Table of Contents I. Installation Clearances ...................... 3 Mounting ......................3 Piping ......................3 Electrical Power ....................3 Filling the Unit ....................3 II. Startup Phase Monitor (CGS only) ................4 ON/OFF Switch ....................5 Pump Priming (CGS only) ................6 III.
3’ (91cm) clearance on the front is required. Mounting • A CWS must be mounted on a wall. Use appropriate anchors to support the weight of the unit. • A CGS must be mounted on the floor and secured to a wall. Use appropriate anchors to prevent any risk of tipping over.
Purpose: Units configured for 3-phase electrical have a phase monitor to check incoming electrical power. Operation: The phase monitor is factory adjusted by Haskris according to the proper electrical settings for the unit. Do not adjust the knobs on the phase monitor without discussion and approval from Haskris.
ON/OFF Switch Location: A rotary ON/OFF switch is located on the front or side of the unit (Figure 3). Operation: Rotate the switch to turn the unit ON or OFF. If a fault occurs, turning the switch to OFF and then back ON will reset the fault. Figure 3: ON/OFF switch, vertical position Revision: 02 Page 5 of 12...
Pump Priming (CGS only) Purpose: All fluid is removed from the pump head prior to shipment from Haskris. When starting the pump, it needs to be filled with fluid. This process is called priming the pump. When the piping is full of fluid, the pump suction line is “flooded”. In some cases, this flooded suction will automatically prime the pump.
III. Controller Display Main Display Status Supply Setpoint (CGS only) Supply Actual Flow Rate (if applicable) Figure 5: Main display Status Indicates the state of the unit Desired supply fluid temperature to the application when city Supply Setpoint water backup is active (CGS only) Supply Actual Measured supply fluid temperature Flow Rate...
Adjusting Temperature Setpoint (CGS only) Notes: Setpoint is the only adjustable value on the Main display (Figure 5). To change the setting, follow the procedure below. 1. Press to move the blinking cursor to the value 2. Press to adjust the value 3.
Adjusting Alarm Set Points Purpose: When the CWS/CGS is in Auto mode, it will automatically switchover to city water backup on high temperature and low flow. The high temperature alarm set point is the supply temperature threshold at which switchover to city water backup is triggered. On units with a flow transducer, the low flow alarm set point is the threshold at which switchover to city water backup is triggered.
Units of Measure Purpose: Several combinations of units of measure are available depending on what is most useful. The following units of measure are available: • CAN (°C, psi, GPM) • UK (°C, bar, IGM) • USA (°F, psi, GPM) •...
Faults Identify if there is a fault: The button will flash red when there is a fault. Display faults and details: Press to see fault descriptions. # of simultaneous faults Description Time and date stamp Figure 8: Example fault screen Description: Provides information about the specific fault.
Page 12
Start and Stop: In the bottom right-hand corner, certain faults will display “Start” or “Stop”. Start indicates when the fault occurred. Stop indicates when the fault was cleared. Log #, higher number is more recent Description Time and date stamp Figure 10: Example fault history screen Common Faults Wording...
Need help?
Do you have a question about the CWS and is the answer not in the manual?
Questions and answers