MPDU User Manual
MPDU User Manual
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Excellent Series and is the answer not in the manual?

Questions and answers

Summary of Contents for DirekTronik Excellent Series

  • Page 1 MPDU User Manual MPDU User Manual...
  • Page 2: Table Of Contents

    MPDU User Manual Contents 1 MPDU Introduction ............................. 4 2 SCOPE OF APPLICATION ..........................4 3 TERMS & DEFINITIONS ..........................4 4 MAIN FUNCTIONS AND INSTALLATION ....................6 4.1 Function description ........................... 6 ........................7 Product picture and description 4.3 Installation ..............................11 ...........................
  • Page 3 Maximum load must not exceed MPDU rating. Maintenance requirements  Change the main control module and excellent series output module, and must be operated by professional and technical personnel.  Because the MPDU output module base is strongly charged, in order to ensure personal safety, in the maintenance of equipment, please do a good job of insulation protection.
  • Page 4: Mpdu Introduction

    MPDU User Manual 1 MPDU Introduction MPDU (Module Power Distribution Unit) is the latest scientific achievements in the power distribution industry for data center. The originated Hot-Swap Control Module and field-replaceable Output Module design enable the user to upgrade the PDU to different product functional series (A, B, C, D series) and different product categories (MPDU, ZPDU) as well.
  • Page 5 MPDU User Manual Product Types Main functions Excellent series Flyover series transcendence series (Modular) (integration) (Multi Standard) ● ● Sheet metal shell ● Aluminum alloy housing ● ● ● Main control module hot swap ● Output module hot swap ●...
  • Page 6: Main Functions And Installation

    MPDU User Manual ● ● Power ON/OFF delay of individual outlet Note:● Means the specified function is supported 3.2.3 MPDU C/D series come with 2 options on the relay, monostable (normally open) relay and the latching relay; C/D series Main functions Monostable Relay Type Latching relay type ●...
  • Page 7: Product Picture And Description

    MPDU User Manual MPDU A/B/C/D series function table Function Description Monitoring function: Through the local LCD screen user can view the current/voltage/energy consumption/power at input level or individual outlet Monitoring level(A&C series not included), temperature/humidity status, band rate, serial communication address, device series, IP address. Outlet switching function (A&B series not included): switching on/off each Switching individual outlet or all outlets, set up the power on/off delay, reset power...
  • Page 8 MPDU User Manual 4.2.1 Vertical MPDU(0U) Excellent series (Modular) Flyover series(integration) transcendence series (Multi Standard) Vertical Vertical Vertical...
  • Page 9 MPDU User Manual Excellent series (High-density; Modular) Excellent series (High-density; Modular)
  • Page 10 MPDU User Manual 4.2.2 Horizontal MPDU(1U) Horizontal Flyover series 1. Input power cord; 2. Hydraulic circuit breaker; 3. NMC Module; 4. LCD screen; 5. RUN:Operation indicator; kWh:Energy pulse indicator; ALM:Alarm indicator; 6. UP:Scroll up to the previous page; 7. DOWN:Scroll down to the next page; 8.
  • Page 11: Installation

    MPDU User Manual 4.3 Installation 4.3.1 Vertical-mounting (0U) 4.3.2 horizontal-mounting(1U)
  • Page 12: Hardware Instruction

    MPDU User Manual 5 Hardware instruction 5.1 MPDU module Item Function Instruction RUN indicator Status: flashing every second kWh indicator Status: flashing frequency depends on the connected load Alarm indicator Status: flashing when threshold is exceeded. Ethernet port LAN/WAN communication port Serial port RS-485 Serial communication port Daisy-Chain port...
  • Page 13 MPDU User Manual 5.2.2 Press the CONTROL button to view the current/power/power consumption of individual outlet (A&C series not included) 5.2.3 Press and hold the CONTROL button for 4 seconds to back to the input voltage/current/power/power consumption of each phase...
  • Page 14 MPDU User Manual...
  • Page 15: Hardware Settings

    MPDU User Manual 5.3 Hardware Settings 5.3.1 Restore to factory settings: Press and hold the CONTROL button to power on the MPDU at the same time (Or press and hold the CONTROL button and press RESET button at the same time) till the RUN indicator is flashing. Note: All accounts are cleared and the network configuration is restored to the default after restoring the factory settings.
  • Page 16 MPDU User Manual Note: Only the same product series can support the Daisy-chain connection. Single phase and Three phase or A/B/C/D series cannot Daisy-chain together. For example, A series MPDU with single phase input can be connected by A series with single phase only; D series MPDU with Three phase input can be connected by D series with Three phase input.
  • Page 17: Rj45 Terminal Pin Instruction Of Rs485 Port

