Operating instructions Control Panel RBG 3200 Core module version 50.04 - Build 05.19 Translation of original German version of operating instructions for operators. Read and follow all instructions and safety instructions. All errors and omissions excepted. B0640421_en | Edition 06/09/2021...
5.7.3 Circulation pump - Times ......................25 5.8 System..............................25 5.8.1 System - Current values ......................25 5.8.2 System - Error..........................25 5.8.3 System - Basic display parameters.................... 26 5.8.4 System - Language........................26 B0640421_en | Operating instructions Control Panel RBG 3200...
Page 3
Contents 5.8.5 System - Current Date ....................... 26 5.8.6 System - Current Time....................... 27 5.8.7 System - Current User Level...................... 27 6 Troubleshooting ............................28 6.1 Procedure for fault messages....................... 28 B0640421_en | Operating instructions Control Panel RBG 3200...
When work is carried out on electrical components: r Always have work carried out by a qualified electrician r Observe the applicable standards and regulations Ä Work must not be carried out on electrical components by unauthorised persons B0640421_en | Operating instructions Control Panel RBG 3200...
When using a bus repeater, the two galvanically separated sub-networks must be considered separately. The jumpers for each network must be set on the first and last module. B0640421_en | Operating instructions Control Panel RBG 3200...
(image right), the end jumper is set and the bus connection is terminated. 2.3 Setting the module address You must set the required order with the module addresses for the RBG 3200 (display module). The standard boiler comes with a display module (boiler display) with the address 0 (except S3 Turbo with S-Tronic controller).
After the system check the basic display will appear. The default basic display provides information about the two main parameters, however it can be customised to the user's individual requirements. Ü "System - Basic display parameters" [} 26] B0640421_en | Operating instructions Control Panel RBG 3200...
The status LED shows the operating status of the system: ▪ GREEN flashing (interval: 5 sec OFF, 1 sec ON): ▪ GREEN constant: BOILER SWITCHED ON ▪ ORANGE flashing: WARNING ▪ RED flashing: FAULT B0640421_en | Operating instructions Control Panel RBG 3200...
Shown when the DHW tank or return temperature control pump is active Shown when the heating circuit or storage tank loading pump is active Shows the status of the heating circuit mixer B0640421_en | Operating instructions Control Panel RBG 3200...
Pressing the info key calls up the information on the resolved, this is shown by a warning symbol at the currently pending fault message again. bottom right on the status line. Procedure for troubleshooting: Ü "Troubleshooting" [} 28] B0640421_en | Operating instructions Control Panel RBG 3200...
DHW tank loading by the tap symbol in the status line. After loading, the mode that was previously set becomes active again. long Only with boiler display! IMPORTANT! See operating instructions for boiler controller! B0640421_en | Operating instructions Control Panel RBG 3200...
After confirming by pressing the enter key, the info text shown will appear and daytime mode will be active for the allocated heating circuit until the end of the set time or until automatic mode is activated. B0640421_en | Operating instructions Control Panel RBG 3200...
After confirming by pressing the enter key, the info text shown will appear and setback mode will be active for the allocated heating circuit until the end of the set time or until automatic mode is activated. B0640421_en | Operating instructions Control Panel RBG 3200...
The factory-set times are loaded by confirming again (06:00 – 22:00). Times Caution - the customer specific time settings are lost in the process! Default program … In the "Change program" menu: B0640421_en | Operating instructions Control Panel RBG 3200...
24:00. If you press the up arrow key repeatedly, the time disappears and is replaced by dashes. Then carry out the same process with the start time. After the enter key has been pressed repeatedly, the changes are adopted and it returns to the previous menu. B0640421_en | Operating instructions Control Panel RBG 3200...
Display of the calculated flow temperature setpoint. Room temperature Prerequisite: Heating circuit used in conjunction with remote control Display of the current room temperature. Outside air temperature Display of the current outside air temperature. B0640421_en | Operating instructions Control Panel RBG 3200...
If the room temperature or the flow temperature is lower than the set value, the heating circuit pump will be switched on and the heating circuit mixer keeps to the maximum heating circuit flow temperature that is set. B0640421_en | Operating instructions Control Panel RBG 3200...
Current temperature in the area of the reference sensor of the solar panel system. DHW tank pump control Specifies the speed of the DHW tank pump as a percentage of maximum speed. B0640421_en | Operating instructions Control Panel RBG 3200...
In order to perform the calculation more precisely, the use of a collector return sensor is recommended. B0640421_en | Operating instructions Control Panel RBG 3200...
Page 20
▪ DFL:Current flow rate of solar collector ▪ Today: Heat quantity that has been produced by the solar panel system today ▪ Total: Heat quantity that has been produced since activation of the solar panel system B0640421_en | Operating instructions Control Panel RBG 3200...
Buffer tank temperature, sensor 3 Prerequisite: Master boiler in the cascade or hydraulic system 4 or fuel amount calculation Display of the current temperature in the lower part of the buffer tank. B0640421_en | Operating instructions Control Panel RBG 3200...
Display of the current pump control for the standby boiler. Standby boiler switch valve Prerequisite: “Switch valve installed” parameter set to “YES” Display of the current switch valve control of the standby boiler. B0640421_en | Operating instructions Control Panel RBG 3200...
If the secondary boiler is started, it will run for at least the length of time set here. Temperature difference between secondary boiler and buffer tank Temperature difference between secondary boiler and upper temperature in layered tank to activate the loading pump of the secondary boiler. B0640421_en | Operating instructions Control Panel RBG 3200...
Flow switch on the domestic hot water line ▪ 0: Flow switch detects no flow rate. ▪ 1: Flow switch detects flow rate. Speed of the circulation pump Specifies the current speed of the circulation pump. B0640421_en | Operating instructions Control Panel RBG 3200...
Display of the current fault messages. In addition, you can also invoke time information here, such as when the fault occurred, when the fault was acknowledged and when the fault was cleared. B0640421_en | Operating instructions Control Panel RBG 3200...
▪ Deutsch, English, Francais, Italiano, Slovenski, Cesky, Polski, Svenska, Espanol, Magyar, Suomi, Dansk, Nederlands, Русский, Serbian 5.8.5 System - Current Date Basic display System Current Date Current Date Display and setting of current date. B0640421_en | Operating instructions Control Panel RBG 3200...
Standard user level for normal operation of the display. All customer-specific parameters are displayed and can be changed. Installer / Service Releases parameters to adjust the controller to the system components (if configured). B0640421_en | Operating instructions Control Panel RBG 3200...
If a fault has various causes or the cause can be resolved in various ways, you can scroll through with the navigation keys. Error resolution Error causes Sensor signal damaged Check sensor and sensor cable B0640421_en | Operating instructions Control Panel RBG 3200...