CS-503 OPOP cascade controller is device connecting up to 4 boilers in one line and provides automatic operation of each of them on temperature or weather control basis. This allows installers to install more than one boiler inside one boiler room and still have all features of automatic operation.
PACKAGING TECHNICAL SPECIFICATION Following list of parts is included inside CS-503 Following list is specification of basic electrical and package: other technical values. 1. CS-503 cascade controller Power supply 230V 2. 4 pcs of RS connection cable (5m) Power consumption ...
Setup of cascade operation is done by v8 or v9 control unit of Biopel boiler. So first ting to enable this feature is to update your boiler control unit firmware. Ask your installer or OPOP representative to explain you which is the required firmware version and how to successfully update your v8 or v9 control unit.
6.2. Modulation mode Cascade controller operates the boiler to achieve selected boiler temperature. Only 1 boiler connected to 1 output is active in the beginning of operation. When boiler reaches maximum power, counter starts to measure time selected in Installer settings (v8) or Main Settings (v9) – Cascade - Waiting time. If set boiler temperature has not been reached during this time period, second boiler will be activated and counter starts to measure “Waiting time”...