Global Fire Equipment GFE-DHA V2 Manual

Addressable magnetic door holder

Advertisement

Quick Links

Sítio dos Barrabés, Armazém Nave Y, Caixa Postal 908-Z, 8150-016 São Brás de Alportel - PORTUGAL | Tel: +351 289 896 560
Email: info@globalfire-equipment.com | Technical Support: techs@globalfire-equipment.com | www.globalfire-equipment.com
SUPPLY VOLTAGE / ADDRESS RANGE
LOOP CURRENT - QUIESCENT / CHARGING
ISOLATOR - LOOP LINE RESISTANCE
SLEEP MODE CONSUMPTION
CHARGE UP TIME / FAIL SAFE RELEASE TIME
MANUAL RELEASE / MAX. CABLE SIZE
MAX. HUMIDITY
OPERATING TEMPERATURE
MAGNETIC FORCE
DIMENSIONS
WEIGHT
GFE-DHA V2
GFE-DHA V2
ADDRESSABLE MAGNETIC
DOOR HOLDER
GLOBAL FIRE EQUIPMENT S.A.
TECHNICAL SPECIFICATIONS
Loop Powered - 17V DC to 30V DC / 1-125
800 uA (650 uA module + 150 uA isolator) / 7 mA
60 mOhms
28 ~ 60 uA
25s / 30s - (Fail Safe Release Time is defined as the time taken to release door after removal of loop
power or loss of communication with control panel is detected)
Push Button - Normally Open / 2.5 mm
95% RH Non-Condensing
0ºC to 50ºC
200 N
Magnet: 112.5 (H) x 84.2 (W) x 46.8 (D) mm; Keeper: 55 (H) x 55 (W) x 50 (D) mm
746g (complete boxed); 139g (Keeper); 580g (Magnet w/ module)
ORDER CODE
ADDRESSABLE MAGNETIC DOOR HOLDER
CONNECTION DETAILS
2
MANUAL 220719
MADE IN PORTUGAL - EU

Advertisement

loading
Need help?

Need help?

Do you have a question about the GFE-DHA V2 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Global Fire Equipment GFE-DHA V2

  • Page 1 DOOR HOLDER MADE IN PORTUGAL - EU GLOBAL FIRE EQUIPMENT S.A. Sítio dos Barrabés, Armazém Nave Y, Caixa Postal 908-Z, 8150-016 São Brás de Alportel - PORTUGAL | Tel: +351 289 896 560 Email: info@globalfire-equipment.com | Technical Support: techs@globalfire-equipment.com | www.globalfire-equipment.com...
  • Page 2 Battery Jumper fitting: ● This new model should not be connected to the loop wires without fitting on the battery jumper. The module does not work properly if that is forgotten. ● If the DHA is connected to the loop wires without the jumper, a fault (2) will be reported to the panel, to avoid unnecessary faults and ensure that the module is connected correctly.
  • Page 3: Loop Connections

    Conventional Mode or Conventional DHA Device To activate the conventional mode, with the jumper removed, enter the address 0 in the dip switch. Insert the battery jumper. The Green and Red LEDs start to flash simultaneously. Connect the DHA to 24V on the (LOOP in) plug. After this step, the DHA will report the status of the door and battery charge through the LEDs indicated in the table below.
  • Page 4 PROGRAMMING MODES ALARM DOOR ATTACHMENT MONITOR (For addressable version only) To Enable or Disable Alarm attachment monitor function: (this function is disabled by default). This function, in the event of an alarm (fire or evacuation) will monitor the status of the door, in case something or someone insists on keeping the door open (attached to the magnet).
  • Page 5: Address Settings

    D.I.L. SWITCHES CONFIGURATION Address Switches binary weights Switches 1-7 1 ON =1 4 ON =8 7 ON =64 Used to configure the module’s address. 2 ON =2 5 ON =16 Switch 8 Programming mode. 3 ON =4 6 ON =32 ADDRESS SETTINGS MORE INFO >>...