Intelligent sounder beacon base

Advertisement

Quick Links

A9097B Intelligent Sounder Beacon Base
Read through these instructions before using this device to ensure correct installation and use!
I. Overview
A9097B Intelligent Sounder Beacon Base is addressable , low power consumption and loop powered to reduce installation
cost. The Intelligent Sounder Beacon Base can be used with a detector. The detector can be mounted directly on the base.
It can be used with a bus-type fire alarm control panel. After receiving a start command given by the fire alarm control
panel following an accident, the Sounder Beacon Base will begin to work. At this moment, the Sounder Beacon Base will give
a dazzling visual alarm signal and a harsh audible alarm signal, to remind the persons on the scene of the accident, the fact that
a fire has occurred on the site, quickly and necessity to take related evacuation measures, thus preventing the fire accident from
becoming a major one.
The Sounder Beacon Base may be used to give audible alarms and flashing alarms at the scenes of accidents. It is
applicable to places like high-rise residential buildings, public places, hotels, amusement buildings, factories, shopping centers,
hospitals, schools, office buildings and stock exchanges, and particularly to the places with a low visibility or the possibility of
generation of smoke.
II. Product features
Meet EN54-3.
It is installed by rotating, it can be installed conveniently and reliably.
It uses multiple super bright red LEDs as light sources for visual display, ensuring a striking display effect.
Set the detector base and Sounder beacon as a whole, it can be equipped with A9030T smoke detector and A9020T
heat detector, single point connection for detector, sounder and LED beacon (saving on both time and installation
costs) , debugged and maintained conveniently.
III.Technical Specification
1. Executive Standard: EN54-3 Type A Sounder
2. Loop input: DC24V(20-28V), ≤2mA(monitoring status), ≤8mA(alarm status)
3. Power consumption: ≤0.2W@DC24V
4. Sound output: ≥73dB(A)@ 1m
5. Flash rate: 1~2Hz
6. Flash color: RED
7. Protection class: IP21C
8. Operating temperature: -10℃~+55℃
9. Material Body: Flame retardant PC/PC+ABS
10.Dimension: φ115mm×H44mm (with bracket) , See Fig.1
11. Weight: about 169g
Version:30144000200413
Relative Humanity: ≤95% (non-condensing)
1
IV. Use and engineering application
1.
Wiring:See Fig.2.The Sounder Beacon Base is subject to a two-wire non-polarity connection: Terminals 1 and 3 are
respectively connected with the terminals L1 and L2 of the loop bus of a compatible fire alarm control panel.
Terminals 2 and 4 are respectively connected with the terminals 2 and 4 of A9020T(Heat Detector) or
A9030T(Smoke Detector).
TERMINALS
FROM CONTROL PANEL
1 PAIR FIRE CABLE
2.
Coding address: The Sounder Beacon Base must be encoded address by a special coder (CODER-F900E) before the
installation. Fig.3 shows the wiring diagram of the Sounder Beacon Base and coder. After wiring, press the "#" key
to select "324" mode, set the coder with the coding function, then select the correct address number and press the
"RUN/STOP" key to complete the address code setup. (Note: See the User's Manual of the coder for the detailed
operation.)
Fig.1
TO NEXT DEVICE
1 PAIR FIRE CABLE
Fig.2
Fig.3