LST FI750/RF/OT Quick Start Manual

LST FI750/RF/OT Quick Start Manual

Wireless multicriteria detector

Advertisement

Quick Links

GENERAL DESCRIPTION
The FI750/RF/OT detector samples the air and the environmental temperature in the protected area; when the environmental smoke quantity,
the temperature level or the thermal variation rate exceeds a certain degree, a fire alarm message is sent to the control panel.
FI750/RF/OT is battery powered and doesn't need any system cabling installation.
1
1
1) LED indicators
2) Battery A
3) Battery B
4) Link program switch
5) Tamper spring (internal)
6) Tamper switch (external)
7) Battery cover
8) Battery cover latch
9) Insulating tab
10) Wall fixing openings
11) Identification tag
12) Identification tag lodgement
13) Magnet test area
14) Base / detector reference marks
15) Safety screw
DEPLOYMENT PROCEDURE
1)
Select a location for the detector. See LOCATION SELECTION.
2)
Unbox the detector from its packaging.
3)
Detach the detector from its base. See INSTALLING / REMOVING THE DETECTOR.
4)
Detach the battery cover from the detector. See BATTERY COVER.
5.1) a) Link the detector to the system (insulating tab extraction).
See LINKING - WAKE-UP - WITH INSULATING TAB.
See LINKING - ONE-BY-ONE - WITH INSULATING TAB.
5.2) a) Power up the detector.
See POWERING UP - FIRST TIME USE - WITHOUT INSULATING TAB.
See POWERING UP - RECOVERY.
b) Link the detector to the system (moving the link program switch).
See LINKING - WAKE-UP - WITHOUT INSULATING TAB.
See LINKING - ONE-BY-ONE - WITHOUT INSULATING TAB.
6)
Reinstall the battery cover on the detector. See BATTERY COVER.
7)
Detach the identification tag from the base adapter. See IDENTIFYING THE DETECTOR.
8)
Install the base adapter. See FIXING THE ADAPTOR BASE.
9)
Install the detector on the base adapter. See INSTALLING / REMOVING THE DETECTOR.
10) Install the identification tag to the base adapter, with all relevant information written / labelled on it. See IDENTIFYING THE DETECTOR.
11) Secure the detector to its base with its safety anti-tamper screw. See INSTALLING THE SAFETY SCREW.
12) Test the detector. See TESTING.
LOCATION SELECTION
Select a location for the detector that conforms to your local applicable safety standards and that is in a good position for sending / receiving
wireless signals to / from the father FI750/RF/W2W, FI750/RF/CWE or FI750/RF/WE network device.
Mount the detector as far as possible from metal objects, metal doors, metal window openings, etc. as well as cable conductors, cables
(especially from computers), otherwise the operating distance may greatly drop.
The FI750/RF/OT must NOT be installed near electronic devices and computer equipment that can interfere with its wireless communication
quality.
Labor Strauss Sicherungsanlagenbau Gmbh - Wiegelestrasse 36 A-1230 Wien Austria
FI750/RF/OT
Wireless Multicriteria Detector
3
2
4
5
11
12
10
10
-- or --
It is advisable to use the FI750/RF/MK survey kit
to locate a good wireless installation location.
6
7
8
13
14
should be removed before construc-
tion, major re-decoration or other dust
producing work is started.
Dust covers MUST be removed before
the system can be made operational.
1
9
15
Picture 1
Dust covers DO NOT provide
complete protection against
contamination:
detectors
www.laborstrauss.com

Advertisement

loading
Need help?

Need help?

Do you have a question about the FI750/RF/OT and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for LST FI750/RF/OT

  • Page 1 GENERAL DESCRIPTION The FI750/RF/OT detector samples the air and the environmental temperature in the protected area; when the environmental smoke quantity, the temperature level or the thermal variation rate exceeds a certain degree, a fire alarm message is sent to the control panel.
  • Page 2 POWERING UP AND LINKING - PRELIMINARY NOTES FI750/RF/OT needs to be powered up with the supplied batteries. Linking is the operation through which FI750/RF/OT is “wirelessly connected” to a FI750/RF/W2W, FI750/RF/CWE or FI750/RF/WE network device. LINKING - WAKE-UP - WITH INSULATING TAB “Wake-up”...
  • Page 3 2) Insert the two supplied batteries into their device’s lodgments. POWERING UP - DEVICE LINKED TO THE SYSTEM Use this procedure when a FI750/RF/OT is successfully linked to its system and you have to extract one or both batteries (e.g. batteries substitution).
  • Page 4 Use only with compatible fire detection and alarm systems. DOP103 WARRANTY FI750/RF/OT All devices are supplied with the benefit of a limited 2 years warranty relating to faulty materials or manufac- EN 54-25:2008 turing defects, effective from the production date indicated on each product. This warranty is invalidated by EN 54-7:2000+A1:2002+A2:2006 mechanical or electrical damage caused in the field by incorrect handling or usage.