LG GDL1329CGS3 Service Manual page 30

Electric & gas dryer
Table of Contents

Advertisement

WARNING:
!
Connect the power co r d to the terminal block. Each colo r ed wi r e should be connected to
same color sc r e w . Wi r e color indicated on manual is connected to the same color sc r ew
in block. Failu r e to follow these instructions may r esult in a short or overload.
G r ounding th r ough the neutral conductor is p r ohibited for: (1) new branch-ci r cuit
installations, (2) mobile homes, (3) r ec r eational vehicles, and (4) a r eas whe r e local
codes p r ohibit g r ounding th r ough the neutral conducto r .
• A 4-wire connection is required for all mobile
and manufactured home installations, as well
as all new construction after January 1, 1996.
• A UL-listed strain relief is required.
Remove the terminal block access cover
on the upper back of the dryer. Install a
UL-listed strain relief into the power cord
through-hole; then thread a UL-listed, 30A,
240V, 4-wire, #10 AWG-minimum copper
conductor power cord through the
strain relief.
Terminal
Block
UL-Listed
Strain Relief
UL-Listed
4-Wire
Power Cord
30
• Use a 30-amp, 240V, UL-listed power cord
with #10 AWG-minimum copper conductor
and closed loop or forked terminals with
upturned ends.
Hot
(Black)
Ground Screw
Power Cord
Ground Wire
Transfer the dryer's ground wire from behind
the green ground screw to the center screw
of the terminal block. Attach the two hot
leads of the power cord to the outer terminal
block screws. Attach the white neutral wire
to the center terminal block screw. Attach the
power cord ground wire to the green ground
screw. TIGHTEN ALL SCREWS SECURELY.
Reinstall the terminal block access cover.
Neutral
Hot
(White)
(Red)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents