofin TCS.2 Series Operating Manual

thermofin TCS.2 Series Operating Manual

Control system 2nd generation
Table of Contents

Advertisement

Quick Links

OPERATING MANUAL
Controller TCS.2
thermofin
control system 2
generation
®
nd
(from TCS.2 software version TCS.2_A06_v20201125)
Operating manual - translation into English © thermofin GmbH

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TCS.2 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for thermofin TCS.2 Series

  • Page 1 OPERATING MANUAL Controller TCS.2 thermofin control system 2 generation ® (from TCS.2 software version TCS.2_A06_v20201125) Operating manual - translation into English © thermofin GmbH...
  • Page 2: Tcs.2 Series - Thermofin ® Control System

    If problems arise in connection with the installation and/or operation of the device that are not immediately. Further described in this manual, the operator/installer is obliged to contact thermofin ® installation and/or operation of the device is not permitted until the facts have been fully clarified.
  • Page 3: Table Of Contents

    Low load regulation control ............... 36 Spray pump control .................. 37 Medium pump control ................39 Inputs / Outputs................... 40 Digital IN basic unit ................... 40 Digital OUT basic unit ................42 Operating manual - translation into English © thermofin GmbH...
  • Page 4 Analogue IN basic unit ................77 Analogue OUT basic unit ................78 Fans – Auto/Hand ..................78 IN / OUT extensions ................. 80 Counter ......................81 Alarms ......................82 Fan Operating data / Status ..............83 Operating manual - translation into English © thermofin GmbH...
  • Page 5 Fresh water meter .................. 117 I/O valves settings ..................118 BUS parameter valves ................119 Adjustments in the Main menu  Additional functions  Wet menu Spray ..................... 120 Winter operation/Summer operation ............121 Operating manual - translation into English © thermofin GmbH...
  • Page 6: Nd Generation Page

    ....................149 Adjustments in Main menu  Additional functions  Wet mode ..149 Insulating / penthouse cooler ............ 149 Adjustments in Device settings  Additional functions  Humidification system ....................149 Operating manual - translation into English © thermofin GmbH...
  • Page 7: Nd Generation Page

    Flaps messages – Error code K…............153 Measured values messages – Error code M........... 154 Signals external messages – Error code S..........158 Valve messages – Error code V............... 160 Closing remarks ................. 162 Operating manual - translation into English © thermofin GmbH...
  • Page 8: General Information

    The split systems are mainly used for fan drives in which the power section is already integrated in the motor housing or the drive concept and the like provides a separate inverter or voltage regulator. Operating manual - translation into English © thermofin GmbH...
  • Page 9: Scope Of Application

    Without an appropriately classified control cabinet, control units of the TCS series may only be operated in dry, weather-protected and properly air-conditioned rooms. Control cabinets from thermofin® company meet all of the important criteria for outdoor installation and therefore also enable trouble-free operation with a built-in TCS.
  • Page 10: Circuit Diagram Tcs.2

    15.11.2020 – Version 1.1 TCS.2 series – Page: 10/162 thermofin control system 2 generation ® Circuit diagram TCS.2 Picture 1 Standard assignment, it may vary. Exemplary assignment of the inputs and outputs. Operating manual - translation into English © thermofin GmbH...
  • Page 11: Structure / Navigation

    Back Jump one menu level back. Forward Jump one menu level forward. Confirm The current entry or error message is acknowledged. Confirm all All currently pending error messages are acknowledged. Operating manual - translation into English © thermofin GmbH...
  • Page 12 The Modbus fan is stopped with the STOP button. This is a prerequisite for starting the fan parametrisation process. After exiting the parametrisation menu, the Modbus is automatically restarted. Write parameters to fan All preselected parameters and addresses are loaded into the respective Modbus fan(s). Operating manual - translation into English © thermofin GmbH...
  • Page 13 The limit values (switch-on and switch-off conditions for the mat moistening) for the “water-saving” or “power-saving” mode are set here. Cooling mat system Device-specific settings for all devices in which the supply air is pre-cooled using mats (adiabatic pads). Operating manual - translation into English © thermofin GmbH...
  • Page 14 Neutral position (with % indication) All parameters for switching the All parameters for switching the humidification on and off are set to humidification on and off are set to “energy-saving” “water-saving” Operating manual - translation into English © thermofin GmbH...
  • Page 15: Menu Structure

    *** only visible if a thermofin® adiabatic pad device is selected There are four main function buttons in the right half of the display of the start screen. These are described in a separate chapter.
  • Page 16 By pressing the yellow highlighted information window, the user gets directly to the corresponding, still activated, output. Operating manual - translation into English © thermofin GmbH...
  • Page 17 By pressing the “country flag” directly, the user gets to a language selection menu. The user can currently choose between the following languages: German  English  French  Spanish  Operating manual - translation into English © thermofin GmbH...
  • Page 18 If the demand for the analogue inputs increases to over 4 (these are available as standard  on the basic unit), the humidity sensor is automatically assigned to an analogue IN CAN extension (see chapter C) „Assignment of possible analogue I/O extensions“). Operating manual - translation into English © thermofin GmbH...
  • Page 19: Passwords

    Picture 5  Hold down the “DELETE PASSPORD” button for 5 seconds (Picture 5) Then the following window opens. If the system password has already been entered, this step is skipped (22a) Operating manual - translation into English © thermofin GmbH...
  • Page 20  The message “Customer password saved” confirm the entry with the tick appears (Picture 9) (Picture 8)  After this process, the process can be repeated using the currently assigned password (Picture 9) Operating manual - translation into English © thermofin GmbH...
  • Page 21: Change (Edit) Values