    MPDU User Manual address code on Device Manage page; The Master unit collects the data from the SER port through the RS-485 serial communication cable. Please refer to the《MPDU MODBUS RTU Protocol Guide》for details. 5.4.4 Serial Connection settings(Optional) The Modbus-RTU protocol is used here for the Star connection, The MODBUS Serial Server connect to the IN port from the first MPDU.
  • Page 18: Sensor Box(Optional

    MPDU User Manual 5.6 Sensor Box(Optional) MPDU could monitoring extend temperature, humidity, door status, smoke status, water status real time through external sensor box.Please refer to the《Sensor Box Operating Manual》 MPDU Sensor Box Note: This function is disabled by default and user may enable it by accessing the Web UI according to 6.2.1-C. Once the function is enabled, Ethernet Daisy-Chain as 5.4.3 will no longer be available.
  • Page 19: Web Interface

    MPDU User Manual 6.2.1 Web interface Type the IP address(https://192.168.1.163 by default, the IP address can be viewed from the LCD display by pressing the UP/DOWN botton) of the Rack PDU in the Web browser’s URL address field and press ENTER. The popup will require creating a new account on first login as figure 1-1 Figure 1-1 The Username and Password can be between 6 to 16 characters and contains any letters and numbers.
  • Page 20 MPDU User Manual The system will be blocked for one hour after 15 failed attempts in a row, Or you will have to restart the PDU again for immediate login. The main interface will appear as figure 1.3 if you entered the correct Username and Password. Note: User will be auto logout if no activity in 20 minutes.
  • Page 21 MPDU User Manual The input current threshold range: 0-63A for single phase, 0-32A for three phase Temperature/Humidity threshold range: 0-40℃ for temperature, 0-99% for humidity Figure 1-4 Individual outlet threshold settings: The individual outlet current threshold range: 0-16A User-defined power On/Off delay for individual outlets or all outlets range: 0-10 seconds Note: The low-load and overload threshold should be within the threshold range.
  • Page 22 MPDU User Manual Figure 1-5 Power consumption Return-To-Zero User can v iew the power consumption of individual outlet or each phase. The specified power consumption can be returned to zero by clicking the Reset button. The power consumption value of specified outlet will be reduced from the total power consumption.
  • Page 23 MPDU User Manual Figure 1-6 Outlet Control Click the ON/OFF button after the outlet to switch ON/OFF the specified individual outlets; Click the ON/OFF button after each phase to switch ON/OFF the outlets from the specified phase; Click All ON/All OFF button to switch ON/OFF all outlets at the same time. Figure 1-7 Switch Group Tick off the box from the Outlet Groups listed;...
  • Page 24 MPDU User Manual Figure 1- Port permissions settings: Modify the port permissions: In the user name drop-down list, select the administrator or normal user account. Next to the corresponding output bit name, click the √ symbol to have the output bit control permission, and the unsigned symbol is no output bit control permission.
  • Page 25 MPDU User Manual Figure 1-9 C. Device Management Device Settings: To configure the device name, mute the buzzer alarm, Sensor Box, IN/OUT port cascade mode ,Work mode, Modbus address code and baud rate. Figure 1-10...
  • Page 26 MPDU User Manual D. Network Settings: HTTP settings Set-up and save the SSL port according to the working mode. HTTPS(SSL) Mode Port is 443 by default Note: These settings will take effect when MPDU is restarted Network settings and modify IP address, for example: IP address:192.168.1.163(factory default IP);...
  • Page 27 MPDU User Manual Figure 1-12 Note: When DHCP is On, the device automatically obtains the router to assign an IP address and will not allow you to manually modify the network settings. SNMP settings a. SNMP V1/V2c settings: SNMP v1/v2c is disabled by default, get community and set community is public and private respectively. Trap address: can set 2 trap addresses.
  • Page 28 MPDU User Manual Figure 1-13 SMTP settings: Click SMTP from the network navigation tab to enter the SMTP setting as figure 1-14 Fill in the parameters of SMTP service including SMTP account, password, SMTP server, working mode (SMTP/SMTPS) and e-mail recipients (up to 5 recipients), then Click Save. SMTP settings will take effect when MPDU is restarted.
  • Page 29 MPDU User Manual Figure 1-14 Telnet Settings Telnet: select “Enable” or “Disable” (Enable by default) and save, make sure to restart the software after modification. Telnet account and password is the same one used for login. Telnet port is 23 Figure 1-15...
  • Page 30 MPDU User Manual Note: telnet settings will take effect when MPDU is restarted. NTP Settings: NTP section displays the device current time which is also the time recorded for the logs. Figure 1-16 a. Local time calibration Click Time Acquisition to synchronize the MPDU system time to the local machine. b.
  • Page 31 MPDU User Manual Figure 1-17 Note: Modbus-TCP settings will take effect when MPDU is restarted. E. User Settings Create new account: Click User Settings tab and fill in the user name, password, confirm password, then click Add to create new user account. Note: The Username and Password can be between 6 to 16 characters and contains any letters or numbers.
  • Page 32 MPDU User Manual Figure 1-18 F. Logs Log type: Alarm log and operation log Log information: time, log type and detail information Memory capacity: Max 1500 logs, the initial logs will be removed when reached 1500 logs. To view the logs: Click a page number to open a specific page of the log Every page display 25 logs and maximum support to 60 pages;...
  • Page 33 MPDU User Manual Figure 1-19 Note: At the prompt of “Sever object cannot be built”, please try again after configuring the security level of IE browser following the below steps: The internet Explorer goes to: Tools-- Internet Options-- Security- Custom Level-- Tick off Enable(unsafe) from Initialize and script ActiveX controls not marked as safe for scripting--- OK-- OK G.
  • Page 34: Snmp Access

