Introduction Thanks for choosing PX Series UPS products! PX Series double conversion online UPS powered by DSP digital control technology and high frequency PWM Inverter technology, output clean and stable AC mains supply, provides comprehensive protection to mission critical equipment, such as computer, communication equipment, medical equipment etc.
Chapter 1 Safety Instruction This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries. Please read all instructions before operating the equipment and save this manual for future reference. Strictly follow the Safety instruction for equipment installation, operation and maintenance, inappropriate operation may cause injury to personnel and equipment.
AC power supply. The PX Series UPS user friendly interface make it easy to use, the small dimension for saving valuable installation space, perfectly meet infrastructure needs in areas of IT, finance, traffic control, manufacturing industry, education and government etc.
Page 9
Input/Output Terminal Output Socket RS232 RS232 AC INPUT AC OUTPUT External Battery Terminal RS232 Input/Output Terminal I/P CB RS232 AC INPUT AC OUTPUT BAT+ BAT- Input Circuit Breaker RS232 Output Terminal Block External Battery LAN(Option) Output socket AC Input connector Input Circuit Breaker RS232 Output Terminal Block...
Page 10
AC Input Circuit Breaker External Battery Connector AC Input/ Output Terminal Block Ethernet Card RS232 USB(Option) (Option) RS232 Mains Input Circuit Breaker Ethernet Card Port (Option) External Battery AC Input & Output Terminal Block Connector Note: 1. The socket and terminal configuration on the rear panel may be slightly different for countries or regions according to order.
Chapter 3 Installation 3.1 Product inspection Unpacking the cabinet, Open the outer carton and remove the accessories Packed in the cabinet. Carefully lift the cabinet out of the outer carton. Note the UPS mode with internal battery is heavy, two person or proper tools should be used to take the equipment out.
Page 12
PX1, 2, 3K LV(110V/120V/127V) Model and PX6K, PX10K, PX6K(LV), PX10K(LV) model use fixed terminal block for input wiring, a ring terminal is recommended for reliable wiring. Note the voltage and current rating of the product. Refer to below table for input wiring Nominal Input Rated Input Input Cable...
Page 13
Output Socket and Terminal with UPS protection 1~3K output socket and terminal 6~20kVA model input and output wiring connector is a ring type terminal block, the wiring should well make with suitable ring type terminal, to make sure the wire is securely fix to the terminal block, loosen or other kind of bad connection make cause over head or even fire accident, which much avoid INPUT...
Page 14
phase or 3phases mains are used, the R Phase wiring should choose big enough cable to carry full rated current of 69A/91A considering bypass operating situation. Input N Input L Input PE OUTPUT INPUT 15K, 20K 1phase input wiring For 15K, 20K model, to work with single phase mains input, just short-circuit input R,S,T terminal and connect 1phase 3wire( L, N, G) to the input terminal as shown in above figure, the UPS will automatically work in single phase input mode.
Page 15
INPUT OUTPUT 120V 220V 240V 6K, 10K_LV Input and output terminal block with silkscreen marking The 6K, 10K_LV need 220/230V Nominal input voltage, typical Line L1, L2 of dual phase 110/120V Low voltage Mains system if suitable. The (optional) maintenance bypass (BYP) is default connected to L2 via a jumper, while user may select other source if only the voltage is 220/230V respect to L1.
Page 16
Output 220V INPUT OUTPUT Single Phase 220V Mode Wiring To have single 220V output, connect the Jumper between terminal H2, H3(default status). Then you can have Dual independent phase between H1& H4. Output 240Vac INPUT OUTPUT Single Phase 240V To have single 240V output, connect the Jumper between terminal H2, H3(default status). Then you can have Dual independent phase between H1&...
Page 17
Please find rated output capacity of product, avoid overload and used wire with sufficient current rating, with refer to below table. Model Nominal Output Voltage Rated output Current Wire for terminal PX1K(HV) 220V/230V/240V >14AWG/2mm PX2K(HV) 220V/230V/240V >14AWG/2mm PX3K(HV) 220V/230V/240V >14AWG/2mm PX1K(LV) 110V/120V/127V >14AWG/2mm...
Page 18
Use only battery bank of correct voltage, check the product rating label for correct information. Choose Wire with sufficient current rated, prepared well the terminal. CHECK THE POLARITY of battery bank, fix wires of correct polarity to the battery bank with proper color and clear label for distinguish the polarity.
Chapter 4 Panel & Operation Guide 4.1 Front panel Bypass BYPASS LINE BATTERY FAULT Fault Indicator Indicator Line Mode Battery Mode Indicator Indicator ENTER MUTE/DOWN TEST/UP ON/OFF ON/OFF SET/ENTER Button Button Up-Page/ Down Page Battery Test /Buzzer Mute Button Button LCD Display Panel...
Page 20
4.1.5 LCD Display Function description Input Source Information Indicates the AC input. Indicate input voltage, input frequency, battery voltage Fault Information Indicates the warning and fault codes. Warning: flashing with warning code. Fault: lighting with fault code Output Information Indicate output voltage, output frequency, load percent, load in VA, load in Watt.
Load Information Indicates overload. Indicates the load level by 0-25%, 26-50%, 51-75% and 76-100%. 0%~25% 26%~50% 51%~75% 76%~100% Mode Operation Information Indicates unit connects to the mains. Indicates load is supplied by utility power. Indicates the AC/DC PFC Rectifier and utility charger circuit is working. Indicates the DC/AC Inverter circuit is working.
well as waveform, UPS will automatically switch to run in battery mode, in which the battery work as energy source, and maintain the stable AC power supply at the output side of the UPS product. In the Battery mode, UPS will beep once every 4s. the user can mute the buzzer beep by the down page(mute) button.
Page 23
Turn off UPS under the Normal mode Press and hold the ON/OFF button for more than 3 second to turn off UPS. If bypass mode is enable, the bypass indicator will be turned on to indicate that UPS is working in bypass mode. In order to cut off the output of the UPS, simply cut off the utility power.
Chapter 5 Maintenance 5.1 Routine Maintain To make sure UPS work normal, appropriate maintenance should be schedule periodical,below items should be checked: Check UPS running status. If the utility power is normal, UPS should work in line mode or in battery mode. And there is no warning or fault indication.
Chapter 6 Trouble shooting When any trouble with UPS, please check the problem refer to the table below first. If the problem cannot be solved, please contact local supplier. 6.1 LCD Warning and Fault Code Fault Description Possible cause and solution code Battery Low UPS start up not success...
7.2 3phases input model Specification Item Model PX10K-3P1 PX10KL-3P1 PX15K-3P1 PX15KL-3P1 PX20K-3P1 PX20KL-3P1 Rated power 10KVA/9KW 15KVA/13.5KW 20KVA/18KW Input system 3phases (L1, L2, L3, N, PE) or 1phases (L, N, PE) Nominal voltage 208/220/230/240Vac Frequency 50Hz/60HZ L-N : 90~300VAC±5VAC AC Input Voltage range L-L: 156~520VAC ±5VAC Frequency range...
7.4 Environmental ITEM Normal range C~ +40 Ambient temperature Environment humidity 0~97%, no condensing no derating for lower than 1000M: Altitude Over 1000m :1% derating for every 100M rise Storage temperature C~+45 7.5 EMC & Safety Regulation ITEM Standard Level IEC61000-4-2 LEVEL4 IEC61000-4-3...