    OK or cancelled with ESC. The minimum and maximum values to be entered are displayed above the keypad (see Picture 11). Operating manual - translation into English © thermofin GmbH...
  • Page 22: Info / Status

     FC: Release active, Free Cooling (Setpoint changeover active, see chapter 4.2.2: Control -> Setpoint changeover)  HR: Release active, Heat Recovery - only with condensers! (Setpoint changeover active, see chapter 4.2.2: Control -> Setpoint changeover) Operating manual - translation into English © thermofin GmbH...
  • Page 23: Device Settings

    Picture 15 The device settings, including its submenus, are exited using the back or HOME button. The description of the marked submenus is given below. The framed numbers indicate the chapter number. Operating manual - translation into English © thermofin GmbH...
  • Page 24: Heat Exchanger System

    12. Dry cooler sprayed, two circuits, separate control 13. Condenser adiabatic pads 14. Condenser adiabatic pads, two circuits, separate control 15. Dry cooler adiabatic pads 16. Dry cooler adiabatic pads, two circuits, separate control Operating manual - translation into English © thermofin GmbH...
  • Page 25 Because no water is applied directly to the heat exchanger, but only pre-cooled air, the possible switch-on time of the humidification is significantly longer than with the sprayed systems. Operating manual - translation into English © thermofin GmbH...
  • Page 26: Selection Of Device Design

    Attention! All previously made parameter adjustments and customer settings are lost. A prior comparison of the set parameters with the parameter list on the circuit diagram is essential! Operating manual - translation into English © thermofin GmbH...
  • Page 27: Save / Load Device Settings

    The saved data is now loaded from drive B: back into drive A: If the process is to be cancelled, this can be done at any time with the “Undo” button. Operating manual - translation into English © thermofin GmbH...
  • Page 28: Control

    HR - heat recovery) is applied to the controller. * Factory setting ** These settings are typically used for function tests and commissioning. If, for example, no external release has yet been sent from the BCS. Operating manual - translation into English © thermofin GmbH...
  • Page 29: Setpoint Changeover Control

    Reading HR1 (heat recovery 1) active: Register 164, bit 4 (Bool), (register value 16) Reading HR2 (heat recovery 2) active: Register 164, bit 5 (Bool), (register value 32) Reading HP1 (heat pump operation 1) active: Operating manual - translation into English © thermofin GmbH...
  • Page 30: Night Time Reduction Control

     Via bus Options: The following parameters apply to direct communication via MODBUS: Writing: Register 1, bit 2 (Bool), (register value 4)  Off Function deactivated. * Factory setting Operating manual - translation into English © thermofin GmbH...
  • Page 31: Setpoint Shift Control

    -25,0°C to +25,0°C or -450 to +450  for -45,0°F to +45,0°F) Circuit 2: Register 5 (INT), (register value: -250 to 250 -25,0°C to +25,0°C or -450 to +450  for -45,0°F to +45,0°F) * Factory setting Operating manual - translation into English © thermofin GmbH...
  • Page 32: Slave Control Value Control

    Register 6 (INT), (register value: 0 to 1000  0.0 to 100.0 %) Circuit 2: Register 7 (INT), (register value: 0 to 1000  0.0 to 100.0 %) * Factory setting Operating manual - translation into English © thermofin GmbH...
  • Page 33: Winter Operation Control

    “4.5 „BMS (Building management system) bus system”).  Via bus The following parameters apply to direct communication via MODBUS: Register 1, bit 13 (Bool), (register value 8192)  Off Function deactivated. * Factory setting Operating manual - translation into English © thermofin GmbH...
  • Page 34: Hygienic Circuit Control

    “4.5 „BMS (Building management system) bus system”].  Via bus The following parameters apply to direct communication via MODBUS: Register 1, bit 14 (Bool), (register value 16384)  Off Function deactivated. * Factory setting Operating manual - translation into English © thermofin GmbH...
  • Page 35: External Master Mode Control

    + 24 V DC at terminal X7.5 (DI-5) “Reversion of rotation” Options:  Via terminal Device settings  Inputs / Outputs  “Digital IN basic unit” see also chapter 1.4 (Circuit diagram TCS.2) Operating manual - translation into English © thermofin GmbH...
  • Page 36: Low Load Regulation Control

    “4.5 „BMS (Building management system) bus system”].  Via bus The following parameters apply to direct communication via MODBUS: Writing: Register 2 SL control level 1, bit 0 (Bool), (register value Operating manual - translation into English © thermofin GmbH...
  • Page 37: Spray Pump Control

    There is currently no digital input dedicated to activating the spray pump. In case of “internal”,  Via terminal the pump is also switched on via the release (external requirement, DI-1). Operating manual - translation into English © thermofin GmbH...
  • Page 38 Register 2, bit 6 (Bool), (register value 64) Reading (feedback): Spray pump 1 Register 144, bit 12 (Bool), (register value 4096) Spray pump 2 Register 144, bit 13 (Bool), (register value 8192) * Factory setting Operating manual - translation into English © thermofin GmbH...
  • Page 39: Medium Pump Control

    Register 2, bit 8 (Bool), (register value 256) Reading (feedback): Medium pump 1 Register 164, bit 8 (Bool), (register value 256) Medium pump 2 Register 164, bit 9 (Bool), (register value 512) * Factory setting Operating manual - translation into English © thermofin GmbH...
  • Page 40: Inputs / Outputs

