Appendix A.
In the Navigation tree, click on Setup. Click on File Transfer. Then click on the General
Tab.
Then click on browse and select the bdt.ini file.
Click on submit.
When the download is complete, power cycle the unit.

Appendix A.5. LED Diagnostics for Serial Communications Between ET9500 and Devices

SPL
RUN
ERR
RX
TX
PWR
Diagnostic LEDs
Tag
The SPL LED will light if the ET9500 is off line.
The RUN LED will start flashing 20 seconds after power indicating normal operation.
The SYS ERR LED will go on solid 15 seconds after power up. It will turn off after 5
seconds. A steady red light will indicate there is a system error on ET9500
Not used – ignore
Not used – ignore
This is the power light and should show steady green at all times when ET9500 is
powered.
Figure 22: Diagnostic LEDs
Description
— 21 —
Troubleshooting