TABLE OF CONTENTS Page No. Description Table of Contents Safety Information Technical Data Specifications Operator Control Panel Operation and Service Troubleshooting Electrical Schematic Electrical Panel Layout Piping Schematic Structural\Sheet Metal BOM Contact TCRS at 440-658-2020...
If a tool, procedure, work method or operating technique that is not specifically recommended by TCRS is used, you must satisfy yourself that it is safe for you and for others. You should also ensure that you are authorized to perform this work, and that the product will not be damaged or become unsafe by the operation, lubrication, maintenance or repair procedures that you intend to use.
Page 4
Ensure that all protective guards and all covers are secured in place on the unit. Never put maintenance fluids into glass containers. Glass containers can break. Use all cleaning solutions with care. Report all necessary repairs. Contact TCRS at 440-658-2020...
Page 5
Always use leak proof containers when you drain fluids. Do not pour waste onto the ground, down a drain, or into any source of water. Burn Prevention Do not service an operating unit. Allow the compressor to cool before any maintenance is performed. Contact TCRS at 440-658-2020...
Refrigerant R-410A Charge system 1 & 2 12 LBS. x 2 High Press Cut Out 610 PSIG Low Press Cut Out 40 PSIG Bitzer BVC32 180oz. DBA @20’ 73 DBA Weight 2250 LBS. Made in USA Contact TCRS at 440-658-2020...
HIGH PRESS CO TRIP – System pressure above High Pressure Cut Out. MOTOR OVERLOAD – Compressor system 1&2 status. HIGH PRESSURE SW – System pressure 1&2 above limit, tripped mechanical switch. LOW PRESSURE SW – System pressure 1&2 below limit, tripped mechanical switch. Contact TCRS at 440-658-2020...
Page 8
Select Temp Display – Selects temperature display units (Celsius or Fahrenheit) COND AUTO – Switches condenser fan to manual mode for testing. Set 0-100 Monitor Screen – Monitor the Suction (Low) Pressure and Discharge (High) Pressure. For System 1&2 Contact TCRS at 440-658-2020...
Operation and Service Designed Performance Features Air conditioning system design requirements: 1. To be located outside of the conditioned space by the use of 2 -20 inch flexible supply air ducts and 2 -20 inch flexible return air ducts. 2. To operate in outdoor temperatures from 0° F to 100° F. 3.
High Pressure and low pressure switches are located in the compressor compartment. The high pressure switch must be physically reset if pressure exceeds 600psi. The low pressure switch will reset automatically when pressure is above 80psi. Contact TCRS at 440-658-2020...