     FB defrosting flap closed  Forced opening of valves  Collection tray failure  External master OK (see chap. 4.2.8)  External winter operation (see chap. 4.2.6)  Flow monitor (see chap. C) Operating manual - translation into English © thermofin GmbH...
  • Page 41  External emergency stop  External emergency stop 2 (circuit 2)  Subcooler fan 2  NH monitor  Reversion of rotation (see chap. 5.6.6 “Speed reversion of rotation”)  * Factory setting Operating manual - translation into English © thermofin GmbH...
  • Page 42: Digital Out Basic Unit

    DO – 5  Reversion of rotation active (X7.13)  Drain valve  Vent valve  Inlet valve  Louver flap 1  Defrosting flap start  Fresh air damper closed Operating manual - translation into English © thermofin GmbH...
  • Page 43  Message winter mode  Main contactor = emergency stop  Main contactor 2 = emergency stop (circuit 2)  Oil return solenoid valve  Tray heater  Subcooler fan 2 Operating manual - translation into English © thermofin GmbH...
  • Page 44: Analogue In Basic Unit

    (X4.32)  Setpoint shifting 2 (see chap. 4.2.4)  Speed slave 2 (0-10 V, see chap. 4.2.5)  Current sensor of lift motor 4 (0-10 V)  Humidity sensor (4-20 mA) Operating manual - translation into English © thermofin GmbH...
  • Page 45 TCS.2 series – Page: 45/162 thermofin control system 2 generation ®  Feedback of control valve mat 1  Not used  The factory settings vary depending on the selected device type Operating manual - translation into English © thermofin GmbH...
  • Page 46 For temperature inputs, two associated correction values can be determined using two different measuring points. The characteristic curve is thus adapted to the non-100% linear course of the temperature sensors (see Picture 18). Operating manual - translation into English © thermofin GmbH...
  • Page 47: Analogue Out Basic Unit

     Adiabatic valve 1 (2-10 V)  Adiabatic valve 2 (2-10 V)  Low load level 1, 2-10 V  Wetting pump 1 speed (0-10 V)  Wetting pump 2 speed (0-10 V) Operating manual - translation into English © thermofin GmbH...
  • Page 48  3-way valve, compressor (0-10 V)  Ambient temperature (-50 °C  0 V to +100 °C  10 V)  Not used  The factory settings vary depending on the selected device type Operating manual - translation into English © thermofin GmbH...
  • Page 49: In / Out Extensions

    2 generation ® IN / OUT extensions For devices with an extended range of functions (e.g. thermofin ® adiabatic pad cooler or thermofin ® hybrid cooler), the digital and analogue I/Os from the TCS.2 basic unit are not sufficient. They are then expanded with external I/O modules via the CAN bus.
  • Page 50 See 4.3.5D) „Korrekturwerte “ Picture 23 By pressing the right arrow button, the assignment of the analogue outputs (AO- 03 to 06) and their current value are displayed. Operating manual - translation into English © thermofin GmbH...
  • Page 51 Correction values for standard signals in % Analogue voltage or current inputs (0-10 V, 2-10 V, 0-20 mA, 4-20 mA) are corrected as a percentage. Editable from -5.00 % to 5.00 % Operating manual - translation into English © thermofin GmbH...
  • Page 52: Fans Settings

    70.00 … 140.00 °F Correction value 2: -10.00 … 10.00 dt°C -20.00 … 20.00 dt°F Fans settings Picture 26 4.4.1 4.4.9 4.4.2 4.4.3 4.4.10 4.4.4 4.4.11 4.4.5 4.4.12 4.4.6 4.4.13 4.4.7 4.4.8 4.4.14 Operating manual - translation into English © thermofin GmbH...
  • Page 53: Control Of The Fans

    The data transfer is realized by the TCS wireless wireless system instead of a signal cable. For setting the communication parameters, see chapter 4.5 “BMS (Building management system) bus system”. Operating manual - translation into English © thermofin GmbH...
  • Page 54: Direction Of Rotation

    Clockwise rotation in normal operation. As soon as “Reversion of rotation” is activated, the fan rotates to the left. Counter-clockwise rotation in normal operation. As soon as “Reversion of rotation” is activated, the fan rotates to the right. * Factory setting Operating manual - translation into English © thermofin GmbH...
  • Page 55: Number Of Fans Per Unit

    Not editable with step switching (see also chapter 4.4.1 “Control of the fans”) Percentage lower speed limit related to the limit speed. The controller only outputs this entered value as a minimum. Factory setting: 0 % Operating manual - translation into English © thermofin GmbH...
  • Page 56: Limit Speed In Rpm

    Number of fans alarm per circuit In this parameter the minimum number of impaired fans is entered in order to trigger an alarm (DO- 2, Alarm  High priority). (DO-2 drops out) Operating manual - translation into English © thermofin GmbH...
  • Page 57: Emergency Mode

    Adjustable speed in percent if the signal source is lost. This value relates to the maximum speed (see chapter 4.4.4 “Max speed in %”). Possible settings: 10 to 100% of maximum speed Factory setting: 50 % Operating manual - translation into English © thermofin GmbH...
  • Page 58: Emergency Mode Delay In Seconds

    Only trained or instructed personnel should make changes here. Changing factory parameters (fan addresses etc.) is only possible with the manufacturer password (see also chapter 2.4.1 “Manufacturer password”). Operating manual - translation into English © thermofin GmbH...
  • Page 59 Green: Parametrization successful. White: Fan has not yet been parametrized. When exiting the menu, the bus is automatically set back to RUN. Operating manual - translation into English © thermofin GmbH...
  • Page 60 All parameters set in chap 4.4 (Fans settings) are written to fan. The address set is not changed.  “Reset fan address(es)” The addresses of all fans connected to the BUS and supplied with voltage are reset to “Factory settings”. Operating manual - translation into English © thermofin GmbH...
  • Page 61: Number Of Faults

    Upper limit: Number of fans in the device (max. 1 fault per fan) Lower limit: 0 faults Operating manual - translation into English © thermofin GmbH...
  • Page 62: Bms (Building Management System) Bus System

    This field is subdivided into registers, the number of registers to be transmitted and, if applicable, into information that is read out or stored. Stopbits: 1 stop bit if parity is used; 1 or 2 bits if no parity is used. Operating manual - translation into English © thermofin GmbH...
  • Page 63: Additional Functions

     Spray” Chapter 7.1 “Adjustments in: Device settings Additional settings Wet settings Mat”   Chapter 8.1 “Adjustments in Device settings  Additional functions  Humidification system” Water circulation Description follows. Operating manual - translation into English © thermofin GmbH...
  • Page 64: Refrigerant

    The refrigerant used can be selected separately for each circuit. Circuits 3 and 4 can also be selected by assigning an additional pressure sensor to input 3 or 4 in the “Analogue IN” submenu. Operating manual - translation into English © thermofin GmbH...
  • Page 65 Therefore, the air pressure in hPa (mbar) from the installation location of the device serves as the necessary correction value. Factory setting: 1,013 bar = 1013 mbar (hPa)  Sea level air pressure Operating manual - translation into English © thermofin GmbH...
  • Page 66: Reset Counter

    (see also chapter 4.2.10 “Low load regulation control”): Not all types of control have the same range of functions. When controlled via terminal and via BUS, only two-level control is possible. Operating manual - translation into English © thermofin GmbH...
  • Page 67 If the control has been selected, the “Low load” field in the “Additional functions” menu appears blue and can be activated (see Picture 35). The user gets to the “Low load settings”. Operating manual - translation into English © thermofin GmbH...
  • Page 68 (④) has elapsed. The fans or fan groups are switched on stepwise above this limit. The switch-on thresholds are based on the number of control levels and the limit set here. See the following examples: Operating manual - translation into English © thermofin GmbH...
  • Page 69 The switch-off times should be set as long as possible so that there is no constant switching back and forth between low load and normal control. The times must be optimized accordingly after commissioning. Operating manual - translation into English © thermofin GmbH...
  • Page 70 With these settings, the first analogue output (AO-1) works as a low load basic level and the second analogue output (AO-2) as a low load control level. As a result, both analogue outputs must be wired separately with the corresponding fans or fan groups. Operating manual - translation into English © thermofin GmbH...
  • Page 71: Si / Imp Switching Units

    In this window, the system of units for temperature and pressure can be switched independently of one another from SI (international system of units) to IMP (Anglo-American system of units). Pressure temperature °C °F Operating manual - translation into English © thermofin GmbH...
  • Page 72: Main Menu

    Switching units The submenus on the right in the main menu are protected with a parameter password. Instructed persons receive this password from the supplier of the TCS. See chapter: 2.4 “Passwords”. Operating manual - translation into English © thermofin GmbH...
  • Page 73: Actual Values

    The ambient temperature is only displayed if a humidified or wetted device is selected. Display for dry coolers Picture 42 Standard Display of the display of the optionally measured measured outlet inlet temperature temperature Operating manual - translation into English © thermofin GmbH...
  • Page 74: Monitoring

    ( chapter 4.2.3 “Night limit ” control “Control parameters” possible - see Direct switch to menu: chapter ” 5.1.3 “Monitoring Greyed out functions are not activated in the device settings Operating manual - translation into English © thermofin GmbH...
  • Page 75: I/O (Inputs / Outputs) - Display / Manual

    Device settings -> INPUTS/OUTPUTS (see also chapter 4.3.1 “Digital IN basic unit”). Activated inputs (+24 V DC at the input) are shown in green (see Picture 44 DI-1 and DI-3). Operating manual - translation into English © thermofin GmbH...
  • Page 76: Digital Out Basic Unit

    Picture 48 Picture 47 The hand symbol appears The output is now set to manual and also has a The output can now be switched on and off green background. manually. Operating manual - translation into English © thermofin GmbH...
  • Page 77: Analogue In Basic Unit

    (e.g., KTY, 0-10 V or 4-20 mA). Possibility to switch the temperature from °C to °F and the pressure from bar to psi Operating manual - translation into English © thermofin GmbH...
  • Page 78: Analogue Out Basic Unit

    Depending on the type of fan control (see also chapter 4.4.1 “Control of the fans”). The corresponding output is switched to manual operation by pressing the “– Auto switching button” (see Picture 51). Operating manual - translation into English © thermofin GmbH...
  • Page 79 By pressing the yellow information window, the user gets directly to the corresponding submenu in which manual operation was activated (see Picture 53). Operating manual - translation into English © thermofin GmbH...
  • Page 80: In / Out Extensions

    2 generation ® IN / OUT extensions For devices with an extended range of functions (e.g., thermofin ® adiabatic pad cooler or thermofin ® hybrid cooler), the digital and analogue I/Os from the TCS.2 basic unit are not sufficient. They are then expanded with external I/O modules via the CAN bus.
  • Page 81: Counter

    The manufacturer reserves the right to reset the counter and it is only possible in the Device settings  Additional functions  “Reset counter”. See also chapter 4.6.4 “Reset counter”. Picture 57 All greyed out displays are inactive and are not used. Operating manual - translation into English © thermofin GmbH...
  • Page 82: Alarms

    ® Alarms Messages about an incorrect operating status (warning) or any alarm are shown on the display. This is done directly in the start screen under the thermofin ® lettering in a red-green-flashing window (see chapter 2.3.1 “Start screen”).
  • Page 83: Fan Operating Data / Status

    Here in the example F18 has a red background. In order to display the status of the faulty fan, the corresponding number must be entered at the top right. (See picture ...) Operating manual - translation into English © thermofin GmbH...
  • Page 84: Alarm History

    If the operator wants to delete the password immediately for security reasons, for example because he has finished commissioning, it can be done with the button in the main menu (delete password). Operating manual - translation into English © thermofin GmbH...
  • Page 85: Setpoints

    Setpoints dry cooler 5.6.6 5.6.3 Speed reversion Setpoint rotation shifting (ROR) Display of speed output from circuit Picture 63 5.6.2 Setpoints 5.6.5 condenser Setpoint switching 5.6.4 limit Night 5.6.7 Control parameters Operating manual - translation into English © thermofin GmbH...
  • Page 86: Setpoints Dry Cooler

    Editable from 5 ... 90 °C Factory setting: 20 °C Alarm overtemperature** °F: Editable from 40 ... 200 °F Factory setting: 20 °F ** edited alarm value applies equally to circuit 1 and 2 Operating manual - translation into English © thermofin GmbH...
  • Page 87: Setpoints Condenser

    Editable from 30 ..90 °C Factory setting: 20 °C Alarm overtemperature** °F: Editable from 90 ... 200 °F Factory setting: 20 °F ** edited alarm value applies equally to circuit 1 and 2 Operating manual - translation into English © thermofin GmbH...
  • Page 88: Setpoint Shifting

    Circuit 1: (25 + 10.7 °C = 35.7 °C)  Analogue input 3 (0-10 V) 5.3 V ≙ 10.7 °C “Setpoint act.”: Addition of setpoint and shift value Circuit 2: (25 + 20 °C = 45 °C)  Analogue input 4 (0-10 V) 10 V ≙ 20,0 °C Operating manual - translation into English © thermofin GmbH...
  • Page 89 This function is limited to the setpoint for “Normal cooling” (NC). There is no setting option for the setpoints for free cooling and heat recovery. Circuit 1 and 2 are also treated the same. The shift value has the same effect on both circuits (see Picture 66). Operating manual - translation into English © thermofin GmbH...
  • Page 90 1.0, the setpoint is shifted by 1K when the ambient air temperature is increased by 1K. ④ “Setpoint”: Set target temperature of circuit 1 (25 °C) and circuit 2 (30 °C) ⑤ “Shift value”: Operating manual - translation into English © thermofin GmbH...
  • Page 91 20.0 °F 0 ... 50.0 °C 25.0 °C Setpoint shift start point ambient temperature. 30 ... 120.0 °F 10.0 °F Setpoint shift factor ambient temperature max. 0.5 ... 2,0 K 1,0 K Operating manual - translation into English © thermofin GmbH...
  • Page 92 If “via BUS” is selected, the “Setpoint shifting” button in the Setpoints menu has a blue background and can be pressed. The user gets to the following settings window: (Picture 67) Operating manual - translation into English © thermofin GmbH...
  • Page 93: Night Time Reduction

    * A maximum register value of 1000 (≙ 100%) is possible, if the value set in the “Setpoints” menu is also at If this value is lower, it represents the upper limit for the value sent via the bus ( 100%. see Picture 69) Operating manual - translation into English © thermofin GmbH...
  • Page 94 (see table below). (based on the max speed) Editable: from 40 % to 100 % Factory setting: 50 % Register Meaning Register value TRUE = Night time reduction active “Night time reduction” Operating manual - translation into English © thermofin GmbH...
  • Page 95 Editable from … to: Night time reduction ON: 18 - 23 o’clock Night time reduction OFF: 01 - 10 o’clock Factory setting: Night time reduction ON: 22:00 o’clock Night time reduction OFF: 06:00 o’clock Operating manual - translation into English © thermofin GmbH...
  • Page 96: Setpoint Changeover

    Editable: from 0.0 … 30.0 °C Factory setting: 5 °C FC/HR  NC: If the ambient temperature of the value edited here is reached or exceeded, the setpoint changes Picture 75 Operating manual - translation into English © thermofin GmbH...
  • Page 97: Speed Reversion Of Rotation (Ror)

    The following control options are available to the user: (see also chapter 4.2.9 “Reversion of rotation control”) Reversion of rotation via terminal Two steps are necessary to activate the “Reversion of rotation via terminal” function: Operating manual - translation into English © thermofin GmbH...
  • Page 98: Control Parameters

    (see chapter 5.6 “Setpoints”) to which the system is to be regulated, two other important parameters are required. These are the proportional factor “Kp” and the reset time “Tn”. In Operating manual - translation into English © thermofin GmbH...
  • Page 99 Since the equipment required for this is usually not part of the equipment of the commissioning personnel, we refer at this point to a Operating manual - translation into English © thermofin GmbH...
  • Page 100: Additional Functions

    In contrast to the standard, there are various functions and setting levels that are listed in this submenu item. All functions that are not activated in the device settings are greyed out with a white background. Operating manual - translation into English © thermofin GmbH...
  • Page 101: Wet Menu

     Wet menu for sprayed devices (See chapter 6.4 “Adjustments in the Main menu Additional functions   menu Spray”)  Wet menu for devices with cooling mats (thermofin ® adiabatic pads) (See chapter 7.4 “Adjustments in Main menu Additional functions Wet menu ...
  • Page 102: Spray Pump

    This function enables a circulation pump to be controlled which is used, for example, for evaporators. It feeds water for wetting the tube bundle. Function only for single-circuit devices. With two-circuit devices, the pump function only applies to circuit 1. Operating manual - translation into English © thermofin GmbH...
  • Page 103 - The following values apply to direct communication via MODBUS: Register Register Designation Meaning value Writing Spray pump TRUE = Spray pump 1 “Spray pump” Reading TRUE = Spray pump 1 active Feedback Operating manual - translation into English © thermofin GmbH...
  • Page 104 When it has expired, the spray pump switches OFF. Editable from … to: 0 … 1800 s Factory setting: 120 s ③ Pump ON, fan speed in % Operating manual - translation into English © thermofin GmbH...
  • Page 105 (before switching to manual). After changing from “Automatic” to “Manual” operating mode, the spray pump can be switched on and off with these buttons. Manual mode active Operating manual - translation into English © thermofin GmbH...
  • Page 106 Flow sensor active, line flows through. Flow sensor active, flow interrupted. See also chapter 10.5 “Signals external messages – Error code S...” The following parameters apply to direct communication via MODBUS: Operating manual - translation into English © thermofin GmbH...
  • Page 107 The following states of the dry-running sensor are displayed: Dry-running sensor deactivated. Dry-running sensor active, water level Ok. Dry-running sensor active, water level too low. See also chapter 10.5 “Signals external messages – Error code S...” Operating manual - translation into English © thermofin GmbH...
  • Page 108: Bypass Valve

    2 The left and first level is the so-called base load level. It remains regulated and is not switched off. All other levels are “control levels”. Medium valve Description follows … Operating manual - translation into English © thermofin GmbH...
  • Page 109: Network Ip

     Ethernet IP (standard)  Modbus-TCP  FTP server Picture 80 5.7.1 5.7.2 5.7.3 Undo IP address Adaptation of the network address. Please have the responsible administrator assign a suitable address. Factory setting: 172.25.10.10 Operating manual - translation into English © thermofin GmbH...
  • Page 110: Network Mask / Subnet Mask

    TCP/IP properties. It is then up to the router to forward the packet to the correct subnet. Factory setting: 0.0.0.0 Operating manual - translation into English © thermofin GmbH...
  • Page 111: Time / Date

    TCS.2 switched on. Picture 81 Jump to the right to select the time zone Operating manual - translation into English © thermofin GmbH...
  • Page 112: Select Time Zone

    TCS.2. To avoid this cost, the time zone “Africa/Tunis” can be selected, for example. In Tunisia the time change was abolished in 2008 and therefore has Central European Time (CET) all year round. Operating manual - translation into English © thermofin GmbH...
  • Page 113: Sprayed Devices

    ® SPRAYED DEVICES The thermofin® spray system on condensers or dry coolers is used to cover peak loads at high ambient temperatures. All the necessary settings on the TCS.2 are explained in the following chapter. Adjustments in: Device settings  Additional functions Wet settings - Spray...
  • Page 114: Main Water Valve

    4 spray valves If only one spray valve is used, this can also be used as the main water valve [see chapter 6.1.6 “Spray valve (SPV 1) as Main water valve”]. Operating manual - translation into English © thermofin GmbH...
  • Page 115: Hardness Stabilizer

    The hygienic circuit should prevent legionella formation and stagnation in the supply line of the thermofin® spray system. As soon as the adiabatic system is switched off, a counter begins to record the waiting time. When the set time is reached, the drain valve opens and the entire water line up to the main water valve is drained.
  • Page 116: Storage Container

    This output is set as soon as a wet level (spray level) is active. See also chapter 4.3.2 “Digital OUT basic unit”.  Messages via BUS The following status messages are output via the BUS: Operating manual - translation into English © thermofin GmbH...
  • Page 117: Fresh Water Meter

    Impulse requirement: + 24 V DC ≥ 50 ms  Messages via BUS The following values are output via the BUS: Register Register Word Designation Meaning value Fresh water Fresh water consumption in m³ Cubic meter consumption Operating manual - translation into English © thermofin GmbH...
  • Page 118: I/O Valves Settings

    Spray valve 1 2-4 spray levels 1 spray level Spray valve 2 2-4 spray levels 1 spray level Spray valve 3 2-4 spray levels 1 spray level Spray valve 4 2-4 spray levels Operating manual - translation into English © thermofin GmbH...
  • Page 119: Bus Parameter Valves

    TRUE = Spray valve 3 runtime error runtime error Reading Spray valve 4 open TRUE = Spray valve 4 open V07 Spray valve 4 Reading TRUE = Spray valve 4 runtime error runtime error Operating manual - translation into English © thermofin GmbH...
  • Page 120: Adjustments In The Main Menu  Additional Functions  Wet Menu Spray

    2 generation ® Adjustments in the Main menu  Additional functions  Wet menu Spray Picture 86 Picture 87 Picture 88 6.4.1 6.4.2 6.4.5 6.4.3 6.4.6 6.4.7 6.4.4 6.4.8 Operating manual - translation into English © thermofin GmbH...
  • Page 121: Winter Operation/Summer Operation

    Editable from … to: 4.0 … 40.0 °C Factory setting: 10.0 °C RPM Winter operation OFF: Another switch-off condition that switches off winter operation from a certain speed (in %). Operating manual - translation into English © thermofin GmbH...
  • Page 122: Display Of Ambient Temperature

    Display of main valves Status display of the main valve positions. The following symbols are used as indicators in the display: Valve is OPEN Valve is CLOSED Valve is OPENING Valve is CLOSING Operating manual - translation into English © thermofin GmbH...
  • Page 123: Ambient Temperature Spray On

    The following parameters apply to direct communication via Modbus: Register value Register Name Converted to °C/°F (signed integer) -250 ... 250 -25.0 ... 25.0 °C “Setpoint shift for application point wetting” -450 ... 450 -45.0 ... 45.0 °F Operating manual - translation into English © thermofin GmbH...
  • Page 124: Spray Valves

    Switch-off condition for spray level [No]. This is fulfilled when the actual value is smaller or larger than the setpoint by the percentage value set here (depending on the sign of the edited value). If all switch-off conditions are met, the respective spray level switches OFF. Operating manual - translation into English © thermofin GmbH...
  • Page 125 Factory setting: 60 s ⑥ Operating hours counter Display of operating hours and minutes of the respective spray level. Useful for monitoring and evaluating dry and wet operation of the system. Operating manual - translation into English © thermofin GmbH...
  • Page 126: Hygienic Circuit

    The hygienic circuit should prevent legionella formation and stagnation in the supply line of the thermofin® spray system. As soon as the adiabatic system is switched off, a counter begins to record the waiting time. When the set time is reached, the drain valve opens and the entire water line up to the main water valve is drained.
  • Page 127: Manual Operation

    “Manual-Auto switching button” The hand symbol appears The output can now be switched on and off manually. Additional indication valve + Jump back to 6.4.8A) summer/winter operation ” “Handbetrieb Hauptventile Operating manual - translation into English © thermofin GmbH...
  • Page 128 ® The corresponding output is switched back to automatic operation by pressing the “Manual- Auto switching button” again. It changes back to the state it would normally have in automatic operation. Operating manual - translation into English © thermofin GmbH...
  • Page 129: Devices With Cooling Mats (Adiabatic Pads)

    DEVICES WITH COOLING MATS (ADIABATIC PADS) Devices with cooling mats (thermofin® adiabatic pads) are used to pre-cool the ambient air with the help of a wetted humidifier which is located directly in front of the lamellar tube block. The cooling mat soaks up with water.
  • Page 130: Main Water Valve

    2 spray valves If only one control valve is used, this can also be used as the main water valve [see chapter 7.1.6 “Control valve (CV 1) as Main water valve”]. Operating manual - translation into English © thermofin GmbH...
  • Page 131: Hardness Stabilizer

    The hygienic circuit should prevent legionella formation and stagnation in the supply line of the thermofin® adiabatic pad system. As soon as the humidification is switched off, a counter begins to record the waiting time. When the set time is reached, the drain valve opens and the entire water line up to the main water valve is drained.
  • Page 132: Storage Container

    This output is set as soon as a wet level (wetting level) is active. See also chapter 4.3.2 “Digital OUT basic unit”.  Messages via BUS The following status messages are output via the BUS: Operating manual - translation into English © thermofin GmbH...
  • Page 133: Fresh Water Meter

    The user can access the cooling mat system submenu by pressing the mat symbol (see Picture 96). If the main water valve is open, the symbol is highlighted in light blue. It thus shows whether the adiabatic mats are in operation. Operating manual - translation into English © thermofin GmbH...
  • Page 134: I/O Valves Settings

    1 control valve Air humidity with 2 control valves Ambient with 1 control valve temperature with 2 control valves When using the AKM 730.10 extension module (optionally selectable CAN address 31): Operating manual - translation into English © thermofin GmbH...
  • Page 135 2 control valves Control valve 2 with 2 control valves with 1 control valve Air humidity with 2 control valves Ambient with 1 control valve temperature with 2 control valves Operating manual - translation into English © thermofin GmbH...
  • Page 136: Bus Parameter Valves

    TRUE = Control valve adiab. Reading 2 Position error pads, position error circuit 2 1024 V08 Control valve TRUE = Control valve adiab. Reading 2 wire break pads, wire break circuit 2 Operating manual - translation into English © thermofin GmbH...
  • Page 137: Adjustments In Main Menu  Additional Functions  Wet Menu Mat

    [see also chapter 2.4.3 “User parameter password (editable)”]. Picture 98 Picture 99 Picture 100 7.4.1 7.4.5 7.4.2 7.4.6 7.4.3 7.4.7 7.4.8 7.4.4 7.4.9 Greyed out functions are not activated or selected in the device settings. Operating manual - translation into English © thermofin GmbH...
  • Page 138: Winter Operation / Summer Operation

    10.0 °C RPM Winter operation OFF: Another switch-off condition that switches off winter operation from a certain speed (in %). Editable from … to: 0 … 100 % Factory setting: 80 % Operating manual - translation into English © thermofin GmbH...
  • Page 139: Display Of Ambient Temperature

    Display of main valves Status display of the main valve positions. The following symbols are used as indicators in the display: Valve is OPEN Valve is CLOSED Valve is OPENING Valve is CLOSING Operating manual - translation into English © thermofin GmbH...
  • Page 140: Ambient Temperature Adiabatic On

    101). The following parameters apply to direct communication via Modbus: Register value Register Name Converted to °C/°F (signed integer) -250 ... 250 -25.0 ... 25.0 °C “Setpoint shift for application point wetting” -450 ... 450 -45.0 ... 45.0 °F Operating manual - translation into English © thermofin GmbH...
  • Page 141: Control Valve 1 / 2