    MPDU User Manual Figure 1-20 6.2.2 SNMP access This software support SNMP V1, V2C and V3, a MIB file can be provided at customer’s request. User can view the power information and environment status and receive the alarming from the device. After enable the SNMP function from Web Interface, A SNMP management software is required to be installed.
  • Page 35 MPDU User Manual Figure 2-1 Press ENTER. At the prompts, enter your user name and password to log in to the command line interface as figure Figure 2-2 A. “PHASE” command...
  • Page 36 MPDU User Manual Use the PHASE command to view the power data including current, voltage, power, power factor, power consumption on each phase Command line format: PHASE as figure 2-3 Figure 2-3 B. “OUTPUT” command Use the OUTPUT command to view the current, power, power consumption and ON/OFF status at individual outlet level.
  • Page 37 MPDU User Manual Figure 2-4 C. “SENSOR” command Use the Sensor command to view the temperature/humidity status and its threshold Command line format: SENSOR; see figure as 2-5 Figure 2-5 D. “ON/OFF” command Use the ON/OFF command to switch On/Off the individual outlet, outlets from each phase or all outlets. Command line format: ON/OFF 【index】【operation】...
  • Page 38 MPDU User Manual Figure 2-6 【index】 Description OUTPUT Enter command line: ON OUTPUT 1 to switch on the outlet 1; Enter command line: OFF OUTPUT 1 to switch Off the outlet 1; OUTPUT command can switch ON/OFF only one outlet at one time. GROUP Enter command line: on group 1 to switch on outlet from branch circuit 1;...
  • Page 39 MPDU User Manual PHASE Enter command line: on phase 1 to switch on outlets from phase 1; Enter command line: off phase 1 to switch off outlets from phase 1; E. REBOOT Command Use the REBOOT command to restart the device as figure 2-8 Figure 2-8 F.
  • Page 40: Modbus-Rtu Access

    MPDU User Manual 6.2.4 MODBUS-RTU access MODBUS-RTU access use two-wire RS-485 serial communication port for serial access, please refer to the MPDU MODBUS RTU Protocol Instruction for the MODBUS access Modus-RTU protocol configuration including Modbus -RTU communication address (1-99), baud rate(4800, 9600, 19200, 38400, 115200), data bit (8) , parity (no) , stop bit (1) Note: The serial communication data is collected from the SER port of PDU.
  • Page 41: Technical Parameters

    MPDU User Manual A: Press and hold the CONTROL button to Switch on the MPDU (Or press the CONTROL button and RESET button together), till the RUN indicator is flashing. 8 Technical Parameters Performance parameter Technical parameter Rated input Single phase:100VAC~240VAC Frequency: 50~60Hz; voltage Three phase:200VAC~400VAC Frequency: 50~60Hz;...
  • Page 42 MPDU User Manual Alarm 1× LED IP Address, MPDU 0U:2.8 inch TFT screen state, measurement 1U:1.44 inch TFT screen value, alarm state Full-scale:16A/32A, Accuracy:± 1%rdg.± 10dgt. Total current Load current Resolution:0.01A, Response:500ms display Individual load Full-scale:10A/16A, Accuracy:± 1%rdg.± 10dgt. current resolution:0.01A, Response:500ms Working rang: 0℃...
  • Page 43: Warranty And Service

    MPDU User Manual Working 0℃~+45℃ Environment Relative humidity: 5%~95% Environment Storage Temperature: -20℃~+70℃ Environment Relative humidity :5%~95% ROHS Compliance 9 Warranty and Service The product is guaranteed for two years from the date of purchase. We will repair or replace the detective products covered by this warranty.