Connection Screen - ebm-papst R3G500-AQ33-01 Operating Instructions Manual

Table of Contents

Advertisement

R3G500-AQ33-01

4.5 Connection screen

No.
Conn.
Designation
KL 1
1
L1
KL 1
2
L2
KL 1
3
L3
PE
PE
KL 2
1
NO
KL 2
2
COM
KL 2
3
NC
KL 3
1
RSA
KL 3
2
RSB
KL 3
3 / 10
GND
KL 3
4
Ain1 U
KL 3
5
+ 10 V
Item no. 50813-5-9970 · ENG · Revision 260759 · Release 2022-06-28 · Page 11 / 16
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
Operating instructions
Function / assignment
Mains connection, power supply, phase, see type plate for voltage range
Mains connection, power supply, phase, see type plate for voltage range
Mains connection, power supply, phase, see type plate for voltage range
Earth connection, PE connection
Status relay, floating status contact, make for failure
Status relay, floating status contact, changeover contact, common connection, contact rating, max. 250 VAC/2
A (AC1)/min. 10 mA
Status relay, floating status contact, break for failure
Bus connection RS485, RSA, MODBUS RTU; SELV
Bus connection RS485, RSB, MODBUS RTU; SELV
Signal ground for control interface, SELV
Analogue input 1, set value: 0-10 V, Ri = 100 kΩ, parametrisable curve, only for use as alternative to input
Ain1; SELV
Fixed voltage output 10 VDC, +10 V +/-3 %, max. 10 mA, short-circuit-proof, power supply for ext. devices
(e.g. potentiometer); SELV