    ⑥ Display: Summer / Manual 7.4.9 Display: Winter operation operation Possible pre-cooling, speed output circuit 1 and valve position Picture 104 Picture 105 75 % →90 % Display of mat menu: Operating manual - translation into English © thermofin GmbH...
  • Page 142 °C when the mat is moist. If this falls below the value edited here and all other switch-off conditions are met, the humidification level [No] switches OFF. Editable from … to: depending on the setting in efficiencySLIDE” Factory setting: 0 °C Operating manual - translation into English © thermofin GmbH...
  • Page 143: Efficiencyslide

    Precise pre-setting of the switch-on and switch-off limits and the ratio (speed - possible pre- cooling) in the efficiencySLIDE settings is of great importance in order to use the slide effectively! Operating manual - translation into English © thermofin GmbH...
  • Page 144 Both switching limits can also be combined. Careful commissioning and control of the mode of operation is imperative in order to ensure environmentally friendly operation (saving energy and water). Operating manual - translation into English © thermofin GmbH...
  • Page 145 Setting range limits of air pre-cooling (°C): ⑤ energy-saving: 0.0 to ⑥ possible pre-cooling ON ⑥ water-saving: 0.0 to 20.0 possible pre-cooling OFF ⑦ energy-saving: 0.0 to ⑤ ⑧ water-saving: 0.0 to ⑥ Operating manual - translation into English © thermofin GmbH...
  • Page 146: Hygienic Circuit

    The hygienic circuit should prevent legionella formation and stagnation in the supply line of the thermofin® humidification system. As soon as the adiabatic system is switched off, a counter begins to record the waiting time. When the set time is reached, the drain valve opens and the entire water line up to the main water valve is drained.
  • Page 147: Manual Operation

    The corresponding output is switched back to automatic operation by pressing the “Manual- Auto switching button” again. It changes back to the state it would normally have in automatic operation. Operating manual - translation into English © thermofin GmbH...
  • Page 148 The corresponding valve is switched back to automatic operation by pressing the “Manual- Auto switching button” again. The manipulated variable takes over the value of the controlled variable. Operating manual - translation into English © thermofin GmbH...
  • Page 149: Hybrid Cooler

    Description follows … 9. INSULATING / PENTHOUSE COOLER Adjustments in Device settings  Additional functions  Humidification system Description follows … Adjustments in Main menu  Additional functions  Wet mode Operating manual - translation into English © thermofin GmbH...
  • Page 150: 10. Messages, Warning And Alarms

    Communication to the respective - Check terminal points [no.] CAN - I/O extension is interrupted. - Check the set CAN address (see also device manual, chapter 5.1.3 "Setting the CAN address") Operating manual - translation into English © thermofin GmbH...
  • Page 151: Fan Messages - Error Code F

    - Switch off the mains voltage Communication between the microcontrollers in - Wait error the fan - Switch on again Fan collective - General fan error sent via - Observe further status messages failure MODBUS Operating manual - translation into English © thermofin GmbH...
  • Page 152 - Check the applied mains voltage undervoltage - Check the wiring of the communication bus Communication - No communication between - Check terminal points interrupted TCS.2 and fan possible - Check the power supply of the Operating manual - translation into English © thermofin GmbH...
  • Page 153: Flaps Messages - Error Code K

    I > Open AbtKL[no.], stop at I > Close AbtKL[no.], LZ error, I = Close AbtKL[no.], LZ error, I = Close AbtKL[no.], LZ error, limit swit. Open AbtKL[no.], LZ error, I = Operating manual - translation into English © thermofin GmbH...
  • Page 154: Measured Values Messages - Error Code M

    - Resistance is clearly too low device manual, chapter 3.6.4) - Incorrect configuration of the - Replace the Ambient sensor analogue input (jumper position) - The analogue input may be defective, please contact the manufacturer Operating manual - translation into English © thermofin GmbH...
  • Page 155 - Resistance is clearly too low device manual, chapter 3.6.4) - Incorrect configuration of the - Replace the Coil sensor analogue input (jumper position) - The analogue input may be defective, please contact the manufacturer Operating manual - translation into English © thermofin GmbH...
  • Page 156 - Resistance is clearly too high - Replace the humidity sensor - Incorrect configuration of the - The analogue input may be analogue input (jumper position) defective, please contact the manufacturer Operating manual - translation into English © thermofin GmbH...
  • Page 157 - Resistance is clearly too low device manual, chapter 3.6.4) - Incorrect configuration of the - Replace the cell sensor analogue input (jumper position) - The analogue input may be defective, please contact the manufacturer Operating manual - translation into English © thermofin GmbH...
  • Page 158: Signals External Messages - Error Code S

    - Eliminate the fault in the pump on the respective terminals or the for the pressure increase function is deactivated in the "Control" menu Operating manual - translation into English © thermofin GmbH...
  • Page 159 - Water supply failed - Check water supply Dry run - Valves closed - Clean pipes warning - Line blocked - Check valves - Refill valve defective - Water supply pressure is too low Operating manual - translation into English © thermofin GmbH...
  • Page 160: Valve Messages - Error Code V

    - Check the voltage supply of the running time - Supply voltage to the valve valve interrupted - Check the feedback (limit switch) - No feedback of the valve - Check control of the valve Operating manual - translation into English © thermofin GmbH...
  • Page 161 3.6.4) error - Incorrect configuration of the - The analogue input or the control analogue input (jumper position) valve may be defective, please - Control valve is defective contact the manufacturer Operating manual - translation into English © thermofin GmbH...
  • Page 162: Closing Remarks

    Basically, it is ensured that new versions are backwards compatible This means that new software versions can replace older versions without any loss of functionality. Care is also taken to ensure that older controllers can be replaced without changing the wiring, if possible. Operating manual - translation into English © thermofin GmbH...